System Sensor PERTRONIC Innovair flex D4120 Скачать руководство пользователя страница 1

D4120 Duct Smoke Detector

D4S Sensor Component

D4P120 Power Board Component

INSTALLATION AND MAINTENANCE INSTRUCTIONS

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

TABLE OF CONTENTS 

PAGE

[1] Limitations of Duct Smoke Detectors. . . . . . . . . . . . . . . . . . . . . . . . . . 1
[2] Exploded View of Duct Smoke Detector Components   . . . . . . . . . . . . . 2
[3] General Description   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
[4] Contents of Duct Smoke Detector Kit. . . . . . . . . . . . . . . . . . . . . . . . . . 2
[5] Detector Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
[6] Sampling Tube Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
[7] Measurement Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
[8] Field Wiring Installation Guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . 4
[9] Unit Configuration  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
[10] Detector Status Indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
[11] Interconnection (Multiple Fan Shut Down). . . . . . . . . . . . . . . . . . . . . 6
[12] Verification of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
[13] Detector Cleaning Procedures  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
[14] Sensor replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
[15] Optional Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  8

 

BEFORE INSTALLING

Read System Sensor’s 

Applications Guide for Duct Smoke Detectors 

(

HVAG53

)

, which provides information on detector spacing, placement, 

zoning, wiring, and special applications. This manual is available online at 
www.systemsensor.com. NFPA Standards 72 and 90A should also be refer-
enced for detailed information. 

NOTICE:

 This manual shall be left with the owner/user of this equipment.

I56-2967-008R

NOTE:

 The D4120 duct detector consists of D4P120 Power Board component and the D4S Sensor component.

SPECIFICATIONS 

Operating Temperature: 

D4120 & D4S: –4° to 158° F (–20° to 70° C) D4P120: –40° to 158° F (–40° to 70° C)

Storage Temperature: 

D4120 & D4S: –22° to 158° F (–30° to 70° C) D4P120: –40° to 158° F (–40° to 70° C)

Humidity: 

0% to 95% Relative Humidity Non-condensing

Air Velocity: 

100 to 4000 ft./min. (0.5 to 20.3 m/sec.)

D4120 Footprint Dimensions: 

Rectangular - 14.38 in L x 5 in W x 2.5 in D (37cm L x 12.7cm W x 6.36cm D)
Square - 7.75 in L x 9 in W x 2.5 in D (19.7cm L x 22.9cm W x 6.35cm D)

D4S/D4P120 Footprint Dimensions: 7.75 in L x 5 in W x 2.5 in D (19.7cm L x 12.7cm W x 6.35cm D)
D4120 Weight: 

2.5 pounds; 1.14 kg

Electrical

Power supply voltage: 

20-29 VDC

24 VAC 50-60-Hz 

120 VAC 50-60 Hz

Input capacitance: 

270 µF max. 

270 µF max. 

N/A

Reset Voltage: 

3.0 VDC min. 

2.0 VAC min. 

10 VAC min.

Reset Time (with RTS451/RTS151):  .03 to 0.3 sec. 

.03 to 0.3 sec. 

.03 to 0.3 sec.

Reset Time (by power down): 

0.6 sec. max. 

0.6 sec. max. 

0.6 sec. max.

Power Up Time: 

35 sec. max. 

35 sec. max. 

35 sec. max.

Alarm response time: 

15 sec. 

15 sec. 

15 sec.

Sensitivity Test: 

See detector label 

See detector label 

See detector label

Current Requirements (Using No Accessories)

Max. standby current 

21 mA @ 24 VDC 

65 mA RMS @ 24VAC 60Hz 

20 mA RMS @ 120 VAC 60 Hz

Max. alarm current 

65 mA @ 24 VDC 

135 mA RMS @ 24 VAC 60 Hz 

35 mA RMS @ 120 VAC 60 Hz

CONTACT RATINGS

Alarm initiation contacts (SPST)

2.0A @ 30 VDC (resistive)

Alarm auxiliary contatcs (DPDT) 10A @30 VDC (resistive) 

10A @250 VAC (resistive)

1

/

2

 HP @240 VAC

1

/

4

 HP @120 VAC

NOTE: Alarm auxiliary contacts shall not be connected to initiating circuits of 

control panels. Use the alarm initiation contact for this purpose.

