System Sensor B200SR-LF Скачать руководство пользователя страница 3

(+) SLC

(+) SLC

NO 1

NO 2

NC 2

COMM 2

COMM 1

NC 1

(–) SLC

(–) SLC

(–) POWER

(+) POWER

U.L. LISTED COM

PA

TIBLE

CONTRO

PA

NE

L

OPTIONAL SOUNDER INTERCONNECT*

NO
T

USED

SL

+

EXT 

EXT 
+

RA

SL

NO
T

USED

SL

+

EXT 

EXT 
+

RA

SL

(+) SLC

(–) SLC

SU

(–

)

SU

(+)

* GROUPING OF UP TO 6 MODEL B200SR-LF LOW FREQUENCY SOUNDER BASES

INTELLIGENT

MONITOR MODULE

INTELLIGENT

RELAY MODULE†

FIRST

SOUNDER

BASE

LAST

SOUNDER

BASE

†THIS IS A STANDARD RELAY

MODULE CONFIGURED TO 

REVERSE THE POWER

UL LISTED 

EOL 

RESISTOR 

47k

UL

 LISTED 24V

 

POWER  SUPPL

END OF LINE RELAY 

(EOLR-1 OR EQUIVALENT)

TO OPTIONAL REMOTE 

ANNUNCIATOR

MODEL RA400Z/100Z

FIGURE 4: WIRING DIAGRAM

FIGURE 5: WIRING DIAGRAM

(+) SLC

(–) SLC

(–) POWER

(+) POWER

U.L. LISTED COM

PA

TIBLE

CONTRO

PA

NE

L

OPTIONAL SOUNDER INTERCONNECT*

TO OPTIONAL REMOTE 

ANNUNCIATOR

MODEL RA400Z/100Z

CLASS A OPTIONAL WIRING

CLASS A OPTIONAL WIRING

NO
T

USED

SL

+

EXT 

EXT 
+

RA

SL

NO
T

USED

SL

+

EXT 

EXT 
+

RA

SL

(+) SLC

(–) SLC

SU

(–

)

SU

(+)

* GROUPING OF UP TO 6 MODEL B200SR-LF LOW FREQUENCY SOUNDER BASES

INTELLIGENT

MONITOR MODULE

FIRST

SOUNDER

BASE

SECOND

SOUNDER

BASE

LAST

SOUNDER

BASE

UL LISTED 

EOL 

RESISTOR 

47k

NO
T

USED

SL

+

EXT 

EXT 
+

RA

SL

UL

 LISTED 24V 

POWER  SUPPL

END OF LINE RELAY 

(EOLR-1 OR EQUIVALENT)

C0970-14

C0970-15

DETECTOR ACTIVATES SOUNDER BASE(S) - (COMPLIES WITH UL268)

UL has approved grouping for up to six B200SR-LF low frequency sounder bases. When wired as a group, any detector in the group that has been activated by 
the panel will cause other B200SR-LF units in the group to sound. This type of “local” grouping is accomplished by wiring the grouped devices together using 
terminal 6, Sounder Base Interconnect, as shown in the diagram.  This interconnect can also be used to attach B200SR-LF devices to System Sensor B501-Series 
sounder bases. Some Fire Alarm Control Panels (FACP) support the grouping of sounder bases via software in lieu of the Sounder Base Interconnect.

NOTE: A local grouping of horns via the sounder base interconnect is not supervised, therefore the groups can only be used as a supplementary evacuation 
system. It is not acceptable to group horns via the sounder base interconnect for primary alarm signaling. Sounder bases which are grouped via software are not 
subject to this limitation and may be used as part of the primary alarm signaling.

DETECTOR ACTIVATES SOUNDER BASE(S);  

INTELLIGENT RELAY MODULE ACTIVATES ALL SOUNDER BASES - (COMPLIES WITH UL 268 AND UL 464)

UL has approved grouping for up to six B200SR-LF low frequency sounder bases. When wired as a group, any detector in the group that has been activated by 
the panel will cause other B200SR-LF units in the group to sound. This type of “local” grouping is accomplished by wiring the grouped devices together using 
terminal 6, Sounder Base Interconnect, as shown in the diagram. Some Fire Alarm Control Panels support the grouping of sounder bases via software in lieu of 
the Sounder Base Interconnect.

NOTE:  A local grouping of horns via the sounder base interconnect is not supervised, therefore the groups can only be used as a supplementary evacuation 

system. It is not acceptable to group horns via the sounder base interconnect for primary alarm signaling. Sounder bases which are grouped via software 
are not subject to this limitation and may be used as part of the primary alarm signaling.

  

I56-4152-003R 

 

 06-10

Отзывы: