background image

Smoke Detector Spacing on Level Ceilings with Beams and Joists

 

System Sensor. Advanced Ideas. Advanced Solutions. 

3

and Vision Systems Ltd. using Fire Dynamics Simulator and Smokeview Version 
4

1

 (developed by the National Institute of Science and Technology). The results of 

this research were published in a report entitled, “Smoke Detector Performance 
for Level Ceilings with Deep Beams and Deep Beam Pocket Configurations.”

2

 The 

report was issued March 28, 2006 and was the basis for recommended changes to 
NFPA 72.

Based on a variety of modeled flaming fire scenarios, the results of this 
study indicate:

There is no technical basis for the NFPA 72 2002 edition requirement 
for  placing  smoke  detectors  in  every  beam  pocket  when  ceilings  are 
greater than 12 feet in height and/or beams are greater than 12 inches 
in depth.

The smooth ceiling 30-foot spacing guideline of NFPA 72, with permitted 
increases for narrow space geometry, allows smoke detectors to extend 
to approximately 41 feet on-center and along a corridor. For ceilings up to 
24 feet in height, the deep-beam configurations do not negatively affect 
expected  performance.  This  means  that  for  corridor  conditions,  spot 
smoke detectors can be effectively used with deep beams at spacings for 
smooth ceilings.

Standard 900-square-foot smoke detector spacing is adequate for waffle 
or pan type ceilings up to 24 feet in height and for beams up to 24 inches 
in depth that are spaced no greater than 12 feet on center. 

Spot smoke detectors may be placed on the bottom of the beams or in 
the beam pocket without any significant difference in performance.

The concern about mounting smoke detectors a minimum of 12 inches 
from a ceiling-beam corner, per NFPA 72, is unsubstantiated. The CFD 
modeling  showed  no  stagnant  areas  in  the  beam  pockets  that  would 
preclude  smoke  detector  activation.  Although  the  modeling  results 
showed no stagnant zones, it does not suggest that spot detectors can 
be installed in close proximity or contact to the wall or ceiling surface. 
The  research  report  notes  that  such  close  mounting  may  impact  the 
airflow  characteristics  into  and  around  the  detector  housing,  which 
could  have  a  negative  impact  on  how  smoke  flows  into  a  detector’s 
sensing chamber. 

1

 The CFD software is available free of charge from the NIST web site: www.fire.nist.gov/fds.

2

 The full report is available on the National Fire Protection Association web site: www.nfpa.org.

A recent analysis shows 
no basis for many of the 
spacing requirements in the 
2002 edition.

Отзывы: