background image

D250-01-00

1

I56-595-03

B210LP Plug-in Detector Base

For use with the following models:
In US:

1251, 2251

In Canada:

1251A, 2251A

INSTALLATION AND MAINTENANCE INSTRUCTIONS

A Division of Pittway

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

Before Installing

Please thoroughly read the system wiring and installation
manuals, and manual I56-407, 

Guide for Proper Use of Sys-

tem Smoke Detectors,

 which provides detailed information

on detector spacing, placement, zoning, and special appli-
cations. Copies of these manuals are available from System
Sensor or through a System Sensor distributor. (For installa-
tion in Canada, refer to CAN/ULC-S524, 

Standard for the

Installation of Fire Alarm Systems

 and CEC Part 1, Sec. 32.)

General Description

The Plug-in Detector Base is used with System Sensor mod-
els 1251 and 1251A ionization and 2251 and 2251A photo-
electronic detectors.

The B210LP base is intended for use in a 2-wire intelli-
gent system, with screw terminals provided for power
(+ and –), and remote annunciator connections. Com-
munication takes place over the power (+ and –) lines.

Base Terminals

NO.

FUNCTION

1

Power (–), Remote Annunciator (–)

2

Power (+)

3

Remote Annunciator (+)

Mounting

This detector base mounts directly to 3-1/2 inch and 4 inch
octagon boxes, 4 inch square boxes (with or without plas-
ter rings) and single gang boxes. To mount, remove the
decorative ring by turning it in either direction to unhook
the snaps, then separate the ring from the base. Install the
base on the box using the screws supplied with the junc-
tion box and the appropriate mounting slots in the base.

3

2

1

BASE
TERMINALS

TAMPER PROOF

TAB

Specifications

Diameter:

6.1 inches (155 mm)

Mounting:

4 inch (102 mm) square box with or without plaster ring
Min. Depth: 1.5 inches (38 mm).
4 inch Octagon Box, Min. Depth - 1.5 inches (38 mm).
3-1/2 inch Octagon Box, Min. Depth - 1.5 inches (38 mm).
Single Gang Box, Min. Depth -  1.5 inches (38 mm).

Figure 1. Terminal layout:

 A78-1318-00

Technical Manuals Online! - http://www.tech-man.com

Содержание B210LP

Страница 1: ...rs The B210LP base is intended for use in a 2 wire intelli gent system with screw terminals provided for power and and remote annunciator connections Com munication takes place over the power and lines Base Terminals NO FUNCTION 1 Power Remote Annunciator 2 Power 3 Remote Annunciator Mounting This detector base mounts directly to 3 1 2 inch and 4 inch octagon boxes 4 inch square boxes with or with...

Страница 2: ...ectrical interference If shielded cable is used the shield connection to and from the detector must be continuous by using wire nuts crimp ing or soldering as appropriate for a reliable connection Make electrical connections by stripping about 3 8 10 mm of insulation from the end of the wire use strip gauge molded in base sliding the bare end of the wire under the clamping plate and tightening the...

Страница 3: ...E ANNUNCIATOR CAUTION Do not loop wire under terminal 1 or 2 Break wire run to provide supervision of connections Figure 3 Typical Wiring Diagram for 2 wire loop A78 1253 00 PLASTIC LEVER BREAK TAB AT DOTTED LINE BY TWISTING TOWARD CENTER OF BASE USE SMALL BLADED SCREWDRIVER TO PUSH PLASTIC LEVER IN DIRECTION OF ARROW A78 1175 03 To remove the detector from the base after it has been made tamper r...

Страница 4: ... initiated which will generate the heat needed to drive the smoke to the ceiling Smoke from fires in chimneys in walls on roofs or on the other side of a closed door s may not reach the smoke detector and alarm it A detector cannot detect a fire developing on another level of a building quickly or at all For these reasons detectors shall be located on every level and in every bedroom within a buil...

Отзывы: