D500-08-00

2

I56-512-07R

Note 1:

The inlet sampling tube must be ordered separate-
ly. It must be the correct length for the width of the
duct where it will be installed. See Table 1 to deter-
mine the inlet tube required for different duct
widths. Smoke detector heads (1551, ionization;
2551, photoelectronic) must be ordered separately.

Installation Sequence

Page

Step 1. Verify duct air flow direction and velocity

2

Step 2. Drill the mounting holes

3

Step 3. Secure the housing base to the duct

3

Step 4. Install the inlet sampling tube

3

Step 5. Field wiring

5

Step 6. Install the filters and check pressure differential 5
Step 7. Perform detector check

7

Step 8. Install the cover

8

Step 9. Perform the final system check (Testing)

8

Step 1. Verify Duct Air Flow Direction and Velocity

The DH500 is designed to be used in air handling systems
having air velocities of 500 to 4000 feet per minute. Be sure
to check engineering specifications to ensure that the air
velocity in the duct falls within these parameters. If neces-
sary, an Alnor Model 6000-P velocity meter, Dwyer 460 dif-
ferential pressure gauge, or their equivalent, may be used
to check the air velocity in the duct.

A78-2093-00

SAMPLING TUBE

FILTERS

CONDUIT HOLES

DUCT DETECTOR 

HOUSING

TERMINAL STRIP

DUCT DETECTOR

COVER

SAMPLING TUBE

MOUNTING

SCREWS

DETECTOR HEAD

(SUPPLIED SEPARATELY)

EXHAUST 

FILTER ADAPTER

DETECTOR BASE

INLET SAMPLING TUBE

(SUPPLIED SEPARATELY)

O-RINGS

FOAM

GASKETS

HOUSING

MOUNTING SCREWS

TEST MAGNET

TUBE

END

PLUG

Figure 1:

Step 2. Drill the Mounting Holes

Remove the paper backing from the top and bottom of the
template. Affix the template to the air duct at the desired
mounting location. Make sure the template lies flat and
smooth on the air duct. Center punch hole targets and
remove the template. Drill the holes as indicated on the
template. Slide the two speed nuts over the two small holes
(Hole A) next to the sampling tube bushing holes (Hole B)
previously drilled in the duct. (See Figure 2.)

Step 3. Mount Duct Housing

Remove the duct housing cover. Slide the foam gaskets over
the tube bushings as shown in Figure 2B. Make sure the
two small holes in the gaskets line up with the two base
mounting holes. Put one 5/16-inch O-ring over each of the
two #10 sheet metal screws. Use the two sheet metal screws
to secure the duct housing to the duct.

Do not overtighten the screws.

CAUTION

Содержание DH500

Страница 1: ...ng hazardous condition When sufficient smoke is sensed an alarm signal is initiated at the fire control panel monitoring the detector and appropriate action can be taken to shut off fans and Specifications Length 14 5 inches 36 7 cm Width 5 inches 12 7 cm Depth 3 5 inches 8 9 cm Weight 2 8 lbs 1 1 kg Operating Temperature Range 32 to 120 F 0 to 49 C Operating Humidity Range 10 to 93 Relative Humid...

Страница 2: ...tial pressure gauge or their equivalent may be used to check the air velocity in the duct A78 2093 00 SAMPLING TUBE FILTERS CONDUIT HOLES DUCT DETECTOR HOUSING TERMINAL STRIP DUCT DETECTOR COVER SAMPLING TUBE MOUNTING SCREWS DETECTOR HEAD SUPPLIED SEPARATELY EXHAUST FILTER ADAPTER DETECTOR BASE INLET SAMPLING TUBE SUPPLIED SEPARATELY O RINGS FOAM GASKETS HOUSING MOUNTING SCREWS TEST MAGNET TUBE EN...

