background image

1

I56-351-03

B401R Plug-in Detector Base

INSTALLATION AND MAINTENANCE INSTRUCTIONS

A Division of Pittway

 System Sensor Europe

Via Caboto 19, 34143, Trieste, Italy

Before Installing

Please thoroughly read the System Sensor Manual I56-407,

Guide For Proper Use of System Smoke Detectors

, which pro-

vides detailed information on detector spacing, placement,
zoning, wiring, and special applications. Copies of this
manual are available at no charge from System Sensor.

NOTICE: 

This manual should be left with the owner/user

of this equipment.

IMPORTANT: 

 The detector used with this base must be

tested and maintained regularly following NFPA 72 require-
ments. The detector used with this base should be cleaned
at least once a year.

For use with the following smoke detectors: 1451E and 2451E

Specifications

Diameter:

10.2 cm (4.0 inches)

Height:

2.0 cm (0.8 inches)

Weight:

152 g (0.34 lb.)

Operating Temperature:

–10

°

 to +60

°

C (14

°

 to 140

°

F)

Operating Humidity:

10% to 93% Relative Humidity

Electrical Ratings — includes base and detector

Voltage:

24 VDC

Maximum Ripple Voltage:

4 Volts peak to peak

Start-up Capacitance:

0.02 

µ

F Maximum

Standby Ratings:

15 VDC Minimum
32 VDC Maximum
120 

µ

A Maximum

Alarm Ratings:

10 mA Minimum at 10.5 VDC
62mA Maximum at 32 VDC
(If used, the RA400Z Remote Annunciator operates within the specified
detector alarm currents.)

Reset Voltage:

2.5 VDC Minimum

General Description

The B401R plug-in detector base is used with System Sen-
sor model 2451E photoelectronic detector head and model
1451E ionization detector head. The capability of plugging
these detectors into a variety of special bases makes them
more versatile than equivalent direct-wired models. Refer
to the System Sensor catalog for other plug-in detector
bases.

The B401R base is intended for use in 2-wire systems, with
screw terminals provided for power, ground, and remote
annunciator connections. The B401R base also contains a
resistor to provide current limiting in the alarm state.

firealarmresources.com

Отзывы: