background image

SENSOR MODULE 

COVER

POWER BOARD

MODULE COVER

SENSOR HEAD

METAL 

SAMPLING TUBE

POWER BOARD

EXHAUST TUBE

VARISTOR

4-WIRE

MAGNET TEST LOCATION

(sold seperately)

[3] generaL deScriPTion

Smoke introduced into an air duct system will be distributed throughout the 
entire building. Smoke detectors designed for use in air duct systems are used 
to sense the presence of smoke in the duct. 

Model D4240 Duct Smoke Detectors utilize 4-wire photoelectric technology 
for the detection of smoke. This detection method, when combined with an 
efficient housing, samples air passing through the duct allowing detection of 
a developing hazardous condition. When sufficient smoke is sensed, an alarm 
signal is initiated and appropriate action can be taken to shut off fans, blow-
ers, change over air handling systems, etc. These actions can facilitate the 
management of toxic smoke and fire gases throughout the areas served by the 
duct system.

The D4240 detectors are designed to operate on 24 VDC/VAC or 240 VAC. 
Alarm and supervisory relay contacts are available for control panel interface 
(alarm initiation), HVAC control, and other auxiliary functions. Auxiliary re-
lays are provided for fan shut down. Detector interconnection provides signal-
ing of up to 50 other detectors in the loop for multiple fan shut down. These 
detectors are not designed for 2-wire applications.

[3.1] deTecTor feaTure SeT

-Utilizes 2D51 plug-in head

-2 sensors to 1 power board capability

-Cover missing signal

-Sampling tubes install from front or rear of detector

-Compatible with existing accessories

[4] conTenTS of The ducT Smoke deTecTor kiT

1.  Sensor/power board assembly and cover(s)
2.  Three #10 sheet metal screws for mounting
3.  Drilling template
4.  One sampling tube end cap
5.  One plastic exhaust tube
NOTE: A sampling tube must be ordered to complete the installation. It must 
be the correct length for the width of the duct where it will be installed. 
See Table 1 on page 3 to determine the inlet tube required for different duct 
widths. 

[5] deTecTor inSTaLLaTion
[5.1] VerifY air fLoW direcTion and VeLociTY

Model D4240 detectors are designed to be used in air handling systems with 
air velocities of 100 to 4000 feet per minute. Duct widths from 6 inches to 12 
feet can be accommodated. Be sure to check engineering specifications to 
ensure that the air velocity in the duct falls within these parameters. If neces-
sary, use a velocity meter (anemometer) to check the air velocity in the duct.

[5.2] deTermine mounTing LocaTion and configuraTion

On ducts wider than 18 inches it is recommended that the detector be 
mounted downstream of a bend, obstruction in the duct, or the supply or 
return air inlet.

Exception:

 Installation of duct detectors can be on or within a commercial 

packaged rooftop heating and air-conditioning system, fire/smoke dampers 
and economizers. They may be mounted in either the supply and/or return air 
section as determined by local code.
Once a suitable location is selected, determine if the detector is to be mounted 
in a side-by-side “rectangular” configuration or a top-over-bottom “square” 
configuration as shown in 

Figure 2

. If mounting in the square configuration, 

remove the rear attachment screw, rotate the unit at the hinge, and replace the 
screw into the new attachment hole as shown in 

Figure 2

. Do NOT remove 

the hinge screw during this process. Final installation approval shall be based 
upon passing section 7.2.2 and/or 8.2.4 tests.

figure 2:

REMOVE SCREW AND PIVOT

DETECTOR AS SHOWN BELOW.

REPLACE SCREW

TO SECURE DETECTOR

IN PLACE.

H0550-00

[5.3] driLL The mounTing hoLeS

Remove the paper backing from the mounting template supplied. Affix the 
template to the duct at the desired mounting location. Make sure the template 
lies flat and smooth on the duct. 

[5.3.1] for recTanguLar Side-bY-Side mounTing configuraTion:

Center punch at (4) target centers: (2) “A” for sampling tubes and (2) “B” for 
the rectangular configuration mounting tabs as shown on mounting template. 
Drill pilot holes at target “A” centers and cut two 1.375 inch diameter holes 
using a 1

3

/

8

 inch hole saw or punch. Drill .156 inch diameter holes using a 

5

/

32

 

inch drill at target “B” centers.

[5.3.2] for Square ToP-oVer-boTTom mounTing 
configuraTion or d4S SenSor comPonenT mounTing:

Center punch at (4) target centers: (2) “A” for sampling tubes and (2) “C” for 
the square configuration mounting tabs as shown on mounting template. Drill 
pilot holes at target “A” centers and cut two 1.375 inch diameter holes using 
a 1

3

/

8

 inch hole saw or punch. Drill .156 inch diameter holes using a 

5

/

32

 inch 

drill at target “C” centers. If desired, drill an additional .156 inch hole at the 
location of one of the mounting tabs on the lower housing.

[5.4] Secure The ducT deTecTor To The ducT

Use two (rectangular configuration) or three (square configuration) of the pro-
vided sheet metal screws to screw the duct detector to the duct.

CAUTION:

 Do not overtighten the screws.

SS-300-022 

2 I56-3936-002R

[2] figure 1. exPLoded VieW of ducT Smoke deTecTor comPonenTS:

H0549-03

Содержание Inovair Flex D4240

Страница 1: ...sing No Accessories Max standby current 21 mA 24 VDC 65 mA RMS 24VAC 60Hz 10 mA RMS 240 VAC 60 Hz Max alarm current 65 mA 24 VDC 135 mA RMS 24 VAC 60 Hz 18 mA RMS 240 VAC 60 Hz CONTACT RATINGS Alarm i...

Страница 2: ...city meter anemometer to check the air velocity in the duct 5 2 Determine Mounting location and Configuration On ducts wider than 18 inches it is recommended that the detector be mounted downstream of...

Страница 3: ...ct Plug the end with the end cap and tape closed any holes in the protrud ing section of tube Be sure to seal the duct where the tube protrudes Figure 4 DETECTOR 3 4 HOLE 12 1 4 2 H0215 00 NOTE Air cu...

Страница 4: ...icate 2 sensors as shown in Figure 6 4 The D4S can only be used with new InnovairFlex models and is not com patible with previously sold detectors 9 Unit Configuration 9 unit configuration A three pos...

Страница 5: ...contacts are not to be used for connection to the control panel See specifications for contact ratings NOTE 3 Supervisory contacts shown in standby position Open contacts indi cate a trouble conditio...

Страница 6: ...igure 1 OR 1c Remote Test Accessory See list on page 1 The red alarm LED on the sensor and the power board should latch on as should any accessories i e RA400Z RA100Z RTS451 RTS151 Verify system contr...

Страница 7: ...install the RTS451 RTS151 RTS451KEY RTS151KEY connect the device as shown in Figure 13 wire runs must be limited to 25 ohms or less per interconnecting wire If a system control panel is used the panel...

Страница 8: ...minute tamper Delay if selected Off Alternating Green amber every 1 second Supervisory relay Terminals 3 and 14 are closed Alarm Relay Terminals 4 and 5 are open Aux Relay does not switch states Term...

Отзывы: