[5] Installation Sequence
[5.1] Verify Duct Air Flow Direction And Velocity

Model DH100ACDCLP detectors are designed to be used in air han-
dling systems having air velocities of 100 to 4000 feet per minute. 
Be sure to check engineering specifications to ensure that the air 
velocity in the duct falls within these parameters. If necessary, use a 
velocity meter (anemometer) to check the air velocity in the duct.

[5.2] Drill The Mounting Holes

Remove the paper backing from the mounting template supplied. 
Affix the template to the duct at the desired mounting location. 
Make sure the template lies flat and smooth on the duct. Center 
punch holes A and B. Drill the holes as indicated on the template.

[5.2.1] Sampling Tube Installation for Ducts Less 
Than 1

1

2

 Feet Wide (see Figure 2)

1.  Remove the front cover.
2.  Slide the plastic sampling tube into the housing bushing.
3.   Align the holes in the bushing with the holes in the sampling 

tube. Make sure there are 6 exposed holes on the plastic sam-
pling tube. Secure with the #8 self-tapping screw into the bot-
tom of the permanent tube (shown in Figure 2).

NOTE:

 The sampling tube end cap is critical to the proper opera-

tion of the duct smoke detector. The end cap is needed to create 
the proper air flow to the sensor of the duct smoke detector.

NOTE:

 For ducts greater than 1

1

2

 feet in width, refer to sections 

[5.4.1] and [5.4.2].

Figure 2. Plastic sampling tube connected to duct 
smoke detector:

H0110-00

[5.3] Secure The Detector Housing To The Duct

Slide the foam gaskets over the tube bushings as shown in Figure 
3. Use the two 1

1

/

4

˝ long sheet metal screws to screw the detector 

housing to the duct. 

CAUTION: Do not overtighten the screws.

Figure 3. Installation of foam gaskets over sampling tube 
bushings:

SCREW HOLES FOR
ATTACHING HOUSING
TO DUCT WORK.

H0107-00

[5.4] Sampling Tube Installation for Ducts Greater 
Than 1

1

2

 Feet Wide

The sampling tube is identified by a series of air inlet holes on 
the tube. A plastic tube is included for ducts up to 18˝ in width. 
All  other  lengths  must  be  purchased  separately.  Order  the  cor-
rect length, as specified in Table 1, for width of the duct where it 
will be installed. It is recommended that the sampling tube length 
extend at least 

2

3

 across the duct width for optimal performance. 

The exhaust tube is molded onto the base of the duct housing, 
and the A2440-00 Exhaust Tube Extension is available as an ac-
cessory in those cases where the molded exhaust port does not 
extend at least 2 inches into the duct. 
The  sampling  tube  is  always  installed  with  the  air  inlet  holes 
facing  into  the  air  flow.  To  assist  proper  installation,  the  tube’s 
mounting  flange  is  marked  with  an  arrow.  Make  sure  the  sam-
pling tube is mounted so that the arrow points into the air flow 
(see Figure 4). Figure 5 shows the various combinations of tube 
mounting  configurations  with  respect  to  air  flow.  Mounting  the 
detector housing in a vertical orientation is acceptable, provided 
that  the  air  flows  directly  into  the  sampling  tube  holes  as  indi-
cated in Figure 4.

D200-14-00 

I56-0084-009R

[4] Figure 1: Exploded View of Duct Smoke Detector Components

FOAM

GASKETS

METAL

SAMPLING TUBE

SAMPLING TUBE

FILTERS

DETECTOR

COVER

DETECTOR BOARD

CONDUIT HOLES

DETECTOR

HOUSING

TERMINAL STRIP

POWER BOARD

COVER MOUNTING

SCREWS

H0165-00

Содержание DH100ACDCLP

Страница 1: ...ry functions Auxiliary relays are also provided for fan shut down or signaling of up to 9 other detectors in the loop for multiple fan shut down These detectors are not designed for 2 wire applications For testing the alarm can be enabled by a magnet activated test switch or by the optional remote test station The duct smoke detector latches into alarm state when an alarm occurs A green LED flashe...

Страница 2: ... in Figure 3 Use the two 11 4 long sheet metal screws to screw the detector housing to the duct CAUTION Do not overtighten the screws Figure 3 Installation of foam gaskets over sampling tube bushings SCREW HOLES FOR ATTACHING HOUSING TO DUCT WORK H0107 00 5 4 Sampling Tube Installation for Ducts Greater Than 11 2 Feet Wide The sampling tube is identified by a series of air inlet holes on the tube ...

Страница 3: ...ng holes so that there are a total of 10 to 12 holes spaced as evenly as possible across the width of the duct NOTE Air currents inside the duct may cause excessive vibra tion especially when the longer sampling tubes are used In these cases a 3 floor flange available at most plumbing supply stores may be used to fasten the sampling tube to the other side of the duct When using the flange connecto...

Страница 4: ...an 18 gauge The duct smoke detector terminals accommodate wire sizes up to 12 gauge Smoke detectors and alarm system control panels have specifi cations for allowable loop resistance Consult the control panel manufacturer s specifications for the total loop resistance allowed for the particular model control panel being used before wiring the detector loop Wiring Instructions The DH100ACDCLP detec...

Страница 5: ...ntial fall below 0 0015 inches of water 6 2 Standby Alarm and Sensitivity Tests The cover must be removed to perform these tests The use of a remote accessory for visible indication of power and alarm is recommended 6 2 1 Standby And Trouble Standby Look for the presence of the flashing green LED The LED should flash approximately ev ery 10 seconds Trouble If the detector LED does not flash then t...

Страница 6: ...LE POWER INPUTS ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN ETC 16 6 17 7 18 8 N C C N O N O C N C ALARM AUXILIARY CONTACTS SHOWN IN STANDBY CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS SUPERVISORY TROUBLE CONTACTS TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY CONTACTS OPEN WHILE DETECTOR PCB OR POWER IS REMOVED OR WHEN TAMPER FEATURE TIMES OUT OPEN CONTACTS SIGNAL TROUBLE CONDITION TO P...

Страница 7: ...er in the same fashion Vacuum the screen and cover Use clean compressed air to loosen and blow out any remaining debris Replacement screens S08 39 01 are available 3 Vacuum photo chamber then use clean compressed air to blow area clean 4 Replace the chamber by pressing it onto the base Press the screen into place It should fit tightly on the chamber 8 0 Board Replacement 8 1 Detector Board Replace...

Страница 8: ...AC 50 60 Hz 120 VAC 50 60 Hz 220 240 VAC 50 60 Hz CURRENT REQUIREMENTS USING NO ACCESSORIES Max standby current 15 mA 35 mA RMS 25 mA RMS 15 mA RMS Max alarm current 70 mA 125 mA RMS 35 mA RMS 25 mA RMS CONTACT RATINGS Alarm initiation contacts SPST 2 0A 30 VDC resistive Alarm auxiliary contacts DPDT 10A 30 VDC 10A 250 VAC 1 4 HP 240 VAC 1 8 HP 120 VAC Trouble contacts SPDT 2 0A 30 VDC resistive 2...

Отзывы: