background image

D900-05-00

1

I56-496-16

MA12/24D* Electronic Sounder,

SS12LO, SS24LO*, SS24M*

Electronic Strobe, MASS12LO,

MASS12M, MASS24LO*, MASS24M*

Sounder/Strobe Combined

*ULC models add suffix “A”; strobes and sounder/strobes available in 24VDC only

INSTALLATION AND MAINTENANCE INSTRUCTIONS

A Division of Pittway

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

General Description

The National Fire Protection Association has published standards
and recommended practices for the installation and use of the
listed appliances. It is recommended that the installer be familiar
with these requirements, with local codes, and any special re-
quirements of the authority having jurisdiction.

The electronic Multi-Alert sounder and the signaling strobe are in-
tended to be connected to the alarm indicating circuit of a listed
fire alarm control panel. Both are compatible with DC line super-
vision. The model MA12/24D is suitable for connection to either a
12 or 24 volt panel. Models SS24LO, SS24M, MASS24LO and
MASS24M require 24 volt panels; models SS12LO, MASS12LO and
MASS12M require 12 volt panels. Horn, strobe, or combination
strobe models may be used with panels that have full wave recti-

Sound (Hz)

Clips on Tabs

Current (mA) 

( Note 1)

Output (dBA)

UL (dBA) Ratings

( Note 4)

DC Regulated/

(Note 2)

(Note 3)

FWR Unfiltered

12V

24V

30V

12V

24V

12V

24V

Slow Whoop

ABC

21/40

38/56

46/72

85

92

79

85

800 Continuous

BC

15/24

28/45

35/55

87

93

79

85

800/1000 Alternating

AC

17/32

34/46

43/58

85

92

79

85

2400 Interrupted

AB

19/23

35/56

43/64

89

90

79

85

2400 Continuous

C

21/31

38/59

46/73

85

94

79

85

1200 Interrupted

B

13/19

23/33

27/41

85

91

75

82

Swept Frequency

A

17/24

34/47

43/60

85

92

79

85

Fast Warble

NONE

15/27

30/47

38/59

85

92

79

85

Note 1:

Total current for horn/strobe combinations = horn c
strobe current; refer to tables 1 and 2.

Note 2:

Sound output measured in anechoic room at 10 feet.

Note 3:

Sound output measured in UL reverberant room.

Note 4:

See Figure 4 for tab clip removal & storage.

Note 5:

All horn or combination strobe models can be powered using
full wave rectified unfiltered supplies.

Under no circumstances can
the SS24 or MASS24 input volt-
age exceed 33 VDC or be less
than 18 VDC. Under no cir-
cumstances can the SS12 or
MASS12 input voltage exceed
18.7 VDC or be less than 9.6
VDC. Under no circumstances
can the MA12/24D input volt-
age exceed 33 VDC or be less
than 9.6 VDC.

Table 2. Sound output and current ratings for the MA12/24D:

Model

Supply

Operating

Operating Current

Peak

Minimum Output

Voltage

Current from

from Rectified

Current

@ 100% Viewing

Regulated Supply

Unfiltered Supply

Angle (see Fig. 3)

(VDC)

(mA)

(mA, RMS)

(mA)

(Candela)

SS12LO

12-17

50

80

550

1.5

SS24LOA

22.5-30

(.22@-35

o

 C)

SS24MA

22.5-30

(5.9 @-35

o

 C)

SS24LO

22.5-30

25

45

225

1.5

(.22@-35

o

 C)

SS24M

22.5-30

75

125

450

15

(5.9 @-35

o

 C)

Table 1. SS12/24 electrical and light ratings:

fied, unfiltered supplies. The MA12/24D sounder and MASS12/24
sounder/strobes are suitable for outdoor applications (–35

°

C to

66

°

C) when used with a Weatherproof Back Box (Model WBB) as

tested by UL. In Canada, rigid steel conduit must be used when
installing the Weatherproof Back Box. The light output of the
SS12LO, SS24LO, MASS12LO and MASS24LO is 1.5 cd min
@100% viewing angle. The light output of the SS24M, MASS12M,
and MASS24M is 15 cd min @100% viewing angle (See Figure 3).

