background image

D150-02-00

1

I56-598-03R

B114LP Plug-in Detector Base

For use with the following smoke detectors:
IN US:

1151, 2151

IN CANADA:

1151A, 2151A

IN EUROPE:

1151E, 2151E

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue

St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

Before Installing

Please thoroughly read the System Sensor manual I56-407,

Guide for Proper Use of System Smoke Detectors

. This man-

ual provides detailed information on detector spacing,
placement, zoning, wiring, and special applications, and is
available at no charge from System Sensor. (For installation
in Canada, refer to CAN/ULC-S524, 

Standard for the

Installation of Fire Alarm Systems

and CEC Part 1, Sec. 32.)

NOTICE:

This manual should be left with the owner/user

of this equipment.

IMPORTANT:

The detector used with this base must be

tested and maintained regularly following NFPA 72 require-
ments. The detector used with this base should be cleaned
at least once a year.

Specifications

Base Diameter:

6.2 inches (157 mm)

Base Height:

0.95 inches (24 mm)

Weight:

0.6 lb. (274 g)

Mounting:

4-inch square box with or without plaster ring. Min. depth–1.5 inches 
4-inch octagon box. Min. depth–1.5 inches

Operating Temperature Range:

0° to 49°C (32° to 120°F)

Operating Humidity Range:

10% to 93% Relative Humidity, Noncondensing                

Electrical Ratings - includes base and detector

System Voltage:

120 VAC, 60 Hz

Relay Contact Ratings
Resistive or Inductive (60% power factor) load
Form A:

2.0A @ 30VAC/DC

Form C:

2.0A @ 30VAC/DC
0.6A @ 110VDC
1.0A @ 125VAC

Start-up Time:

36.0 Seconds maximum

(After 60 second reset)

General Description

The model B114LP detector base is designed for use with
System Sensor model 2151 photoelectronic and 1151 ioniza-
tion detector heads. This four-wire base is equipped with
screw terminals for the connection of power, ground, relay
connections, and an optional RA400Z remote annunciator.
It also includes a resistor that limits current when the asso-
ciated smoke detector is in the alarm state.

Mounting

The detector base mounts directly to 3-1/2 inch and 4-inch
octagon boxes and 4-inch square boxes, with or without
plaster rings. To mount the base, remove the decorative
ring by rotating it in either direction to unhook the snaps
before separating the ring from the base. Use the screws
supplied with the junction box to attach the base to the box
through the appropriate slots in the base. 

See Figure 2. Position the decorative ring around the base
and rotate it in either direction until the ring snaps into
place. 

Содержание B114LP

Страница 1: ...ox Min depth 1 5 inches Operating Temperature Range 0 to 49 C 32 to 120 F Operating Humidity Range 10 to 93 Relative Humidity Noncondensing Electrical Ratings includes base and detector System Voltage 120 VAC 60 Hz Relay Contact Ratings Resistive or Inductive 60 power factor load Form A 2 0A 30VAC DC Form C 2 0A 30VAC DC 0 6A 110VDC 1 0A 125VAC Start up Time 36 0 Seconds maximum After 60 second re...

Страница 2: ...r signal wiring the wiring between interconnected detec tors it is recommended that the wire be no smaller than AWG 18 However the screws and clamping plate in the base can accommodate wire sizes up to AWG 12 The use of twisted pair wiring for the power and loop is rec ommended to minimize the effects of electrical interference Wiring Instructions NOTE Refer the manufacturer s instructions for rel...

Страница 3: ...AC EOL SPECIFIED BY PANEL MANUFACTURER CONTROL PANEL SUPERVISORY RELAY ALARM RELAY SUPERVISORY RELAY ALARM RELAY EOL SPECIFIED BY PANEL MANUFACTURER NOTE ABOVE DIAGRAM SHOWS NFPA REQUIRED WIRING OF SUPERVISED SYSTEMS SCHEMATIC SHOWN BELOW FOR REFERENCE Figure 3 Wiring diagram for a typical 120VAC detector system Tamper resistance Feature NOTE Do NOT use the tamper resistance feature if the System ...

Страница 4: ... 800 SENSOR2 736 7672 for a Return Authorization number send defective units postage prepaid to System Sensor Repair Department RA __________ 3825 Ohio Avenue St Charles IL 60174 Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to repair or replace units which are found to be defective because of damage unreasonable use modification...

Отзывы: