D200-101-00

1

I56-3888-103

DESCRIPTION

The LT FL01 Series is part of the Fire Alarm Aspiration Sensing 

Technology

®

 (FAAST) family.  FAAST is an advanced fire detection 

system for use where early warning and very early warning are a 

requirement. The system continuously draws air from the controlled 

environment through a series of sampling holes to monitor the 

environment for smoke particulate.
The FL01 is the stand-alone version of the FAAST LT range and is 

available in 3 different models:

FL0111E -

 Has single channel capability with one laser smoke 

sensor.

FL0112E -

 Has single channel capability with two laser smoke 

sensors in a common chamber for coincidence 

detection.

FL0122E -

 Has two channel capability with two laser smoke 

sensors in separate chambers. (One sensor for each 

channel).

This guide provides information for mounting and basic installation 

using the unit’s default factory settings.  For more extensive 

information please see the FAAST LT Advanced Setup and Control 

Guide - reference D200-100-00.

SPECIFICATIONS
Electrical Characteristics

Voltage Range: 

18.5 - 31.5 VDC

Supply Current: 

1 Channel: 

170mA (typical); 360mA (max) @ 

24 VDC 25

o

C (excluding sounders)

 

2 Channel: 

270mA (typical); 570mA (max) @ 

24 VDC 25

o

C (excluding sounders)

Configurable Input: Activation Time: 

2s (min)

Relay Contact Ratings: 

2.0 A @ 30 VDC, 0.5A @ 30 VAC

Environmental Ratings

Temperature: 

-10°C to 55°C

Relative Humidity: 

10% to 93% (non-condensing)

IP Rating: 

65

Mechanical

Exterior Dimensions: 

See Figure 1

Wiring: 

0.5 mm² to 2 mm² max

Maximum Single Pipe Length:  

100m (Classes A. B & C)

Maximum Number of Holes:  

See Table 1A

Pipe Spec (EN54-20 Compliance):  

to EN 61386 

 

(Crush 1, Impact 1, Temp 31)

Outside Pipe Diameter: 

25mm (nom) or 27mm (nom)

Shipping Weight: 

6.5kg (inc sensors)

FIRE ALARM ASPIRATION SENSING TECHNOLOGY

®

QUICK INSTALLATION GUIDE 

STAND-ALONE FAAST LT MODELS FL0111E  FL0112E  FL0122E

Figure 1: Dimensions and Knock-Outs

E N G L I S H

PARTS LIST
Description Quantity

FAAST LT unit 

1

Mounting bracket 

1

3-pin Terminal block  

6

4-pin Terminal block  

1

2-pin Terminal block  

3

47 k-ohm EOL Resistor  

2

USB Cable 

1

Front Panel Labelling Pack 

1

Installation Kit CD 

1

Quick Installation Guide 

1

Important Note

Aspirating Smoke Detectors supplied and installed within the 

EU  must  conform  to  the  EU  Construction  Products  Directive 

(89/106/EEC)  and  the  related  European  Product  Standard  EN 

54-20. FAAST LT has been tested and certified to ensure that it 

conforms to the necessary Standards, but strict adherence to this 

instruction guide is advised to ensure that the installation meets 

the requirements of the CPD Directive

367

mm

135 mm

56 mm

44 mm

403

mm

356 mm

Содержание FL0111E

Страница 1: ...5o C excluding sounders Configurable Input Activation Time 2s min Relay Contact Ratings 2 0 A 30 VDC 0 5A 30 VAC Environmental Ratings Temperature 10 C to 55 C Relative Humidity 10 to 93 non condensin...

Страница 2: ...s fixed in place This allows the installer to choose the language required for the installation from the Front Panel Labelling Pack Figure 2 shows where the labels need to be placed Figure 6 Fasten th...

Страница 3: ...allation 1 2 3 4 5 6 Figure 8 Pipe Holes FAAST LT MODEL INLET PIPE HOLE OUTLET PIPE HOLE FL0111E 1 2 or 1 or 2 5 FL0112E 1 2 or 1 or 2 6 FL0122E Channel 1 1 2 or 1 or 2 Channel 2 3 4 or 3 or 4 5 6 Tab...

Страница 4: ...EL 2 FILTER POWER AND ALARM CONNECTIONS CHANNEL 1 FILTER USB PORT SENSOR COVER POSITION FOR TEST MAGNET POSITION FOR TEST MAGNET Exhaust Pipe SAMPLING AREA SAMPLING AREA 5 6 EARTH BAR MOUNT EARTH BAR...

Страница 5: ...Alarm Relay CH2 11 NC Fault Relay CH1 T4 12 C Fault Relay CH1 13 NO Fault Relay CH1 14 NC Fault Relay AUX CH2 T5 15 C Fault Relay AUX CH2 16 NO Fault Relay AUX CH2 17 Sounder Output 1 47 k ohm EOL Res...

Страница 6: ...R DR IFT CO MP EN SA TIO N TEMPERATURE INPUT DIS AB LE SY ST EM S O U N D E R F IL T E R L O W F L O W H IG H F L O W INITIALIZATION LEVEL 1 SMOKE FAULT FAULT POWER LEVEL 2 SMOKE INITIALIZATION ALARM...

Страница 7: ...channel unit Upper row Ch1 Lower row Ch2 LOW FLOW ON Low flow fault Check filter check pipe network for blockages SENSOR 1 BLINK Sensor initialization fault Try to restart device Replace faulty sensor...

Страница 8: ...the cabinet door during normal operation will cause the unit to enter Service Mode The FILTER LEDs will blink the unit will switch off power to the fans and the fault relay will indicate a fault When...

Страница 9: ...used to quickly and accuratelydesignpipenetworks generateconfigurationparameters for correct set up and operation and facilitate commissioning and monitoring of the performance of FAAST LT Aspiration...

Страница 10: ...mputer in the normal way for your operating system Launching To launch the PipeIQLT application double click the PipeIQLT icon on the desktop Or click Start bottom left corner of the Windows screen an...

Отзывы: