WIRING INSTRUCTIONS
Make wiring connections by stripping about
3
/
8
" (10 mm) of insulation from
the wire end. Then, insert the wire into the appropriate terminal and tighten
the screw. Wire the communication line in (+) to terminal 1. Insert both
communication line in (–) and communication line out (–) to terminal 2. Wire
communication line out (+) to terminal 3 (see Figures 3 and 4).
A label is affixed to the base for recording the zone, address, and type of
detector being installed at the base location. This information is useful for set-
ting the detector head address and for verification of the sensor type required
for that location.
Once all detector bases have been wired and mounted, and the loop wiring
has been checked, the detector heads may be installed in the bases.
TAMPER-RESIST FEATURE
NOTE:
Do not use the tamper-resist feature if the removal tool is to be used.
This detector base includes a tamper-resist feature that prevents its removal
from the base without the use of a tool.
To activate this feature, break the tab from the detector base as shown in
Figure 5A. Then, install the detector.
To remove the detector from the base once the tamper-resist feature has been
activated, insert a small-bladed screwdriver into the slot from the top and
press down on the lever (see Figure 5B). This allows the detector to be rotated
counterclockwise for removal.
The tamper-resist feature can be defeated by breaking and removing the plas-
tic lever from the base. However, this prevents the feature from being used
again.
Please refer to insert for the Limitations of Fire Alarm Systems
THREE-YEAR LIMITED WARRANTY
System Sensor warrants its enclosed smoke detector base to be free from defects in ma-
terials and workmanship under normal use and service for a period of three years from
date of manufacture. System Sensor makes no other express warranty for this smoke
detector base. No agent, representative, dealer, or employee of the Company has the au-
thority to increase or alter the obligations or limitations of this Warranty. The Company’s
obligation of this Warranty shall be limited to the replacement of any part of the smoke
detector base which is found to be defective in materials or workmanship under normal
use and service during the three year period commencing with the date of manufacture.
After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return
Authorization number, send defective units postage prepaid to: Honeywell, 12220 Rojas
Drive, Suite 700, El Paso TX 79936, USA. Please include a note describing the malfunc-
tion and suspected cause of failure. The Company shall not be obligated to replace units
which are found to be defective because of damage, unreasonable use, modifications,
or alterations occurring after the date of manufacture. In no case shall the Company
be liable for any consequential or incidental damages for breach of this or any other
Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the
Company’s negligence or fault. Some states do not allow the exclusion or limitation of
incidental or consequential damages, so the above limitation or exclusion may not apply
to you. This Warranty gives you specific legal rights, and you may also have other rights
which vary from state to state.
(+)
(–)
(–)
(+)
(–)
(+)
(+)
(–)
(–)
(+)
(–)
(+)
3 (+)
2 (–)
2 (–)
1 (+)
2 (–)
1 (+)
3 (+)
2 (–)
(+)
(–)
(–)
(+)
(+)
(–)
(–)
(+)
2 (–)
2 (–)
3 (+)
1 (+)
2 (–)
2 (–)
3 (+)
1 (+)
(+)
(–)
COMMUNICATION LINE
ALL WIRING SHOWN IS SUPERVISED.
A PAIR OF FAULT ISOLATOR BASES WILL
DISCONNECT A GROUP OF DEVICES IF A
SHORT CIRCUIT OCCURS ON THE SIGNALING
LINE CIRCUIT WITHIN THAT GROUP.
GROUPS OF ADDRESSABLE DEVICES ARE
SEPERATED BY FAULT ISOLATOR BASES. ANY
COMBINATION OF COMPATIBLE LISTED DEVICES
MAY BE MIXED WITHIN A GROUP
COMPATIBLE
CONTROL PANEL
GROUP 1
GROUP 2
GROUP 3
C1013-01
FIGURE 4. WIRING DIAGRAM
FIGURE 5A. ACTIVATING THE TAMPER-RESIST FEATURE
PLASTIC LEVER
BREAK TAB AT DOTTED LINE BY
TWISTING TOWARD CENTER OF BASE.
USE SMALL-BLADED SCREWDRIVER TO PUSH
PLASTIC LEVER IN DIRECTION OF ARROW.
C1065-00
FIGURE 5B. REMOVING THE DETECTOR HEAD FROM THE BASE
SLOT
SLOT
C1082-00
System Sensor® is a registered trademark of Honeywell International, Inc.
NOTE:
B224BI-WH and B224BI-IV replace the previous model number
B224BI; all are functionally the same.
2
I56-3736-005
©2018 System Sensor. 02/01/2018