There are eight different sounds which can be selected on the
electronic sounder by adding or removing tab clips (see Figure 4).
The sound selected will determine the maximum current and
sound power output per device. See Table 2 for these values.

Technical Manuals Online! - http://www.tech-man.com

Содержание MA12D

Страница 1: ... 27 30 47 38 59 85 92 79 85 Note 1 Total current for horn strobe combinations horn current strobe current refer to tables 1 and 2 Note 2 Sound output measured in anechoic room at 10 feet Note 3 Sound output measured in UL reverberant room Note 4 See Figure 4 for tab clip removal storage Note 5 All horn or combination strobe models can be powered using full wave rectified unfiltered supplies Under ...

Страница 2: ...ions within a room Addi tional sounders may be needed to ensure sound output level com plies with NFPA requirements WARNING Limitations Of Sounder Strobes The sounder and or strobe will not work without power The sounder strobe gets its power from the fire security panel monitoring the alarm system If power is cut off for any reason the sounder strobe will not pro vide the desired audio or visual ...

Страница 3: ... VDC VDC Figure 5 Multi Alert Sounder From panel or previous device To Next Device or EOL VDC VDC Figure 6 Strobe only SS Series only A78 2467 01 From panel or previous device To Next Device or EOL VDC VDC Note Use uncoded supply only INOUT STROBE ONLY INOUT INOUT STROBE ONLY INOUT Figure 7 Multi Alert Sounder and Strobe Multi Alert Sounder and Strobe operating in tandem A78 1137 01 From panel or ...

Страница 4: ...screws C and nuts D 2 Complete field wiring See Fig 5 3 Screw plate sounder to box with screws F 1 Plaster ring should be properly mounted to electrical box with screws supplied with box 2 Screw plate to plaster ring with screw G 3 Complete field wiring See Fig 5 7 and 8 4 Screw sounder or sounder strobe to plate with screw A 5 Fill remaining holes with screw B A78 1137 08 A78 1137 20 C F F C MP F...

Страница 5: ...plies Under no circumstances can the MA12 24D input Table 1 SS12 24ADA Series electrical ratings Model Supply Voltage Range Operating Current from Regulated Supply Operating Current from Full Wave Rectified Unfiltered Supply Average Operating Current Peak Current mA 20 30V Peak Current mA 10 5V 17V Inrush Current mA in access of Peak Average Operating Current mArms Peak Current mA 20Vrms 30Vrms Pe...

Страница 6: ...ast once every three seconds meets or exceeds current Un derwriters Laboratories standard 1971 and uses an extremely reliable xe non flash tube The visual warning signal is suitable for direct viewing and must be installed within an area where it can be seen by building occu pants The strobe must not be installed in direct sunlight or areas of high light intensity over 60 foot candles where the vi...

Страница 7: ...ELECT DESIRED TONE COVER SLOT TAB A TAB B TAB C FOR STORING UNUSED CLIPS SLIDE COVER BACK TO ALIGN COVER SLOT WITH CLIP STORAGE POST SLIDE COVER FOR CLIP STORAGE USE A SMALL BLADED SCREWDRIVER TO REMOVE CLIPS TONE SELECTION TABS Figure 2 Figure 3 Multi alert sounder Figure 4 Strobe Figure 5 Multi alert sounder and strobe operating in tandem From panel or previous device To Next Device or EOL VDC V...

Страница 8: ...te to box with screw A 1 Screw sounder to plate 2 Complete field wiring 3 Screw plate sounder to box with screw F 1 Plaster ring should be properly mounted to electrical box with screws supplied with box 2 Screw plate to plaster ring with screw G 3 Complete field wiring 4 Screw sounder strobe to plate with screw A 5 Fill remaining holes with screw B B A A B Signal Strobe Standard Backbox TOP MA 12...