Страница 3: ...ations of tube mounting configurations with respect to air flow A Installation for Ducts Less Than 8 Feet Wide 1 If the inlet tube is longer than the width of the air duct drill a 3 4 inch hole in the duct directly opposite the hole already cut for the inlet tube If the inlet tube is shorter than the width of the air duct install the end cap into the inlet tube see Figure 3 2 Slide the inlet tube ...

Страница 4: ...rted by other means WARNING AIR FLOW DIRECTION DUCT DETECTOR HOUSING DOTS INDICATE POSITION OF SAMPLING TUBE HOLES AIR FLOW DIRECTION DUCT DETECTOR HOUSING INLET TUBE EXHAUST TUBE AIR FLOW DIRECTION INLET TUBE EXHAUST TUBE INLET TUBE EXHAUST TUBE DUCT DETECTOR HOUSING AIR FLOW DIRECTION EXHAUST TUBE INLET TUBE DUCT DETECTOR HOUSING Figure 4 Tube mounting configurations with varying air flow direct...

Страница 5: ...nder the plate and tightening the clamping plate screw Step 6 Install the Filters Most duct installations are subject to dust accumulation System filters remove a large percentage of this contamina tion but cannot remove all of it Dust inside the duct detec tor causes problems First very fine particles of dust can enter the detector sensing chamber and cause the unit to go into alarm Second the ac...

Страница 6: ... UNIT 95mA CURRENT DRAW 4 5 3 2 1 Unused Remote Test RA400Z RTS451 RTS451KEY RA400Z or RTS451 RTS451KEY Comm Line Comm Line Alarm Initiation Loop Comm Line UL Listed Control Panel 1st Detector in Loop 2nd Detector in Loop The RTS451 RTS451KEY test coil circuit requires an external 24VDC power supply which must be UL listed Figure 5C System wiring diagram for duct detectors using a UL listed contro...

Страница 7: ...not sense smoke in the air duct 7 2 Alarm Tests Before replacing the duct housing cover the detector inter connections should be checked The DH500 may be checked as follows A M02 04 00 Magnet Test 1 Make sure power is applied to the detector 2 Place the painted surface of the test magnet against the housing next to the rib molded onto the outside of the housing see Figure 7 3 The LEDs on the detec...

Страница 8: ...n their prop er positions Tighten the four cover screws to 10 in lbs Step 9 Perform the Final System Check Place the magnet in position as shown in Figure 7 The LEDs on the detector should light Any accessory LED s will also light The system control panel should indicate an alarm condition Periodic Maintenance Requirements Air duct smoke detectors should be maintained at least once a year They sho...

Страница 9: ...n by aligning arrow on top with the field test slot on the base of the detector Push screen into place Screen should fit tightly to chamber Ionization Units 9 Remove the detector cover and screen assembly by depressing the three lock prongs on the top of the cover and rotating the cover counterclockwise The CRT400 Cover Removal Tool makes cover removal easier See Figure 11 10 Carefully pull the sc...

Страница 10: ...mote LED RA400ZA Remote Test Station RTS451 RTS451KEY Piezo Alert Sounder PA400 Replacement Filters F36 05 00 Magnet M02 04 00 End Plug For Sampling Tube P48 21 00 Installation Kit Parts bag A2650 01 Ionization Replacement Screen RS14 Sensitivity Test Kit MOD400 Ionization Cover Removal Tool CRT400 Programming Specifications Requirements for Intelligent System Control Panels The 1551 and 2551 mode...

Страница 11: ... 7672 for a Return Authorization number send defective units postage prepaid to System Sensor Repair Department RA __________ 3825 Ohio Avenue St Charles IL 60174 Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to repair or replace units which are found to be defective because of damage unreasonable use modifications or alterations...

Страница 12: ...___________ ______________________________ ________ ____________ ________ ______________ ______________________________ ________ ____________ ________ ______________ ______________________________ ________ ____________ ________ ______________ ______________________________ ________ ____________ ________ ______________ ______________________________ ________ ____________ ________ ______________ ___...

Отзывы: