1
I56-0002-002
12/10/2018
For use with the following models:
Wall Speakers: SPSRL, SPSWL, SPSRL-P, SPSWL-P, SPSRL-SP, SPSWL-CLR-ALERT
Ceiling Speakers: SPSCRL, SPSCWL, SPSCWL-P, SPSCWL-SP, SPSCWL-CLR-ALERT
PRODUCT SPECIFICATIONS
Standard Operating Temperature:
32°F to 120°F (0°C to 49°C)
Humidity Range:
10 to 93% Non-condensing
Nominal Voltage (speakers):
25 Volts or 70.7 Volts
Maximum Supervisory Voltage:
50 VDC
Speaker Frequency Range:
400 – 4000 Hz
Power Settings:
¼, ½, 1, 2 Watts
Input terminal wire gauge:
12 to 18 AWG
Strobe Flash Rate:
1 flash per second
Nominal Voltage (strobes):
Regulated 12VDC, regulated 24VDC or FWR
Operating Voltage Range (includes fire alarm
panels with built in sync):
8 to 17.5V (12V nominal) or 16 to 33V (24V nominal)
Operating Voltage with MDL3 Sync Module:
8.5 to 17.5V (12V nominal) or 16.5 to 33V (24V nominal)
DIMENSIONS FOR PRODUCTS AND ACCESSORIES
MOUNTING BOX OPTIONS
WALL PRODUCTS
Length
Width
Depth
SPEAKER STROBES
Wall Speaker Strobe
6.5" (165 mm)
5.00" (127 mm)
2.30" (58.4 mm)
SBBSPRL/WL (wall), SBBCRL/WL (ceil-
ing), 4" x 4" x 2
1
/
8
"or deeper (When
using 12AWG, 14 AWG, or adding extra
wires in the box, a deeper box or exten-
sion ring is recommended.)
CEILING PRODUCTS
Length
Width
Depth
Ceiling Speaker Strobe
6.8" (173 mm)
N/A
2.87" (73mm)
WALL SURFACE MOUNT BACK BOX
Length
Width
Depth
Speaker Strobe with SBBSPRL/WL Surface
Mount Back Box
6.62" (168mm)
5.12" (130 mm)
2.30" (58.4 mm)
CEILING SURFACE MOUNT BACK BOX
Diameter
Depth
Speaker Strobe with SBBCRL/WL Surface
Mount Back Box
6.92" (176 mm)
5.37" (116mm)
NOTICE:
This manual shall be left with the owner/user of this equipment.
BEFORE INSTALLING
Please read the System Sensor Voice Evacuation Application Guide, which
provides detailed information on speaker notification devices, wiring and
special applications. Copies of this manual are available from System Sensor.
NFPA 72 and NEMA guidelines should be observed. System Sensor also rec-
ommends installing fire alarm speakers in compliance with NFPA 72, ANSI/
UL 1480 and NEC 760
Important:
The notification appliance used must be tested and maintained
following NFPA 72 requirements.
GENERAL DESCRIPTION
System Sensor series of notification appliances offer a wide range of audible
and visible devices for life safety notification. Our indoor speaker strobes
come with 7 field selectable candela setting. The strobe portion is designed
to be used in 12 VDC, 24VDC, or 24V FWR (full wave rectified) systems. The
speaker is designed to be used at either 25 or 70.7 volts, and operate at any
one of four input power levels. Our speaker strobes are suitable for dry and
damp environments. These products are electrically backwards compatible
with previous generation of System Sensor speaker strobes. With its low total
harmonic distortion, the System Sensor SPL series offers high fidelity sound
output.
Speakers Strobes are public mode notification appliances intended to alert oc-
cupants of a life safety event. The speaker is listed to ANSI/UL 1480 (public
mode) and the strobe is listed to ANSI UL 1638 (public mode).
FIRE ALARM SYSTEM CONSIDERATIONS
System Sensor also recommends installing fire alarm speakers in compliance
with NFPA 72, ANSI/UL 1480 and NEC 760.
SYSTEM DESIGN
The system designer must make sure that the total current drawn by the de-
vices on the loop does not exceed the current capability of the panel supply,
and that the last device on the circuit is operated within its rated voltage. The
current draw information for making these calculations can be found in the
tables within this manual. For convenience and accuracy, use the voltage drop
calculator on the System Sensor website (www.systemsensor.com).
When calculating the voltage for the last device, it is necessary to consider
the voltage drop due to the resistance of the wire. The thicker the wire, the
smaller the voltage drop. Note that if Class A wiring is installed, the wire
length may be up to twice as long as it would be circuits that are not fault
tolerant. The total number of strobes on a single NAC must not exceed 69 for
24 volt applications.
AVAILABLE CANDELA SETTINGS
System Sensor offers a wide range of candela settings for your life safety
needs. In order to select your candela output, adjust the slide switch on the
rear of the product to the desired candela setting on the selector switch. (See
Figure 1.)
The candela setting can also be verified by looking into the small window
on the front of the unit. See Tables 1 and 2 for candela settings for wall and
ceiling products. All products meet the light output profiles specified in the
appropriate UL Standards. (See Figures 2–4.)
INSTALLATION AND MAINTENANCE INSTRUCTIONS
Selectable Output Speaker Strobes
– Wall and Ceiling Mount
3825 Ohio Avenue, St. Charles, Illinois 60174
800/736-7672, FAX: 630/377-6495
www.systemsensor.com
I56-000
2-00
2