fIgURE 10. wIRINg DIAgRAM fOR RTS451/RTS151/RTS451kEy/RTS151kEy REMOTE TEST STATION TO
2-wIRE D2-AUS DUCT DETECTOR:
24 VAC (+10%, –15%)
FULL WAVE RECTIFIED,
UNFILTERED POWER
MAY BE USED
RTS451/RTS451KEY
(OPTIONAL) REMOTE
TEST STATION
MAGNET
TEST
SWITCH
ALARM
LED (RED)
4
5
2
1
(+)
(–)
+ RA
+ RTS
– RA
+ TEST COIL
– TEST COIL
+ IN
+ OUT
–
(–)
(+)
D2-AUS
24 VDC
AUX POWER
SUPPLIED
BY USER
(100mA
SUPPLY)
RTS451/RTS451KEY
(OPTIONAL) REMOTE
TEST STATION
24 VAC (+10%, –15%)
FULL WAVE RECTIFIED,
UNFILTERED POWER
MAY BE USED
MAGNET
TEST
SWITCH
ALARM
LED (RED)
4
5
2
1
(+)
(–)
+ RA
+ RTS
– RA
+ TEST COIL
– TEST COIL
+ IN
+ OUT
–
24 VDC
AUX POWER
SUPPLIED
BY USER
(100mA
SUPPLY)
D2-AUS
NOTE:
THE USE OF EITHER THE RTS451 OR RTS451KEY REQUIRES THE INSTALLATION OF AN ACCESSORY COIL, DCOIL, SOLD
SEPARATELY. SEE FIGURE 9 ABOVE FOR REFERENCE.
METHOD #1 - AUX POWER LOCATED
AT DUCT DETECTOR
METHOD #2 - AUX POWER LOCATED
AT TEST STATION
H0612-13
SS-300-023
6
I56-3641-001R
©2010 System Sensor
ThREE-yEAR LIMITED wARRANTy
System Sensor warrants its enclosed product to be free from defects in materials and
workmanship under normal use and service for a period of three years from date of
manufacture. System Sensor makes no other express warranty for the enclosed product.
No agent, representative, dealer, or employee of the Company has the authority to in-
crease or alter the obligations or limitations of this Warranty. The Company’s obligation
of this Warranty shall be limited to the replacement of any part of the product which
is found to be defective in materials or workmanship under normal use and service
during the three year period commencing with the date of manufacture. After phoning
System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization
number, send defective units postage prepaid to: System Sensor, Returns Department, RA
#__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing
the malfunction and suspected cause of failure. The Company shall not be obligated to
replace units which are found to be defective because of damage, unreasonable use,
modifications, or alterations occurring after the date of manufacture. In no case shall the
Company be liable for any consequential or incidental damages for breach of this or any
other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by
the Company’s negligence or fault. Some states do not allow the exclusion or limitation of
incidental or consequential damages, so the above limitation or exclusion may not apply
to you. This Warranty gives you specific legal rights, and you may also have other rights
which vary from state to state.
Please refer to insert for the Limitations of Fire Alarm Systems
[13] OPTIONAL ACCESSORIES
The D2-AUS duct smoke detector can be used with the RA400Z/RA100Z,
RTS451/RTS151, or RTS451KEY/RTS151KEY remote test station.
fIgURE 8. wIRINg DIAgRAMS fOR OPTIONAL ACCESSORIES:
ALARM +
AUX OUT –
15
20
(+)
(–)
RED
RA400Z
(OPTIONAL)
REMOTE (LED)
ANNUNCIATOR
D2-AUS
DUCT DETECTOR
H0611-04
[13.1] RTS451/RTS151/RTS451kEy/RTS151kEy REMOTE TEST
STATION
The RTS451/RTS151/RTS451KEY/RTS151KEY Remote Test Station facilitates
test of the alarm capability of the duct smoke detector as indicated in the
RTS451/RTS151/RTS451KEY/RTS151KEY manual. The D2-AUS duct smoke de-
tector must be reset by the system control panel. If a system control panel is
used, the panel itself may also require testing.
To install the RTS451/RTS151/RTS451KEY/RTS151KEY, connect the device as
shown in
Figure 10
on page 6; wire runs must be limited to 25 ohms or less
per interconnecting wire.
NOTE: The use of a remote test station requires the installation of an acces-
sory coil, part number DCOIL, sold separately. See Figure for reference.
1) Install DCOIL in housing pocket insuring that arrow is pointing toward detector
2) Install DCOIL mounting screw
3) Connect each DCOIL lead to a Test Coil Terminal
fIgURE 9. D2-AUS wITh OPTIONAL TEST COIL:
H0561-00
TEST COIL TERMINALS
TEST COIL
TEST COIL SCREW