background image

FIGURE 3: WIRING DIAGRAM

(+) SLC

(–) SLC

(–) POWER

(+) POWER

U.L. LISTED COM

PA

TIBLE

CONTROL

 P

ANEL

OPTIONAL SOUNDER INTERCONNECT*

CLASS A OPTIONAL WIRING

CLASS A OPTIONAL WIRING

(+) SLC

(–) SLC

SUP

 (–)

SUP

 (+)

* GROUPING OF UP TO 6 MODEL EBS SOUNDER BASES

INTELLIGENT

MONITOR MODULE

FIRST

SOUNDER

BASE

SECOND

SOUNDER

BASE

LAST

SOUNDER

BASE

UL LISTED 

EOL 

RESISTOR 

47k

NO
T

USED

NO
T

USED

NO
T

USED

SL

C +

EXT 
+

SL

C +

EXT 

SL

C –

UL

 LISTED 24V 

POWER  SUPPL

END OF LINE RELAY 

(EOLR-1 OR EQUIVALENT)

NO
T

USED

NO
T

USED

NO
T

USED

SL

C +

EXT 
+

SL

C +

EXT 

SL

C –

NO
T

USED

NO
T

USED

NO
T

USED

SL

C +

EXT 
+

SL

C +

EXT 

SL

C –

C0970-13

DETECTOR ACTIVATES SOUNDER BASE(S) - (COMPLIES WITH UL268 AND UL464)

PLASTIC LEVER

BREAK TAB AT

DOTTED LINE BY

TWISTING TOWARD

CENTER OF BASE.

USE SMALL-BLADED

SCREWDRIVER TO

PUSH PLASTIC LEVER

IN DIRECTION OF

ARROW.

FIGURE 5A. ACTIVATING THE TAMPER-RESIST FEATURE:  

C0144-00

FIGURE 5B. REMOVING THE DETECTOR HEAD FROM THE BASE:

C1082-00

SLOT

SLOT

TAMPER-RESIST FEATURE

NOTE: Do not use the tamper-resist feature if the removal tool will be used.
The detector base includes a tamper-resist feature that prevents removal of 
the detector from the base without  using a small screwdriver or similar tool. 

To activate this feature, use needle-nose pliers to break the tab on the detector 
base as shown in Figure 5A. Then, install the detector.

To remove the detector from the base once the tamper-resist feature has been 
activated, insert a small-bladed screwdriver into the slot from the top and 
press down on the lever (see Figure 5B). This allows the detector to be rotated 
counterclockwise for removal.

The tamper-resist feature can be defeated by breaking and removing the plastic 
lever from the base. However, this prevents the feature from being used again.

FIGURE 4:

C0473-00

  

I56-3742-001R 

 

 06-10

firealarmresources.com

Содержание EBS

Страница 1: ...17 4 cm Base Height less sensor 1 61 in 4 1 cm Operating Temperature Range Refer to applicable sensor Operating Temperature Range using the Base Sensor Cross Reference Chart at systemsensor com Operating Humidity Range 10 to 93 relative humidity Non condensing External Supply Electrical Ratings External Supply Voltage 16 to 33 VDC VFWR Standby Current 500 μA maximum Alarm Current 35 mA maximum SLC...

Страница 2: ...configured as in Figure 3 reverse the polarity of the external 24VDC sup ply All EBS bases on the loop should sound 2 Latch the detector LED on from the control panel That individual detector s EBS should sound When performing maintenance on connected smoke detectors carefully note the location and address of each removed detector FIGURE 2 MOUNTING C0891 06 Horn Grouping No extra connections are r...

Страница 3: ...4 00 FIGURE 5B REMOVING THE DETECTOR HEAD FROM THE BASE C1082 00 SLOT SLOT TAMPER RESIST FEATURE NOTE Do not use the tamper resist feature if the removal tool will be used The detector base includes a tamper resist feature that prevents removal of the detector from the base without using a small screwdriver or similar tool To activate this feature use needle nose pliers to break the tab on the det...

Страница 4: ...ve units postage prepaid to Honeywell THREE YEAR LIMITED WARRANTY 12220 Rojas Drive Suite 700 El Paso TX 79936 USA Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to repair or replace units which are found to be defective because of damage unreasonable use modifications or alterations occurring after the date of manufacture In no c...

Отзывы: