System Sensor innovair flex D4120W Скачать руководство пользователя страница 1

D4120W Duct Smoke Detector

INSTALLATION AND MAINTENANCE INSTRUCTIONS

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

TABLE OF CONTENTS 

PAGE

[1] Limitations of Duct Smoke Detectors. . . . . . . . . . . . . . . . . . . . . . . . . . 1
[2] Exploded View of Duct Smoke Detector Components   . . . . . . . . . . . . . 2
[3] General Description   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
[4] Contents of Duct Smoke Detector Kit. . . . . . . . . . . . . . . . . . . . . . . . . . 2
[5] Detector Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
[6] Sampling Tube Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
[7] Measurement Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
[8] Field Wiring Installation Guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . 4
[9] Unit Configuration  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
[10] Detector Status Indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
[11] Interconnection (Multiple Fan Shut Down). . . . . . . . . . . . . . . . . . . . . 6
[12] Verification of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
[13] Detector Cleaning Procedures  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
[14] Sensor replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
[15] Optional Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  8

 

BEFORE INSTALLING

To maintain the watertight properties of this duct smoke detector, watertight 
conduit and fittings must be used.  Mount the product with the conduit holes 
facing downwards, if possible. Read System Sensor’s 

Applications Guide for 

Duct Smoke Detectors

 (HVAG53), which provides information on detector 

spacing, placement, zoning, wiring, and special applications. This manual 
is available online at www.systemsensor.com. NFPA Standards 72 and 90A 
should also be referenced for detailed information. 

I56-3

046-00

7R

NOTE: The D4120W duct detector consists of a Power Board and Sensor component.

SPECIFICATIONS 

Operating Temperature: 

–4° to 158° F (–20° to 70° C)

Storage Temperature: 

–22° to 158° F (–30° to 70° C)

Environmental Rating: 

NEMA 4* Type 4 Enclosure — Watertight

Humidity: 

0% to 95% Relative Humidity Non-condensing

Air Velocity: 

100 to 4000 ft./min. (0.5 to 20.3 m/sec.)

D4120W Footprint Dimensions: 

Rectangular - 14.38 in L x 5 in W x 2.5 in D (37cm L x 12.7cm W x 6.36cm D)

 

Square - 7.75 in L x 9 in W x 2.5 in D (19.7cm L x 22.9cm W x 6.35cm D)

D4120W Weight: 

2.5 pounds; 1.14 kg

Electrical

Power supply voltage: 

20-29 VDC 

24 VAC 50-60-Hz 

120 VAC 50-60 Hz

Input capacitance: 

270 µF max. 

270 µF max. 

N/A

Reset Voltage: 

3.0 VDC min. 

2.0 VAC min. 

10 VAC min.

Reset Time (with RTS451/RTS151):  .03 to 0.3 sec. 

.03 to 0.3 sec. 

.03 to 0.3 sec.

Reset Time (by power down): 

0.6 sec. max. 

0.6 sec. max. 

0.6 sec. max.

Power Up Time: 

35 sec. max. 

35 sec. max. 

35 sec. max.

Alarm response time: 

15 sec. 

15 sec. 

15 sec.

Sensitivity Test: 

See detector label 

See detector label 

See detector label

Current Requirements (Using No Accessories)

Max. standby current 

21 mA @ 24 VDC 

65 mA RMS @ 24VAC 60Hz 

20 mA RMS @ 120 VAC 60 Hz

Max. alarm current 

65 mA @ 24 VDC 

135 mA RMS @ 24 VAC 60 Hz 

35 mA RMS @ 120 VAC 60 Hz

CONTACT RATINGS

Alarm initiation contacts (SPST)

2.0A @ 30 VDC (resistive)

Alarm auxiliary contatcs (DPDT) 10A @30 VDC (resistive) 

10A @250 VAC (resistive)

1

/

2

 HP @240 VAC

1

/

4

 HP @120 VAC

NOTE: Alarm auxiliary contacts shall not be connected to initiating circuits of 

control panels. Use the alarm initiation contact for this purpose.