Supervisory Contacts (SPDT)

2.0A @ 30 VDC (resistive)
2.0A @ 125 VAC (resistive)

ACCESSORY CURRENT LOADS AT 24 VDC

DEVICE

STANDBY

TROUBLE

ALARM

APA151/APA451

12.5mA

n/a

30mA Max.

MHR/MHW

0mA

n/a

29mA Max.

RA400Z/RA100Z

0mA

n/a

12mA Max.

RTS451/RTS151

0mA

n/a

12mA Max.

RTS451KEY/RTS151KEY

12mA

n/a

12mA Max.

RTS2

3mA Max.

16mA Max.

30mA Max.

RTS2-AOS

3mA 

16mA Max.

55mA Max.

NOTE: Any combination of accessories may be used such that the given accessory 
loads are: 110mA or less at the Aux output, and 50mA or less at the Alarm output.

IMPORTANT:

 This detector must be tested and maintained regularly following 

NFPA 72 requirements. The detector must be tested an maintained regularly fol-
lowing NFPA 72 requirements.  According to NFPA, the detector should be visu-
ally inspected semiannually and functionally tested at least once a year.  This 
may need to be more frequent depending on the air quality of the duct supply air.

[1] LIMITATIONS OF DUCT SMOKE DETECTORS

WARNING

The National Fire Protection Association has established that DUCT DETEC-
TORS MUST NOT BE USED AS A SUBSTITUTE FOR OPEN AREA DETECTOR 
PROTECTION as a means of providing life safety. Nor are they a substitute for 
early warning in a building’s regular fire detection system.
System Sensor supports this position and strongly recommends that the user 
read NFPA Standards 90A, 72, and 101. The D4120 Air Duct Smoke Detectors 
are listed per UL 268A.
This device will not operate without electrical power. Fire situations may 
cause an interruption of power. The system safeguards should be discussed 
with your local fire protection specialist.
This device will not sense smoke unless the ventilation system is operating 
and the cover is installed.
For this detector to function properly, it MUST be installed according to the in-
structions in this manual. Furthermore, the detector MUST be operated within 
ALL electrical and environmental specifications listed in this manual. Failure 
to comply with these requirements may prevent the detector from activating 
when smoke is present in the air duct.

I56-2967-008R 

21

/0

9

/2020

Amended by Pertronic Industries, 

21 September

 20

20

 (DST1

 not available in Australia and New Zealand)

For Australia and New Zealand

Содержание PERTRONIC Innovair flex D4120

Страница 1: ...20 mA RMS 120 VAC 60 Hz Max alarm current 65 mA 24 VDC 135 mA RMS 24 VAC 60 Hz 35 mA RMS 120 VAC 60 Hz CONTACT RATINGS Alarm initiation contacts SPST 2 0A 30 VDC resistive Alarm auxiliary contatcs DPD...

Страница 2: ...ity in the duct 5 2 DETERMINE MOUNTING LOCATION AND CONFIGURATION On ducts wider than 18 inches it is recommended that the detector be mounted downstream of a bend obstruction in the duct or the suppl...

Страница 3: ...s in the protrud ing section of tube Be sure to seal the duct where the tube protrudes FIGURE 4 DETECTOR 3 4 HOLE 12 1 4 2 H0215 00 NOTE Air currents inside the duct may cause excessive vibration espe...

Страница 4: ...th previously sold detectors 9 Unit Configuration 9 UNIT CONFIGURATION A three position Dip Switch is included only on the D4P120 in order to con figure the setup of the unit One switch is used to det...

Страница 5: ...or contact ratings NOTE 3 Supervisory contacts shown in standby position Open contacts indi cate a trouble condition to the panel See specifications for contact ratings NOTE 4 Alarm Initiation contact...

Страница 6: ...sensor and the power board should latch on as should any accessories i e RA400Z RA100Z RTS451 RTS151 Verify system control panel alarm status and control panel execution of all in tended auxiliary fu...

Страница 7: ...ust be limited to 25 ohms or less per interconnecting wire If a system control panel is used the panel itself may require testing 15 2 RTS2 RTS2 AOS MULTI SIGNALING ACCESSORY The RTS2 and RTS2 AOS mul...

Страница 8: ...r every 1 second Supervisory relay Terminals 3 and 14 are closed Alarm Relay Terminals 4 and 5 are open Aux Relay does not switch states Terminals 6 and 16 are closed Terminals 8 and 18 are closed Mai...

Отзывы: