background image

SS-400-011  1 I56-5151-001

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

5151 Plug-In Heat Detector

SPECIfICATIONS

Height: 

1.64 inches (42 mm)

Diameter: 

4.0 inches (102 mm)

Weight 

2.8 oz. (80g)

Operating Temperature Range: 

32° to 100°F (0° to 38°C)

Operating Humidity Range: 

10% to 93% Relative Humidity noncondensing

Operating voltage: 

8.5 to 35VDC

Standby Current: 

80μA @24VDC

Alarm Current: 

10mA Min. 130mA Max. (Must be limited by control panel)

Latching Alarm: 

Reset by momentary power interruption

Sensitivity: 

135°F (57°C) Fixed or 15°F/min rate-of-rise

BEfORE INSTALLING

This detector must be installed in compliance with the control panel installa-
tion manual and meet the requirements of the authority having jurisdiction. 
Inaddition, the National Fire Protection Association has published codes, stan-
dards, and recommended practices for the installation and use of detectors, 
NFPA 72.

Therefore,  the installer must be familiar with these requirements,  with  local 
codes, and any special requirements of the authority having jurisdiction. 

NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: The detector must be tested and maintained regularly following 
NFPA 72 requirements. The detector should be cleaned at least once a year.

GENERAL DESCRIPTION

The 5151 is a rate-of-rise with fixed temperature alarm, conventional 2-wire 
thermal detector. This detector is designed to provide open area protection 
with 50-foot spacing capability as approved by UL 521, RTI rating is classified 
as FAST in accordance with FM 3210. 

Two LEDs on each detector provide local 360° visible alarm indication. They 
flash every five seconds indicating that power is applied and the detector 
is working properly. The LEDs latch on in alarm. LEDs will be off when a 
trouble condition exists indicating that the detector sensitivity is outside the 
listed limit. Remote LED annunciator capability is standard and may be imple-
mented through an optional accessory RA100Z. The alarm can be reset only 
by a momentary power interruption. This detector may be tested by activating 
the internal reed switch with a magnet.

BASE WIRING GUIDE

Refer to the installation instructions for the plug-in detector base for electrical 
specifications and wiring instructions. The base provides screw terminals for 
power and remote annunciator connections.

INSTALLATION

NOTE: All wiring must conform to applicable local codes, ordinances, and 
regulations.

NOTE: Verify that all detector bases are installed, that the initiating-device 
circuits have been tested, and that the wiring is correct. (Refer to detector base 
manual for testing procedure.)

WARNING

Remove power from initiating-device circuits before installing detectors. 

1.  Install detectors:
 

 

a.  Place the detector into the detector base.

 

 

b.  Turn the detector clockwise until the detector drops into place.

 

 

c.  Continue turning detector clockwise to lock it in place.

2.  Tamper Resistance: 
 

   The detector bases can be made tamper resistant. When capability 

is enabled, detectors cannot be removed from the  base without the 
use of a tool. See the detector base installation manual of the detector 
base for details in using this capability.

3.  After all detectors have been installed, apply power to the control unit.
4.  Test the detector using the magnet as described under TESTING.
5.  Reset the detector at the system control panel.
6.  Notify the proper authorities that the system is back on line. 

TAMPER RESISTANCE

The detector bases include a feature that, when activated, prevents removal 
of the detector without the use of a tool. Refer to the installation instruction 
manual of the detector base to make use of this capability.

TESTING

Before testing, notify the proper authorities that the smoke detector system is 
undergoing maintenance and will temporarily be out of service. Disable the 
zone or system undergoing maintenance to prevent unwanted alarms. Detec-
tors must be tested after installation and as part of periodic maintenance. Test 
5151 as follows:

NOTE: Before testing the detector, check to ensure the LEDs blink. If they do 
not, the detector has lost power (check the wiring), it is defective (return it for 
repair), or the detector sensitivity is outside the listed limits.

A. Test Magnet (p/n M02-04-01 or M02-09-00)

1.   Place the magnet against the cover in the location designated by the 

raised mark to activate the test feature (see Figure 1).

2.   The LEDs should latch ON within 5 seconds indicating alarm and annun-

ciating the panel.

B. Direct Heat Method (Hair dryer of 1000-1500 watts)

1.   A hair dryer of 1000-1500 watts should be used to test the thermistor. 

Direct the heat toward the thermistors, holding the heat source approxi-
mately 12 inches from the detector in order to avoid damaging the plastic 
housing. 

2.   The LEDs on the detector should light when the temperature at the de-

tector reaches the set point. 

3.   Reset the detector at the system control panel. The detector will reset 

only after it has had sufficient time to cool.

Notify the proper authorities that the system is back on line.

Detectors that fail these tests should be cleaned as described under MAIN-
TENANCE and retested. If the detectors still fail these tests, they should be 
returned for repair.

MAINTENANCE

NOTE: Before cleaning notify the proper authorities that the system is under-
going maintenance, and therefore the system will temporarily be out of ser-
vice. Disable the loop or system undergoing maintenance to prevent unwanted 
alarms.

It is recommended that the sensor be removed from its mounting base for 
easier cleaning and that sensors be cleaned at least once a year. Use a vacuum 
cleaner to remove dust from the sensing chamber.

I56-5

15

1-00

1

Отзывы: