INSTALLATION AND MAINTENANCE INSTRUCTIONS 

B501AUS Plug-in Detector  Base 

SPECIFICATIONS 

Base Diameter:  
Base Height: 
Operating Temperature: 

4.0 inches (10.2cm) 
0.74 inches (18.8 mm) 
Refer to applicable sensor Operating Temperature Range using the Base/Sensor Cross Reference Chart at 

t

Electrical Ratings – includes base and detector

 

Operating Voltage: 
Standby Current: 

15 to 32 VDC 
150µA 

BEFORE INSTALLING 

Please read the 

System Smoke Detectors Application Guide

, which provides 

detailed information on detector spacing, placement, zoning, wiring, and spe-
cial applications.  Copies of this application guide are available from Xi’an 
System Sensor. NFPA 72 guidelines should be observed. 

NOTICE

: This manual should be left with the owner/user of this equipment. 

IMPORTANT

: The detector used with this base must be tested and main-

tained regularly following NFPA 72 requirements. The detector should be 
cleaned at least once a year. 

GENERAL DESCRIPTION 

The B501AUS is a plug in detector base intended for use in an intelligent 
system with screw terminals provided for power (+) and (–), and remote 
annunciator connections. Communication takes place over the power (+) and 
(–) lines. 

BASE TERMINALS 

For signal wiring (the wiring between interconnected detectors and modules),
it is recommended  that the wiring be no smaller than 18 AWG (0.823 square 
mm). Wire sizes up to 12 AWG (3.31 square mm) may be used with the 
base. 

Alarm system control panels have specifications for allowable loop 
resistance. Consult the control panel specifications for the total loop 
resistance allowed before wiring the detector loops. 

Make wiring connections by stripping about 3/8 inch (10mm) of insulation 
from the wire end (use strip gauge molded in base). Then slide the wire 
under the clamping plate and tighten the clamping plate screw. Do not loop 
the wire under the clamping plate. (see Figure 3) 

Check the zone wiring of all bases in the system before installing the 
detectors. This includes checking the wiring for continuity, correct polarity, 
ground fault testing and performing a dielectric test. 

The base includes an area for recording the zone, address, and type of 
detector to be installed at that location. This information is useful for setting 
the detector head address and for verification of the detector type required for 
that location. 

Once all detector bases have been wired and mounted, and the loop wiring 
has been checked, the detector heads may be installed in the bases. 

FIGURE  2. TYPICAL  WIRING DIAGRAM FOR 2-WIRE LOOP: 

No.

 

1

 

2

 

3

 

Function

 

Power (–), Remote Annunciator (–) 

Power (+) 

Remote Annunciator (+) 

FIGURE  1. TERMINAL LAYOUT :

 

TAMPER  PROOF 

TAB 

TERMINAL  2 

CAUTION: DO NOT LOOP WIRE

REMOTE

TERMINAL 1

TERMINAL  3 

UNDER TERMINAL 1 OR 2.

ANNUNCIATOR

BREAK WIRE RUN TO PROVIDE

+

-

SUPERVISION OF CONNECTIONS.

3

 

3

1

1

 

1

C0133-01

FIGURE  3.: 

C0131-01

MOUNTING 

This detector base mounts directly to 4 inch square with plaster ring, 3.5 inch 
octagon, single gang box, 50 mm, 60 mm, and 70 mm centers. 

INSTALLATION AND WIRING GUIDELINES  (SEE FIGURE  2) 

All wiring must be installed in compliance with all applicable local codes and 
any special requirements of the local authority having jurisdiction. Proper wire 
gauges should be used. The conductors used to connect smoke detectors to 
control panels and accessory devices should be color-coded to reduce the 
likelihood of wiring errors. Improper connections can prevent a system from 
responding properly in the event of a fire. 