Страница 9: ...h current du ration is less than 20 m i c r o s e c o n d s 00002 seconds Table 2 Sound output and current ratings for the MA12 24D Sound Hz Clips on Current mA Output dBA UL dBA Tabs DC Regulated Note 3 Ratings Note 1 FWR Unfiltered Note 4 12V 24V 30V 12V 24V 12V 24V Slow Whoop ABC 21 40 38 56 46 72 85 92 79 85 800 Continuous BC 15 24 28 45 35 55 87 93 79 85 800 1000 Alternating AC 17 32 34 46 43...

Страница 10: ...ambient noise at all locations within a room Additional sounders may be needed to ensure sound output level complies with NFPA requirements The Sounder and or Strobe will not work without power The sounder strobe gets its power from the fire security panel monitoring the alarm system If power is cut off for any reason the sounder strobe will not pro vide the desired audio or visual warning The Sou...

Страница 11: ...STORING UNUSED CLIPS SLIDE COVER BACK TO ALIGN COVER SLOT WITH CLIP STORAGE POST SLIDE COVER FOR CLIP STORAGE USE A SMALL BLADED SCREWDRIVER TO REMOVE CLIPS TONE SELECTION TABS Figure 2 Figure 3 Multi alert sounder Figure 4 Multi alert sounder and strobe operating in tandem Figure 5 Strobe From panel or previous device To Next Device or EOL VDC VDC VDC VDC STROBE SOUNDER INOUT STROBE ONLY INOUT IN...

Страница 12: ...137 11 1 Complete field wiring 2 Screw plate sounder to Box with screw F A78 1137 08 C F F C MP F MA 12 24D D D BB D A78 2515 00 A78 2514 00 Figure 9 Strobe surface mount 1 Complete field wiring 2 Screw sounder strobe to box with screw A 3 Fill remaining screw holes with screw B Figure 10 Sounder strobe surface mount MA 12 24D A B B A Signal Strobe Standard Backbox 1 Complete field wiring 2 Screw ...

Страница 13: ...ge Current from from Rectified Current 100 Viewing Regulated Supply Unfiltered Supply Angle see Fig 3 VDC mA mA RMS mA Candela SS12LO 12 17 50 80 550 1 5 SS24LOA 22 5 30 22 35o C SS12M 12 17 180 300 440 15 SS24MA 22 5 30 5 9 35o C SS24LO 22 5 30 25 45 225 1 5 22 35o C SS24M 22 5 30 75 125 450 15 5 9 35o C Table 2 Sound output and current ratings for the MA12 24EH Table 1 SS12 24 electrical and lig...

Страница 14: ...must conform to appropriate agency re quirements including but not limited to the following NFPA 72 NEC ART 760 ET AL CAN ULC S524 CEC PART 1 SEC 32 ULC models have suffix A CAUTION The rated output of the sounder is specified at 10 feet It should not be assumed that the output will meet the NFPA requirement of 15 dB over ambient noise at all locations within a room Addi tional sounders may be nee...

Страница 15: ...t Device or EOL VDC VDC Figure 5 Multi alert sounder From panel or previous device To Next Device or EOL VDC VDC Figure 6 Strobe only SS series only From panel or previous device To Next Device or EOL VDC VDC Note Use uncoded supply only INOUT STROBE ONLY INOUT INOUT STROBE ONLY INOUT Figure 7 Multi alert sounder and strobe operating in tandem From panel or previous device To Next Device or EOL VD...

Страница 16: ...upplied with box 2 Screw plate to plaster ring with screw G 3 Complete field wiring See Fig 5 7 and 8 4 Screw sounder or sounder strobe to plate with screw A 5 Fill remaining holes with screw B A78 1137 08E A78 1137 20E C F F C MP F MA 12 24EH D D BB D 1 Screw plate to box with screw E 2 Complete field wiring See Fig 5 7 and 8 3 Screw sounder or sounder strobe to plate with screw A 4 Fill remainin...

