System Sensor innovair flex D4120W Скачать руководство пользователя страница 4

[7.2] LOW FLOW AIR FLOW TEST USING DWYER SERIES 607 

DIFFERENTIAL PRESSURE TRANSMITTER

Verify the air speed of the duct using an anemometer. Air speed must be at 
least 100 FPM. Wire the Dwyer transmitter as shown in 

Figure 5

. Connect the 

leads of the meter to either side of the 1000

Ω

 resistor. Allow unit to warm up 

for 15 seconds. With both HIGH and LOW pressure ports open to ambient air, 
measure and record the voltage drop across the 1000

Ω

 resistor (measurement 

1), 4.00 volts is typical. Using flexible tubing and rubber stoppers, connect the 
HIGH side of the transmitter to the sampling tube of the duct smoke detec-
tor housing, and the LOW side of the transmitter to the exhaust tube of the 
duct smoke detector housing. Measure and record the voltage drop across the 
1000

Ω

 resistor (measurement 2). Subtract the voltage recorded in measure-

ment 1 from the voltage recorded in measurement 2. If the difference is greater 
than 0.15 volts, there is enough air flow through the duct smoke detector for 
proper operation.

[8] FIELD WIRING INSTALLATION GUIDELINES

All wiring must be installed in compliance with the National Electrical Code 
and the local codes having jurisdiction. Proper wire gauges should be used. 
The conductors used to connect smoke detectors to control panels and acces-
sory devices should be color-coded to prevent wiring mistakes. Improper con-
nections can prevent a system from responding properly in the event of a fire.

For signal wiring, (wiring between interconnected detectors or from detectors 
to auxiliary devices), it is recommended that single conductor wire be no 
smaller than 18 gauge.

Smoke detectors and alarm system control panels have specifications for al-
lowable loop resistance. Consult the control panel manufacturer’s specifica-
tions for the total loop resistance allowed for the particular control panel being 
used before wiring the detector loop.

[8.1] WIRING INSTRUCTIONS

The D4120W detector is designed for easy wiring. The housing provides a 
terminal strip with clamping plates. The D4S housing provides 4 wiring ter-
minals with clamping plates. Wiring connections are made by sliding the bare 
end of the wire under the plate, and tightening the clamping plate screw. See 

Figure 7

 on page 5 for system wiring.

[8.2] SENSOR 2 INSTALLATION/WIRING

The power board is capable of controlling a second housed sensor. The second 
sensor, model D4S (NOT available in Type 4 enclosure), can be wired to the 
power board per the following:

1.   Connect wires to the four wire terminals in the corner of the D4S sensor 

housing designated as Tamper (Y,Y), +R, and –B. Route wires through the 
conduit openings in the sensor housing and D4120W power board housing.

2.   Connect the opposing ends of the wires to the terminal connections 

marked “Sensor 2” on the Power Board. See 

Figure 6

 for reference. En-

sure that wires are connected to the appropriate terminal locations. A 
No. 0 or 1 phillips screwdriver should be used for terminal connection. 
The tamper terminals are not polarity sensitive. 

3.   Adjust the middle dipswitch on the power board to indicate (2) sensors 

as shown in 

Figure 6

.

4.   The D4S can only be used with new InnovairFlex models and is not com-

patible with previously sold detectors.

HIGH

LOW

9 VOLT

BATTERY

9 VOLT

BATTERY

9 VOLT

BATTERY

TO SAMPLING TUBE
TO EXHAUST TUBE

DIFFERENTIAL 

PRESSURE 

TRANSMITTER 

MODEL #607-01

15 TO 36 

VDC SUPPLY

1000 OHM 5%

1 WATT RESISTOR

VOLT METER FLUKE 

MODEL 87 OR 

EQUIVALENT

+

FIGURE 5. PROCEDURE FOR VERIFYING AIR FLOW LESS THAN 500 FPM:

