(+) SLC
(+) SLC
NO 1
NO 2
NC 2
COMM 2
COMM 1
NC 1
(–) SLC
(–) SLC
(–) POWER
(+) POWER
U.L. LISTED COM
PA
TIBLE
CONTRO
L
PA
NE
L
OPTIONAL SOUNDER INTERCONNECT*
NO
T
USED
SL
C
+
EXT
–
EXT
+
RA
SL
C
–
NO
T
USED
SL
C
+
EXT
–
EXT
+
RA
SL
C
–
(+) SLC
(–) SLC
SU
P
(–
)
SU
P
(+)
* GROUPING OF UP TO 6 MODEL B200SR-LF LOW FREQUENCY SOUNDER BASES
INTELLIGENT
MONITOR MODULE
INTELLIGENT
RELAY MODULE†
FIRST
SOUNDER
BASE
LAST
SOUNDER
BASE
†THIS IS A STANDARD RELAY
MODULE CONFIGURED TO
REVERSE THE POWER
UL LISTED
EOL
RESISTOR
47k
UL
LISTED 24V
POWER SUPPL
Y
END OF LINE RELAY
(EOLR-1 OR EQUIVALENT)
TO OPTIONAL REMOTE
ANNUNCIATOR
MODEL RA400Z/100Z
FIGURE 4: WIRING DIAGRAM
FIGURE 5: WIRING DIAGRAM
(+) SLC
(–) SLC
(–) POWER
(+) POWER
U.L. LISTED COM
PA
TIBLE
CONTRO
L
PA
NE
L
OPTIONAL SOUNDER INTERCONNECT*
TO OPTIONAL REMOTE
ANNUNCIATOR
MODEL RA400Z/100Z
CLASS A OPTIONAL WIRING
CLASS A OPTIONAL WIRING
NO
T
USED
SL
C
+
EXT
–
EXT
+
RA
SL
C
–
NO
T
USED
SL
C
+
EXT
–
EXT
+
RA
SL
C
–
(+) SLC
(–) SLC
SU
P
(–
)
SU
P
(+)
* GROUPING OF UP TO 6 MODEL B200SR-LF LOW FREQUENCY SOUNDER BASES
INTELLIGENT
MONITOR MODULE
FIRST
SOUNDER
BASE
SECOND
SOUNDER
BASE
LAST
SOUNDER
BASE
UL LISTED
EOL
RESISTOR
47k
NO
T
USED
SL
C
+
EXT
–
EXT
+
RA
SL
C
–
UL
LISTED 24V
POWER SUPPL
Y
END OF LINE RELAY
(EOLR-1 OR EQUIVALENT)
C0970-14
C0970-15
DETECTOR ACTIVATES SOUNDER BASE(S) - (COMPLIES WITH UL268)
UL has approved grouping for up to six B200SR-LF low frequency sounder bases. When wired as a group, any detector in the group that has been activated by
the panel will cause other B200SR-LF units in the group to sound. This type of “local” grouping is accomplished by wiring the grouped devices together using
terminal 6, Sounder Base Interconnect, as shown in the diagram. This interconnect can also be used to attach B200SR-LF devices to System Sensor B501-Series
sounder bases. Some Fire Alarm Control Panels (FACP) support the grouping of sounder bases via software in lieu of the Sounder Base Interconnect.
NOTE: A local grouping of horns via the sounder base interconnect is not supervised, therefore the groups can only be used as a supplementary evacuation
system. It is not acceptable to group horns via the sounder base interconnect for primary alarm signaling. Sounder bases which are grouped via software are not
subject to this limitation and may be used as part of the primary alarm signaling.
DETECTOR ACTIVATES SOUNDER BASE(S);
INTELLIGENT RELAY MODULE ACTIVATES ALL SOUNDER BASES - (COMPLIES WITH UL 268 AND UL 464)
UL has approved grouping for up to six B200SR-LF low frequency sounder bases. When wired as a group, any detector in the group that has been activated by
the panel will cause other B200SR-LF units in the group to sound. This type of “local” grouping is accomplished by wiring the grouped devices together using
terminal 6, Sounder Base Interconnect, as shown in the diagram. Some Fire Alarm Control Panels support the grouping of sounder bases via software in lieu of
the Sounder Base Interconnect.
NOTE: A local grouping of horns via the sounder base interconnect is not supervised, therefore the groups can only be used as a supplementary evacuation
system. It is not acceptable to group horns via the sounder base interconnect for primary alarm signaling. Sounder bases which are grouped via software
are not subject to this limitation and may be used as part of the primary alarm signaling.
3
I56-4152-003R
06-10