PF24V Directional Sounder with Voice Messaging

INSTALLATION AND MAINTENANCE INSTRUCTIONS

GENERAL DESCRIPTION

Before installing, please read the Directional Sound Applications Guide, avail-
able through System Sensor. The installation must meet the requirements of 
the authority having jurisdiction, CAN/ULC S524 and CSA C22.1. Directional 
sounders are used as supplemental signals on a fire alarm system to aid in the 
evacuation of building occupants. Although directional sounders may be con-
nected to notification appliance circuits (NAC) for fire alarm service, they are 
not a replacement for audible or visible notification appliances as required by 
the authority having jurisdiction.

The directional sounder can be installed in systems using 24 Volt DC regulated 
power supplies only. It is not approved for use with FWR unregulated power 
supplies.

Directional sound is a broadband, multi-frequency sound. The sound source 
is easily and quickly located by building occupants, making it ideal for rapid 
building evacuation. The sounder incorporates four different speed settings 
which consist of broadband noise. The four speed settings can be used to cre-
ate an egress pathway out of a building. The speed setting should be set faster 
for units installed at the perimeter exit. In addition to the broadband noise, the 
sounder is capable of playing an alert message in the form of a recorded voice 
message or other audible signals. These messages will instruct the occupant 
of what action to take as they approach the directional sounder. The voice 
messages include: exit here, stairs up, stairs down, or area of refuge. 

Speed settings are made via DIP switches on the back of the sounder. 

POWER SUPPLY CONSIDERATIONS FOR DIRECTIONAL SOUNDERS

Panels typically supply DC filtered voltage or FWR (full-wave rectified) volt-
age. This device is only compatible with DC filtered supplies and must not be 
used with panel supplies that are FWR. Be certain the sum of all the device 
currents do not exceed the current capability of the panel power supply. Cal-
culations are based on using the device current found in 

Table 1

 and must be 

the current specified for the installed settings of the device.

WIRE SIZES

The last device on the circuit must have sufficient voltage to operate the de-
vice within its rated voltage range. When calculating the voltage available to 
the last device, it is necessary to consider the voltage drop due to the resis-
tance of the wire. The thicker the wire, the less the voltage drop. Generally, 
for purposes of determining the wire size necessary for the system, it is best 
to consider all of the devices as “lumped” on the end of the supply circuit 
(simulates “worst case”).

Typical wire size resistance:

18 AWG solid:  Approximately 8 ohms/1,000 ft.
16 AWG solid:  Approximately 5 ohms/1,000 ft.
14 AWG solid:  Approximately 3 ohms/1,000 ft.
12 AWG solid:  Approximately 2 ohms/1,000 ft.

SPECIFICATIONS

Mechanical

Input terminals: 

12 – 24 AWG

Sounder size: 

4 inches (101mm)

Grille Size: 

7

/

8

˝ (127mm)

Electrical

Voltage Input: 

Regulated 24 Volts DC

Operation Voltage Range: 

16 to 33 Volts

Operating Humidity Range: 

10% to 93% relative humidity non-condensing

Frequency range: 

707 Hz to 11314 Hz

Operating Temperature range: 

32° to 120°F (0° to 49°C)

Power: 

Selectable Low, Med-Low, Medium, Medium-High, High

Listings: 

UL 464 Directional Sounder, supplemental notification appliance, ULC S524

NOTICE:

 This manual should be left with the owner/user of the equipment.

Example: Assume you have 10 devices on a zone and each requires 50mA 
average and 2000 ft. of 14 AWG wiring (total length = ou return). 
The voltage at the end of the loop is 0.050 Amps per device × 10 devices ×  
3 ohms/1000 ft. × 2000 ft. = 3 volts drop.

The same number of devices using 12 AWG wire will produce only a 2 volt 
drop. The same number of devices using 18 AWG wire will produce an 8 volt 
drop. Consult your panel manufacturer’s specifications, as well as the sound-
er’s operating voltage to determine the acceptable voltage drop.

NOTE:

 If class “A” wiring is installed the wire length may be up to 4 times the 

single wire length in this calculation.

TABLE 1. CURRENT DRAW MEASUREMENTS AND SOUND OUTPUT GUIDE:

Speed Selection

Power 

Setting

Maximum DC 

Operating 

Current

(mA RMS)

(16 to 33V)

Audibility 

(dBA)
(16 to 

33V)

Note 1

Audibility 

(dBA)
(16 to 

33V)

Note 2

Speed

DIP Switch 

Selection

FAST (exit)

10

High

185

98

75

FAST (exit)

10

Med-High

131

95

72

FAST (exit)

10

Med

78

92

69

FAST (exit)

10

Med-Low

76

89

66

FAST (exit)

10

Low

64

86

63

MED-FAST

9

High

170

98

74

MED-FAST

9

Med-High

124

95

71

MED-FAST

9

Med

75

93

68

MED-FAST

9

Med-Low

73

90

65

MED-FAST

9

Low

62

87

62

MED-SLOW

8

High

135

97

73

MED-SLOW

8

Med-High

104

95

70

MED-SLOW

8

Med

67

92

67

MED-SLOW

8

Med-Low

65

89

64

MED-SLOW

8

Low

57

87

61

SLOW

7

High

120

98

72

SLOW

7

Med-High

92

95

69

SLOW

7

Med

62

92

66

SLOW

7

Med-Low

61

89

63

SLOW

7

Low

54

86

60

NOTE 1: Sound output data is peak dB measured in ULC anechoic room at 10 feet.
NOTE 2: Sound output measured in a reverberant room at 10 feet.

I56-296

1-00

2R

3825 Ohio Avenue, St. Charles, Illinois 60174

1.800.SENSOR2; Fax: 630.377.6495

www.systemsensor.com

  

I56-2961-002R 

 

 06-10

firealarmresources.com

Содержание ExitPoint PF24V

Страница 1: ...he wire the less the voltage drop Generally for purposes of determining the wire size necessary for the system it is best to consider all of the devices as lumped on the end of the supply circuit simulates worst case Typical wire size resistance 18 AWG solid Approximately 8 ohms 1 000 ft 16 AWG solid Approximately 5 ohms 1 000 ft 14 AWG solid Approximately 3 ohms 1 000 ft 12 AWG solid Approximatel...

Страница 2: ... High setting and if all three switches are on this selects the Low setting Directional Characteristics are as follows 3dBA angles 40 130 horizontal and vertical 6dBA angles 15 160 horizontal and vertical TABLE 4 POWER SETTING GUIDE DIP Switch Position 1 Setting DIP Switch Position 2 Setting DIP Switch Position 3 Setting Power Setting off off off High on off off Med High off on off Med off off on ...

Страница 3: ...ut of the directional sounder These terminals can be connected to the dry relay contacts of control devices such as heat sensors or control mod ules When the input is active it will disable the sound output of the Sounder Connect the disable function as shown in Figure 5 Refer to Table 3 for func tion switch settings FIGURE 5 VDC TO NEXT DEVICE OR EOL OPTIONAL DISABLE CONTACT VDC MECHANICAL Two sc...

Страница 4: ...0 Rojas Drive Suite 700 El Paso FCC STATEMENT NOTE Directional Sounder has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency en...

Отзывы: