7.  Slide the actuating arm into the valve until it bottoms 

 on the flag, but do not tighten the lever screw.

8.  Open the valve to the full open position and tighten the 

 lever screw to hold actuating arm in position. (Actuat- 
 ing arm length will adjust slightly as valve is opened.) 
 Check to ensure that in the full open position the actu- 
 ating arm is not resting on the nipple. 

9.  Carefully  close  valve  and  note  the  number  of  handle 

 revolutions until the switch trips. The switch must trip 
 within 

1⁄5

 of the total travel range of the valve.

10. Wire the switch as shown in Fig. 3.
   

NOTE: 

When removing the cover of the PIBVEXP use  

 provided allen wrench in box.

Figure 2:

Figure 3:

SUP. SWITCH 

 

 

   SUP. SWITCH

TO NON-SILENCEABLE

INITIATING ZONE OF 

LISTED FACP

END OF LINE

RESISTOR

TYPICAL FACP CONNECTION

TO POWER SOURCE

COMPATIBLE WITH BELL

TYPICAL LOCAL BELL CONNECTION

LOCAL

BELL

BREAK WIRE AS SHOWN FOR SUPERVISION

OF CONNECTION. DO NOT ALLOW STRIPPED 

WIRE  LEADS  TO  EXTEND  BEYOND  SWITCH 

HOUSING. DO NOT LOOP WIRES.

TO

O

P

EN

CLOSE

CLOSE

W0244-00

W0245-00

W0246-00

W0247-00