H0163-01

FIELD SELECTABLE 

DIP SWITCHES

TEST/RESET 

BUTTON

POWER 

BOARD LED 2

SENSOR 

LEDs

GROUND 

SCREW

SENSOR #1 

TERMINALS

D4120

CO-LOCATED

WIRING TERMINALS

24V 

AC
/DC
,  10

24V 

AC
/DC
,  9

AU
X OUT +,

  19

AU
X OUT -,

  20

INT/

AU
X-

, 1

INT+

, 12

ALARM,

  15

TEST

,  11

R RESET

,  2

AC

-

AC

+

120 VAC

B

-

R

+

Y

Y

B

-

R

+

Y

Y

TAMPER

TAMPER

SENSOR 1

SENSOR 2

OFF/ON 

TRBL SHUTDN

1/2 SENSORS

7/0 MIN 

TMPR DEL

AY

7,

  NO

18
,  C

AUX B

8,

  NC

17
,  NO

AUX A

6,

  C

16
,  NC

14
,  N0

3,

  C

13
,  NC

5,

  NO

SUP

ALARM

4,

 C

D4S

SENSOR ONLY

(NOT AVAILABLE IN

TYPE 4 ENCLOSURE)

SENSOR #2 

TERMINALS

TAMPER           

Y       Y       R       B

Y       Y       R       B

+     –

TAMPER           

+     –

SENSOR 2         

D4120        

D4S       

POWER 

BOARD LED 1

120

VAC INPUT

24 VAC/

DC INPUT

24V AC/DC,  10

24V AC/DC,  9

AUX OUT +,  19

AUX OUT -,  20

INT/AUX-, 1

INT+, 12

ALARM,  15

R TEST,  11

R RESET,  2

ACC -

ACC +

7,  NO

18,  C

8,  NC

17,  NO

6,  C

16,  NC

14,  N0

3,  C

13,  NC

5,  NO

4, C

H0557-17

FIGURE 6. OPTIONAL SENSOR 2 CONFIGURATION AND WIRING:

  

I56-3046-007R 

 

 06-10

Содержание innovair flex D4120W

Страница 1: ...VDC 65 mA RMS 24VAC 60Hz 20 mA RMS 120 VAC 60 Hz Max alarm current 65 mA 24 VDC 135 mA RMS 24 VAC 60 Hz 35 mA RMS 120 VAC 60 Hz CONTACT RATINGS Alarm initiation contacts SPST 2 0A 30 VDC resistive Al...

Страница 2: ...TION 5 1 VERIFY AIR FLOW DIRECTION AND VELOCITY Model D4120W detectors are designed to be used in air handling systems with air velocities of 100 to 4000 feet per minute Duct widths from 6 inches to 1...

Страница 3: ...alled using the 1 2 inch con duit fitting Make sure that the holes on both sections of the air inlet sampling tube are lined up and facing into the airflow 2 For tubes longer than the width of the duc...

Страница 4: ...mping plates Wiring connections are made by sliding the bare end of the wire under the plate and tightening the clamping plate screw See Figure 7 on page 5 for system wiring 8 2 SENSOR 2 INSTALLATION...

Страница 5: ...arm Initiation contacts shown in standby position Closed contacts indicate an alarm condition to the panel See specifications for contact ratings H0558 07 9 UNIT CONFIGURATION A three position dipswit...

Страница 6: ...maintenance and that the system will temporarily be out of service Disable the zone or system undergoing maintenance to prevent unwanted alarms and possible dispatch of the fire department 12 5 1 ALA...

Страница 7: ...g is required continue with Step 4 otherwise skip to Step 7 4 Remove the chamber cover screen assembly by pulling it straight out 5 Use a vacuum cleaner or compressed air to remove dust and debris fro...

Страница 8: ...e tamper Delay if selected Off Alternating Green amber every 1 second Supervisory relay Terminals 3 and 14 are closed Alarm Relay Terminals 4 and 5 are open Aux Relay does not switch states Terminals...

Отзывы: