FIGURE 7. SYSTEM WIRING DIAGRAM FOR 4-WIRE DUCT SMOKE DETECTORS:

CAUTION

Do not loop wire under terminals when wiring detectors. Break wire runs to provide system supervision of connections.

24VAC/DC

9

10

AUXILIARY CONTACTS

FOR FAN SHUTDOWN, ETC. (NOTE 2)

16

6

17

8

18

7

N.O.

C.

N.C.

N.O.

C.

N.C.

16

6

17

8

18

7

N.O.

C.

N.C.

N.O.

C.

N.C.

SUPERVISORY CONTACTS

(NOTE 3)

24V

9

10

AUXILIARY CONTACTS

FOR FAN SHUTDOWN, ETC. (NOTE 2)

SUPERVISORY CONTACTS

(NOTE 3)

SUP N.O.

SUP C

SUP C

SUP N.O.

4

5

ALARM

INITIATION

CONTACTS

(NOTE 4)

4

5

ALARM

INITIATION

CONTACTS

(NOTE 4)

ALARM

INITIATION

LOOP

UL/FM LISTED

4-WIRE

CONTROL PANEL

+

120

VAC

120

VAC

OR

OR

AUX A

AUX B

AUX A

AUX B

ALARM N.O.

ALARM N.O.

ALARM C

ALARM C

3

3

14

14

FIRST DETECTOR IN THE LOOP

POWER INPUTS (NOTE 1)

POWER INPUTS (NOTE 1)

LAST DETECTOR IN THE LOOP

EOL RESISTOR 

SPECIFIED BY 

PANEL 

MANUFACTURER

NOTE 1:

 24V Power Inputs accept a non-polarized 24VDC or 24VAC 50-60Hz. 

120VAC Power Inputs accept only 120VAC 50-60Hz. Connect power source to 
appropriate terminals of each detector. See specifications for additional power 
supply information.

NOTE 2:

 Auxiliary contacts shown in standby position. Contacts switch dur-

ing alarm as indicated by arrows. Auxiliary contacts are not to be used for 
connection to the control panel. See specifications for contact ratings.

NOTE 3:

 Supervisory contacts shown in standby position. Open contacts indi-

cate a trouble condition to the panel. See specifications for contact ratings.

NOTE 4:

 Alarm Initiation contacts shown in standby position. Closed contacts 

indicate an alarm condition to the panel. See specifications for contact ratings.

H0558-07

Designation

Default

Selection

Features

TRBL SHUTDN

OFF

OFF

Aux relay does not switch states with a Trouble condition

ON

Aux relay switches states with a Trouble condition

SENSORS

1

1

Only one sensor is connected the Power Board

2

Two sensors are connected to the Power Board

MIN TMPR 

DELAY

7

7

Provides a Trouble condition ( terminals 3 and 14 open) when Sensor Housing cover has 

been removed or has been secured improperly for more than 7 minutes

0

Provides an instantaneous Trouble condition(terminals 3 and 14 open) upon cover removal

TABLE 2. DIP SWITCH SETTINGS:

[10] DETECTOR STATUS INDICATION

Detector Staus is indicated by the LED sensor, and the correcsponding LED on
the power board. The power board has two separate LED’s to indicate the sta-
tus of each sensor connected to it. Refer to Table 3 on page 8 for more details.

[11] INTERCONNECTION (MULTIPLE FAN SHUT DOWN)

When using the interconnect feature, an alarm from an initiating device will
switch the Aux Relays on the other devices interconnected.

I56-2967-008R 

21

/0

9

/2020

Amended by Pertronic Industries, 

21 September 2020 (DST1 not available in Australia and New Zealand)

Содержание PERTRONIC Innovair flex D4120

Страница 1: ...20 mA RMS 120 VAC 60 Hz Max alarm current 65 mA 24 VDC 135 mA RMS 24 VAC 60 Hz 35 mA RMS 120 VAC 60 Hz CONTACT RATINGS Alarm initiation contacts SPST 2 0A 30 VDC resistive Alarm auxiliary contatcs DPD...

Страница 2: ...ity in the duct 5 2 DETERMINE MOUNTING LOCATION AND CONFIGURATION On ducts wider than 18 inches it is recommended that the detector be mounted downstream of a bend obstruction in the duct or the suppl...

Страница 3: ...s in the protrud ing section of tube Be sure to seal the duct where the tube protrudes FIGURE 4 DETECTOR 3 4 HOLE 12 1 4 2 H0215 00 NOTE Air currents inside the duct may cause excessive vibration espe...

Страница 4: ...th previously sold detectors 9 Unit Configuration 9 UNIT CONFIGURATION A three position Dip Switch is included only on the D4P120 in order to con figure the setup of the unit One switch is used to det...

Страница 5: ...or contact ratings NOTE 3 Supervisory contacts shown in standby position Open contacts indi cate a trouble condition to the panel See specifications for contact ratings NOTE 4 Alarm Initiation contact...

Страница 6: ...sensor and the power board should latch on as should any accessories i e RA400Z RA100Z RTS451 RTS151 Verify system control panel alarm status and control panel execution of all in tended auxiliary fu...

Страница 7: ...ust be limited to 25 ohms or less per interconnecting wire If a system control panel is used the panel itself may require testing 15 2 RTS2 RTS2 AOS MULTI SIGNALING ACCESSORY The RTS2 and RTS2 AOS mul...

Страница 8: ...r every 1 second Supervisory relay Terminals 3 and 14 are closed Alarm Relay Terminals 4 and 5 are open Aux Relay does not switch states Terminals 6 and 16 are closed Terminals 8 and 18 are closed Mai...