Страница 17: ...nder can be connected to either 12 or 24 VDC pan Model Supply Voltage Range Operating Current from Regulated Supply Operating Current from Full Wave Rectified Unfiltered Supply Average Operating Current Peak Current mA 20 30V Peak Current mA 10 5V 17V Inrush Current mA in access of Peak Average Operating Current mArms Peak Current mA 20Vrms 30Vrms Peak Current mA 10 5Vrms 17Vrms Inrush Current Amp...

Страница 18: ...1 and uses an extremely reliable xe non flash tube The visual warning signal is suitable for direct viewing and must be installed within an area where it can be seen by building occu pants The strobe must not be installed in direct sunlight or areas of high light intensity over 60 foot candles where the visual flash might be disre garded or not seen The strobe may not be seen by the visually im pa...

Страница 19: ...E SELECTION TABS Figure 3 INOUT STROBE ONLY INOUT INOUT STROBE ONLY INOUT From panel or previous device To Next Device or EOL VDC VDC Figure 4 Multi alert sounder From panel or previous device To Next Device or EOL VDC VDC Note Use uncoded supply only INOUT STROBE ONLY INOUT INOUT STROBE ONLY INOUT Figure 5 Multi alert sounder and strobe operating in tandem From panel or previous device To Next De...

Страница 20: ...ate sounder to box with screw F C F F C MP F MA 12 24EH D D BB D A78 1137 08E 1 Plaster ring should be properly mounted to electrical box with screws supplied with box 2 Screw plate to plaster ring with screw G 3 Complete field wiring See Fig 4 5 and 6 4 Screw sounder strobe to plate with screw A and fill remaining holes with screw B A B B G G MA 12 24EH MP SF Plaster Ring Standard Backbox A A78 1...

Страница 21: ...Vrms Vrms NOTE In rush current du ration is less than 20 m i c r o s e c o n d s 00002 seconds Table 2 Sound output and current ratings for the MA12 24EH Sound Hz Clips on Current mA Output dBA UL dBA Tabs DC Regulated Note 3 Ratings Note 1 FWR Unfiltered Note 4 12V 24V 30V 12V 24V 12V 24V Fast Whoop ABC 21 40 38 56 46 72 85 92 79 85 800 Continuous BC 15 24 28 45 35 55 87 93 79 85 800 1000 Alterna...

Страница 22: ...ambient noise at all locations within a room Additional sounders may be needed to ensure sound output level complies with NFPA requirements The Sounder and or Strobe will not work without power The sounder strobe gets its power from the fire security panel monitoring the alarm system If power is cut off for any reason the sounder strobe will not pro vide the desired audio or visual warning The Sou...

Страница 23: ... STORING UNUSED CLIPS SLIDE COVER BACK TO ALIGN COVER SLOT WITH CLIP STORAGE POST SLIDE COVER FOR CLIP STORAGE USE A SMALL BLADED SCREWDRIVER TO REMOVE CLIPS TONE SELECTION TABS Figure 2 Figure 3 Multi alert sounder Figure 4 Multi alert sounder and strobe operating in tandem Figure 5 Strobe From panel or previous device To Next Device or EOL VDC VDC VDC VDC STROBE SOUNDER INOUT STROBE ONLY INOUT I...

Страница 24: ...78 1137 31 1 Complete field wiring 2 Screw plate sounder to box with screw F A78 1137 30 C F F C MP F MA12 24EH D D BB D A78 2515 03 A78 2514 00 Figure 9 Strobe surface mount 1 Complete field wiring 2 Screw sounder strobe to box with screw A 3 Fill remaining screw holes with screw B Figure 10 Sounder strobe surface mount MA12 24EH A B B A Signal Strobe Standard Backbox 1 Complete field wiring 2 Sc...

Отзывы: