Specifications 

 

Diameter : 

104 mm (Installed in DZ-B401 Base) 

Height : 

51mm( Installed in DZ-B401 Base) 

Weight : 

80g(Without Base) 

Operating Temperature Range : 

-10°C to 50°C 

Operating Humidity Range : 

10% to 95% Relative Humidity noncondensing 

Operating voltage : 

8.5 to 28VDC 

Standby Current : 

≤120uA

 

Alarm Current : 

10mA Min. 93mA Max. (Must be limited by control panel) 

Latching Alarm : 

Reset by momentary power interruption 

Sensitivity : 

63°C Fixed or 10°C /min rate-of-rise 

Standard : 

GB4716-2005 / GB3836.1-2000 / GB3836.4-2000 

Intrinsic Safety Rating : 

Exia 

C   T5 

Certification : 

                                                  Software Version

 
 

BEFORE INSTALLING 

Before In stalling please thor oughly r ead the  X i’an Syst em  Sensor manu al,  Copies o f this manu al ar e  available  from  Xi’an  System 
Sensor. 

GENERAL DESCRIPTION 

JTWB-BCD-5151EIS/HT is a conventional 2-wire intrinsically safe thermal detector. This detector is designed to provide open area 
protection and to be used with compatible panels (or interface module) only. This sensor utilizes a state-of-the-art thermistor sensing 
circuit for fast response. It can be used in every environmental condition and also has the simple maintenance and lower fault rate 
advantages. Two red LEDs blink in standby each 5S and latch on in alarm, and do not blink in trouble. A remote output option is also 
available. A built in test switch is used in the detector for test alarm. The detector is commpliance with the GB3836.1-2000 
&GB3836.4-2000 standards requiremets. 

INSTALLATION 

NOTE: All wiring must comply with all applicable national codes of practice and regulations.   
WARNING: Disconnect the power to the initiating device before installing the detectors.

   

1.

 

Install detectors: 

a.

 

Place the detector into the detector base. 

b.

 

Turn the detector clockwise until the detector drops into 
place.  

c.

 

Continue turning detector clockwise to lock it in place. 

Tamper  Resistance: T he d etector b ases  can be made  tamper 
resistant. When capability is  enabled, detectors cannot be removed 
from the   base  without t he u se o f a   tool.  See the detector  base 
installation ma nual  of the de tector base  for  details in us ing this 
capability 
2.

 

After all detectors have been installed, apply power to the control 
unit. 

3.

 

Test the detector using the magnet as described under TESTING. 

4.

 

Reset the detector at the system control panel. 

5.

 

Notify the proper authorities that the system is back on line. 

TESTING 

A. Test Magnet 
1.

 

Place the magnet against the cover in the location designated by 
the raised mark to activate the test feature (see Figure 1). 

2.

 

The LEDs should latch ON within 5 seconds indicating alarm and 
an-nunciating the panel. 

INSTALLATION AND MAINTENANCE INSTRUCTIONS   

Model JTWB-BCD-5151EIS Plug-in 

Intrinsically Safe Thermal Detector 

with Fixed Temperature Alarm 

28 Tuan Jie South Road, Xi’an National

Hi-tech Industrial Development Zone

Province of Shaanxi, 710075, China

Telephone: (029) 85387800      Fax: (029) 88332959

Figure 1. 

 

4                   

               

          

           I56-5151-007C 

3.

 

Reset the detector at the system control panel.   

B. Direct Heat Method (Hair dryer of 1000 - 1500 watts)   

From the side  of the d etector, direct the heat toward the sensor. Hold the h eat source about 15 cm away to prevent damage to th e 
cover during testing   

NOTE: If a detector goes into alarm, it will reset only if the detector has cooled and if its power is momentarily interrupted. Check the 
control panel being used to determine whether the RESET switch (or some other auxiliary device or control) momentarily cuts off power 
to the detector loop.   
Detectors that fail these  tests should be cleaned as desc ribed under MAINTENANCE and retested. If the detectors still fail these tests 
they should be returned for repair. 

MAINTENANCE 

The JTWB-BCD-1151EIS/HT detector has  been designed to b e as maintenance free as possible. Normal ai r-borne dust, however, can 
accumulate on the detector’s sensing elements and cause them to become less sensitive. All detectors should be tested and cleaned at least 
once a year, and those in dustier areas should be tested and cleaned more often. Detectors must also be  cleaned and tested immediately 
after a f ire.    Before cleaning, notify the proper authorities that the system is und ergoing maintenance, and therefore the system w ill 
temporarily be out of service. Disable the loop or system undergoing maintenance to prevent unwanted alarms. 
1. Remove detector from mounting base.   
2. Use a vacuum cleaner to remove dust from the sensing chamber.   
3. Reinstall the detector.   
4. Test detector as described under TESTING. 

SYSTEM WIRING DIAGRAM

 

The system includes the control panel, the zener diode safety barrier or the isolated barrier, the intrinsically detector, the DZ-B401 base 
and the wires. 

Intrinsic

Safety Barrier

[Exia]ⅡC

3  2    4

(B401 Base)

Detector

Exia ⅡC T5

To next
detector

HAZARDOUS  AREA

Note 2

Note 3

SAFE AREA

Safe area apparatus

w hich is

unspecified  except  that  it must
not be suppliedo from or contain
under normal or abnormal condi-
ions  a  source of  potential  w ith
respect  to  earth  in   excess  of
250Vrms or 250VDC

 

Notes:  
1. The detector has the following Intrinsically-safe parameters: Ui: 28VDC, Li: 93mA,  Pi: 0.65W, Ci: 0, Li:  0 When to compatible with 

the S afety b arrier, th e  parameters mu st b e c omplied w ith t he fo llowing  formula: Uo

Ui, I o

Ii, Po

Pi, Co

Ci+Cc, L o

Li+Lc,   

Among them, about the definitions of Uo

Ui

Io

Ii

Po

Pi

Co

Ci

Lo

Li refer to the GB3836.4-2000. Cc and Lc separately stand 

for the capacitance and inductance between the detector and the safety barrier, the remote indicator or the general cable.   

2. The transformer in the hazardous area must be accordance with the Item 8.1 of the GB3836.4-2000 standard.   
3. The installation must comply with the Item 15 of the GB3836.15-2000 standard.   
4. Don’t clean the detector housing with a dry cloth.   
5. The electrical circuit in the hazardous area must be capable of withstanding an A.C. test voltage of 500VRMS to earth or frame of the 

apparatus for one minute. 

6. Zone wiring of the detector bases refer to the DZ-B401 base installation manual. 

PRODUCT NAMEPLATE DATE CODE NOTE 

X                                                              X X                                        X                 

         

Stands for: The end number of the producing year t he producing month     the week of the month 

LIMITATIONS OF FIRE ALARM SYSTEMS

 

This smoke sensor is designed to activate and initiate emergency action.    It will not work without power and it has its limitations. It also 
can not last forever.   

THREE-YEAR LIMITED WARRANTY 

Xi’an System Sensor warrants its enclosed thermal detector to be free from defects in materials and workmanship under normal use and 
service for a period of three years from date of manufacture. The Company’s obligation of this Warranty shall be limited to the repair or 
replacement o f  any p art o f  the  thermal dete ctor  which is  found to be d efective in  materials or  workmanship und er n ormal u se  and 
service during the three year period commencing with the date of manufacture.     

Ver.A

LED Status

Indicators

Magnet Test

Marker

Test Magnet 

Position

Test Magnet 

Position

Magnet Test

Marker

HEAT