background image

SS-300-018 

I56-3371-003R

1)   Install DCOIL in housing pocket insuring that arrow is pointing toward detector
2)  Install DCOIL mounting screw
3)  Connect each DCOIL lead to a Test Coil Terminal  
See 

Figure 9

 below for reference.

fIgURE 9. DNRW WITh OPTIONAL TEST COIL

TEST COIL TERMINALS

TEST COIL

TEST COIL SCREW

H0561-00

fIgURE 10. WIRINg DIAgRAM fROM DNRW TO RTS451/RTS151/
RTS451kEy/RTS151kEy:

EXTERNAL

(-) POWER (+)

SUPPLY

*

RTS451/151,

RTS451/151KEY

REMOTE TEST STATION

LED OPTION

1 PER UNIT

10mA CURRENT DRAW

TEST COIL OPTION

1 PER UNIT

95mA CURRENT DRAW

4

5

3

2

1

TEST COIL +

TEST COIL –

COMM +

OUT (CONV ONLY) +

COMM –

RA/RTS –

RA +

RTS +

NOTE: THE RTS451/151, RTS451/151KEY TEST COIL 

CIRCUIT REQUIRES AN EXTERNAL 24 VDC POWER 

SUPPLY WHICH MUST BE UL LISTED.

NOTE: THE USE OF A REMOTE TEST STATION REQUIRES THE 

INSTALLATION OF AN ACCESSORY COIL, PART NUMBER DCOIL, SOLD 

SEPARATELY.

11.2 RTS451/RTS151/RTS451kEy/RTS151kEy REMOTE TEST 
STATION WITh OPTIONAL SENSOR REMOTE TEST CAPABILITy

To install the RTS451/RTS151/RTS451KEY/RTS151KEY, using the sensor with 
remote  test  capability  connect  the  device  as  shown  in  Figure  11;  wire  runs 
must be limited to 25 ohms or less per interconnecting wire.

H0571-07

CAUTION

Canned aerosol simulated smoke (canned smoke agent) formulas will vary by 
manufacturer.  Misuse or overuse to these products may have long term adverse 
effects on the smoke detector.  Consult the canned smoke agent manufacturer’s 
published instructions for any further warnings or caution statements.

[9]DETECTOR CLEANINg PROCEDURES

Notify  the  proper  authorities  that  the  smoke  detector  system  is  undergoing 
maintenance, and that the system will temporarily be out of service. Disable 
the zone or system undergoing maintenance to prevent unwanted alarms and 
possible dispatch of the fire department.

[9.1]DETECTOR SENSOR

1.  Remove the sensor to be cleaned from the system.
2.   Remove the sensor cover by pressing firmly on each of the four removal 

tabs that hold the cover in place.

3.   Vacuum the screen carefully without removing it. If further cleaning is 

required continue with Step 4, otherwise skip to Step 7.

4.   Remove the chamber cover/screen assembly by pulling it straight out.
5.   Use a vacuum cleaner or compressed air to remove dust and debris from 

the sensing chamber.

6.   Reinstall the chamber cover/screen assembly by sliding the edge over the 

sensing chamber. Turn until it is firmly in place.

7.   Replace  the  cover  using  the  LEDs  to  align  the  cover  and  then  gently 

pushing it until it locks into place.

8.  Reinstall the detector.

[9.2]REINSTALLATION

1.  Reinstall the detector in its housing.
2.  Restore system power. 
3.  Perform Detector Check.
4.   Notify the proper authorities testing has been completed and the smoke 

detector system is back in operation.

[10]SENSOR REPLACEMENT

1.  Remove the sensor head by rotating counterclockwise.
2.  Pull gently to remove it. 
3.   To replace the sensor head, align the mounting features and rotate clock-

wise into place.

[11] OPTIONAL ACCESSORIES

Optional  accessories  include  RA400Z/RA100Z,  RTS451/RTS151  and  RTS-
451KEY/RTS151KEY

fIgURE 8. WIRINg DIAgRAM fOR DNRW TO RA400Z/RA100Z:

(+)

(-)

RA400Z/RA100Z

– RA

+ RA

REMOTE ALARM LED 

OPTION 1 PER UNIT 

H0570-03

Note: If using a RA400Z, the tab should be broken for use with the intelligent 
duct smoke detector. If using RA100Z, ensure that jumper is removed.

[11.1]RTS451/RTS151/RTS451kEy/RTS151kEy REMOTE TEST 
STATION WITh OPTIONAL TEST COIL

The RTS451/RTS151/RTS451KEY/RTS151KEY Remote Test Station facilitates 
test of the alarm capability of the duct smoke detector. These accessories 
provide the stimulus to initiate an alarm condition at the detector. The DNRW 
duct smoke detector must be reset by the system control panel.  

NOTE:

 The use of a remote test station requires the installation of an acces-

sory coil, part number DCOIL, sold separately. 

RTS451/RTS451KEY

RTS151/RTS151KEY

JUMPER

4

5

3

2

1

TEST COIL +

TEST COIL –

COMM +

OUT (CONV ONLY) +

COMM –

RA/RTS –

RA +

RTS +

11.3 ADDITIONAL MODULE OPTION

The DNRW can also accommodate a relay or control module (sold separately) 
within the power board side of the housing. The relay or control module must 
be listed as compatible to the fire alarm control panel.

Physical Module Mounting 

1)  Remove the breakaway tabs at the four corners of the module
2)   Locate the module at right most corner of the power board. The upper 

left corner mounting hole of the module will align with a screw boss in 
the housing.

3)  Install a # 8 x 3/8” Plastite screw at the screw boss location
Note: See the corresponding module Installation Instructions for general de-
scription, control panel compatibility, wiring and ratings.

HO633-00

fIgURE 11. RTS451/RTS451kEy/RTS151/RTS151kEy:

Отзывы: