D770-08-00 

I56-0551-007R

  a. Mount the device directly to the line via the 

1

2

 NPT 

pressure  connection.  The  use  of  teflon  pipe  sealant 
tape  is  recommended.  Be  sure  the  fitting  is  tight 
enough to prevent leaks.

  b. Apply tightening torque to the black plastic hex por-

tion of device.

WARNING

High voltage. Electrocution hazard. Do not handle live AC 
wiring or work on a device to which AC power is applied. 
Doing so may result in severe injury or death. When utiliz-
ing  switches  at  voltages  greater  than  74  VDC 

  or  49 

VAC 

, means to provide all-pole disconnection must be 

incorporated in the field wiring, such as a circuit breaker.

3. Wire  the  device  in  accordance  with  the  National 

Electrical  Code.  Two 

7

8

  diameter  conduit  connection 

holes  have  been  provided  in  the  mounting  plate  to 
accept  standard 

1

2

  conduit  fittings  (one  is  removable 

knock-out type). If a NEMA 4/UL 4x (waterproof unit) is 
required, waterproof flexible metallic conduit and appro-
priate conduit fittings must be used. Recommended con-
nectors are Thomas and Betts PN 5332 (180° coupling), 
PN 5352 (90° coupling), and PN 5262 seal ring.

4. Connect wiring to terminals (see Figure 3 and Table 1).

WET

SYSTEM

ALARM

CHECK

VALVE

OS & Y

VALVE

WATER

BY-PASS

VALVE

LOCAL ALARM

SHUT OFF

VALVE

RETARD

WATER

MOTOR

GONG

EPS10EXP

WET

SYSTEM

ALARM

CHECK

VALVE

OS & Y

VALVE

WATER

BY-PASS

VALVE

LOCAL ALARM

SHUT OFF

VALVE

RETARD

WATER

MOTOR

GONG

EPS10EXP

DRY

SYSTEM

ALARM

CHECK

VALVE

OS & Y

VALVE

WATER

BY-PASS

VALVE

LOCAL ALARM

SHUT OFF

VALVE

WATER

MOTOR

GONG

CHECK

VALVE

EPS10

WET SYSTEM

WET SYSTEM

DRY SYSTEM

WIRE TO ALARM

INDICATING CIRCUIT

OF FIRE ALARM

CONTROL PANEL

WIRE TO ALARM

INDICATING CIRCUIT

OF FIRE ALARM

CONTROL PANEL

WIRE TO ALARM

INDICATING CIRCUIT

OF FIRE ALARM

CONTROL PANEL

TO

SPRINKLER

SYSTEM

TO

SPRINKLER

SYSTEM

TO

SPRINKLER

SYSTEM

Figure 2. Typical piping diagram for EPS10-1, EPS10-2

W0171-01

Figure 3. Switch terminals:

W0173-00

Table 1. Electrical connections (referenced at factory 
settings):

MODEL EPS10-1

MODEL EPS10-2

A

COM

B

SWITCHES AT 0 P.S.I.

SWITCH AT 0 P.S.I.

SWITCH AT 4-8 P.S.I. (HIGH TRIP PT.)

B

COM

A

B

COM

A

B

COM

A

A

COM

B

A

COM

B

SWITCH 1

BOTH SWITCHES ACTIVATE SIMULTANEOUSLY

SW1

SW2

SW1

SW2

SWITCHES AT 4-8 P.S.I. (HIGH TRIP PT.)

GROUND

SCREW

COM

B

A

COMMON

TERMINALS

BREAK WIRE AS SHOWN FOR

SUPERVISION OF CONNECTION.

DO NOT ALLOW STRIPPED WIRE

LEADS TO EXTEND BEYOND

SWITCH HOUSING. DO NOT

LOOP WIRES.

SWITCH #1

SWITCH #2

SW

ITC

H #2

LOCKING

SCREW

TERMINAL “A”

TERMINAL “B”

EPS10

EPS10

Содержание EPS10 Series

Страница 1: ... condition System Sensor is not responsible for devices that have been improperly installed tested or maintained CAUTION Do not use in potentially explosive atmospheres Do not leave unused wires exposed Specifications Contact Ratings 10 A 1 2 HP 125 250 VAC 2 5A 6 12 24 VDC Overall Dimensions See Figure 1 Operating Temperature Range 40 to 160 F Maximum Service Pressure 250 PSI Maximum Adjustment R...

Страница 2: ... Figure 3 and Table 1 WET SYSTEM ALARM CHECK VALVE OS Y VALVE WATER BY PASS VALVE LOCAL ALARM SHUT OFF VALVE RETARD WATER MOTOR GONG EPS10EXP WET SYSTEM ALARM CHECK VALVE OS Y VALVE WATER BY PASS VALVE LOCAL ALARM SHUT OFF VALVE RETARD WATER MOTOR GONG EPS10EXP DRY SYSTEM ALARM CHECK VALVE OS Y VALVE WATER BY PASS VALVE LOCAL ALARM SHUT OFF VALVE WATER MOTOR GONG CHECK VALVE EPS10 WET SYSTEM WET S...

Страница 3: ...nge of switch 4 Retest the set point several times to ensure accuracy of setting 5 Re seat locking screw Table 2 Factory Settings PSI MODEL Fall Low Switch Approx Reset Rise High Switch EPS10 1 EPS10 2 3 PSI diff 3 PSI diff 4 8 4 8 Approx Reset D770 08 00 3 I56 0551 007R NOTE The sensor assembly is not field replaceable Do not attempt to disassemble these parts If you have any questions consult Sy...

Страница 4: ...rn Authorization number send defective units postage prepaid to System Sensor Return Please refer to insert for the Limitations of Fire Alarm Systems Three Year Limited Warranty Department RA __________ 3825 Ohio Avenue St Charles IL 60174 Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to repair or replace units which are found to...

Отзывы: