3
I56-5151-007C
Specifications
Diameter :
104 mm (Installed in DZ-B401 Base)
Height :
51mm( Installed in DZ-B401 Base)
Weight :
80g(Without Base)
Operating Temperature Range :
-10°C to 50°C
Operating Humidity Range :
10% to 95% Relative Humidity noncondensing
Operating voltage :
8.5 to 28VDC
Standby Current :
≤120uA
Alarm Current :
10mA Min. 93mA Max. (Must be limited by control panel)
Latching Alarm :
Reset by momentary power interruption
Sensitivity :
63°C Fixed or 10°C /min rate-of-rise
Standard :
GB4716-2005 / GB3836.1-2000 / GB3836.4-2000
Intrinsic Safety Rating :
Exia
Ⅱ
C T5
Certification :
Software Version
:
A
BEFORE INSTALLING
Before In stalling please thor oughly r ead the X i’an Syst em Sensor manu al, Copies o f this manu al ar e available from Xi’an System
Sensor.
GENERAL DESCRIPTION
JTWB-BCD-5151EIS/HT is a conventional 2-wire intrinsically safe thermal detector. This detector is designed to provide open area
protection and to be used with compatible panels (or interface module) only. This sensor utilizes a state-of-the-art thermistor sensing
circuit for fast response. It can be used in every environmental condition and also has the simple maintenance and lower fault rate
advantages. Two red LEDs blink in standby each 5S and latch on in alarm, and do not blink in trouble. A remote output option is also
available. A built in test switch is used in the detector for test alarm. The detector is commpliance with the GB3836.1-2000
&GB3836.4-2000 standards requiremets.
INSTALLATION
NOTE: All wiring must comply with all applicable national codes of practice and regulations.
WARNING: Disconnect the power to the initiating device before installing the detectors.
1.
Install detectors:
a.
Place the detector into the detector base.
b.
Turn the detector clockwise until the detector drops into
place.
c.
Continue turning detector clockwise to lock it in place.
Tamper Resistance: T he d etector b ases can be made tamper
resistant. When capability is enabled, detectors cannot be removed
from the base without t he u se o f a tool. See the detector base
installation ma nual of the de tector base for details in us ing this
capability
2.
After all detectors have been installed, apply power to the control
unit.
3.
Test the detector using the magnet as described under TESTING.
4.
Reset the detector at the system control panel.
5.
Notify the proper authorities that the system is back on line.
TESTING
A. Test Magnet
1.
Place the magnet against the cover in the location designated by
the raised mark to activate the test feature (see Figure 1).
2.
The LEDs should latch ON within 5 seconds indicating alarm and
an-nunciating the panel.
INSTALLATION AND MAINTENANCE INSTRUCTIONS
Model JTWB-BCD-5151EIS Plug-in
Intrinsically Safe Thermal Detector
with Fixed Temperature Alarm
28 Tuan Jie South Road, Xi’an National
Hi-tech Industrial Development Zone
Province of Shaanxi, 710075, China
Telephone: (029) 85387800 Fax: (029) 88332959
Figure 1.
4
I56-5151-007C
3.
Reset the detector at the system control panel.
B. Direct Heat Method (Hair dryer of 1000 - 1500 watts)
From the side of the d etector, direct the heat toward the sensor. Hold the h eat source about 15 cm away to prevent damage to th e
cover during testing
NOTE: If a detector goes into alarm, it will reset only if the detector has cooled and if its power is momentarily interrupted. Check the
control panel being used to determine whether the RESET switch (or some other auxiliary device or control) momentarily cuts off power
to the detector loop.
Detectors that fail these tests should be cleaned as desc ribed under MAINTENANCE and retested. If the detectors still fail these tests
they should be returned for repair.
MAINTENANCE
The JTWB-BCD-1151EIS/HT detector has been designed to b e as maintenance free as possible. Normal ai r-borne dust, however, can
accumulate on the detector’s sensing elements and cause them to become less sensitive. All detectors should be tested and cleaned at least
once a year, and those in dustier areas should be tested and cleaned more often. Detectors must also be cleaned and tested immediately
after a f ire. Before cleaning, notify the proper authorities that the system is und ergoing maintenance, and therefore the system w ill
temporarily be out of service. Disable the loop or system undergoing maintenance to prevent unwanted alarms.
1. Remove detector from mounting base.
2. Use a vacuum cleaner to remove dust from the sensing chamber.
3. Reinstall the detector.
4. Test detector as described under TESTING.
SYSTEM WIRING DIAGRAM
The system includes the control panel, the zener diode safety barrier or the isolated barrier, the intrinsically detector, the DZ-B401 base
and the wires.
Intrinsic
Safety Barrier
[Exia]ⅡC
3 2 4
(B401 Base)
Detector
Exia ⅡC T5
To next
detector
HAZARDOUS AREA
Note 2
Note 3
SAFE AREA
Safe area apparatus
,
w hich is
unspecified except that it must
not be suppliedo from or contain
under normal or abnormal condi-
ions a source of potential w ith
respect to earth in excess of
250Vrms or 250VDC
Notes:
1. The detector has the following Intrinsically-safe parameters: Ui: 28VDC, Li: 93mA, Pi: 0.65W, Ci: 0, Li: 0 When to compatible with
the S afety b arrier, th e parameters mu st b e c omplied w ith t he fo llowing formula: Uo
≤
Ui, I o
≤
Ii, Po
≤
Pi, Co
≥
Ci+Cc, L o
≥
Li+Lc,
Among them, about the definitions of Uo
、
Ui
、
Io
、
Ii
、
Po
、
Pi
、
Co
、
Ci
、
Lo
、
Li refer to the GB3836.4-2000. Cc and Lc separately stand
for the capacitance and inductance between the detector and the safety barrier, the remote indicator or the general cable.
2. The transformer in the hazardous area must be accordance with the Item 8.1 of the GB3836.4-2000 standard.
3. The installation must comply with the Item 15 of the GB3836.15-2000 standard.
4. Don’t clean the detector housing with a dry cloth.
5. The electrical circuit in the hazardous area must be capable of withstanding an A.C. test voltage of 500VRMS to earth or frame of the
apparatus for one minute.
6. Zone wiring of the detector bases refer to the DZ-B401 base installation manual.
PRODUCT NAMEPLATE DATE CODE NOTE
X X X X
Stands for: The end number of the producing year t he producing month the week of the month
LIMITATIONS OF FIRE ALARM SYSTEMS
This smoke sensor is designed to activate and initiate emergency action. It will not work without power and it has its limitations. It also
can not last forever.
THREE-YEAR LIMITED WARRANTY
Xi’an System Sensor warrants its enclosed thermal detector to be free from defects in materials and workmanship under normal use and
service for a period of three years from date of manufacture. The Company’s obligation of this Warranty shall be limited to the repair or
replacement o f any p art o f the thermal dete ctor which is found to be d efective in materials or workmanship und er n ormal u se and
service during the three year period commencing with the date of manufacture.
Ver.A
LED Status
Indicators
Magnet Test
Marker
Test Magnet
Position
Test Magnet
Position
Magnet Test
Marker
HEAT