Supervisory Contacts (SPDT)

2.0A @ 30 VDC (resistive)
2.0A @ 125 VAC (resistive)

ACCESSORY CURRENT LOADS AT 24 VDC

DEVICE

STANDBY

TROUBLE

ALARM

APA151/APA451

12.5mA

n/a

30mA Max.

MHR/MHW

0mA

n/a

29mA Max.

RA400Z/RA100Z

0mA

n/a

12mA Max.

RTS451/RTS151

0mA

n/a

12mA Max.

RTS451KEY/RTS151KEY

12mA

n/a

12mA Max.

RTS2

3mA Max.

16mA Max.

30mA Max.

RTS2-AOS

3mA

16mA Max.

55mA Max.

NOTE: Any combination of accessories may be used such that the given accessory 
loads are: 110mA or less at the Aux output, and 50mA or less at the Alarm output.

IMPORTANT:

 This detector must be tested and maintained regularly following 

NFPA 72 requirements. The detector must be tested an maintained regularly fol-
lowing NFPA 72 requirements.  According to NFPA, the detector should be visu-
ally inspected semiannually and functionally tested at least once a year.  This 
may need to be more frequent depending on the air quality of the duct supply air.

[1] LIMITATIONS OF DUCT SMOKE DETECTORS 

WARNING

The National Fire Protection Association has established that DUCT DETEC-
TORS MUST NOT BE USED AS A SUBSTITUTE FOR OPEN AREA DETECTOR 
PROTECTION as a means of providing life safety. Nor are they a substitute for 
early warning in a building’s regular fire detection system.
System Sensor supports this position and strongly recommends that the user 
read NFPA Standards 90A, 72, and 101. The D4120W Air Duct Smoke Detec-
tors are listed per UL 268A.
This device will not operate without electrical power. Fire situations may 
cause an interruption of power. The system safeguards should be discussed 
with your local fire protection specialist.
This device will not sense smoke unless the ventilation system is operating 
and the cover is installed.
For this detector to function properly, it MUST be installed according to the in-
structions in this manual. Furthermore, the detector MUST be operated within 
ALL electrical and environmental specifications listed in this manual. Failure 
to comply with these requirements may prevent the detector from activating 
when smoke is present in the air duct.

  

I56-3046-007R 

 

 06-10

Содержание innovair flex D4120W

Страница 1: ...VDC 65 mA RMS 24VAC 60Hz 20 mA RMS 120 VAC 60 Hz Max alarm current 65 mA 24 VDC 135 mA RMS 24 VAC 60 Hz 35 mA RMS 120 VAC 60 Hz CONTACT RATINGS Alarm initiation contacts SPST 2 0A 30 VDC resistive Al...

Страница 2: ...TION 5 1 VERIFY AIR FLOW DIRECTION AND VELOCITY Model D4120W detectors are designed to be used in air handling systems with air velocities of 100 to 4000 feet per minute Duct widths from 6 inches to 1...

Страница 3: ...alled using the 1 2 inch con duit fitting Make sure that the holes on both sections of the air inlet sampling tube are lined up and facing into the airflow 2 For tubes longer than the width of the duc...

Страница 4: ...mping plates Wiring connections are made by sliding the bare end of the wire under the plate and tightening the clamping plate screw See Figure 7 on page 5 for system wiring 8 2 SENSOR 2 INSTALLATION...

Страница 5: ...arm Initiation contacts shown in standby position Closed contacts indicate an alarm condition to the panel See specifications for contact ratings H0558 07 9 UNIT CONFIGURATION A three position dipswit...

Страница 6: ...maintenance and that the system will temporarily be out of service Disable the zone or system undergoing maintenance to prevent unwanted alarms and possible dispatch of the fire department 12 5 1 ALA...

Страница 7: ...g is required continue with Step 4 otherwise skip to Step 7 4 Remove the chamber cover screen assembly by pulling it straight out 5 Use a vacuum cleaner or compressed air to remove dust and debris fro...

Страница 8: ...e tamper Delay if selected Off Alternating Green amber every 1 second Supervisory relay Terminals 3 and 14 are closed Alarm Relay Terminals 4 and 5 are open Aux Relay does not switch states Terminals...

Отзывы: