System Sensor 2WTR-B Скачать руководство пользователя страница 3

D100-99-00 

I56-2170-007R

1.  Wire the mounting base screw terminals per Figure 3a or Figure 3b, 

as applicable.

2.  Place  detector  on  the  base  and  rotate  clockwise.  The  detector  will 

drop into the base and lock into place with a “click”.

3.  After  all  detectors  have  been  installed,  apply  power  to  the  alarm 

control unit.

4.  Test each detector as described in Testing.
5.  Reset all the detectors at the alarm control unit.
6.  Notify the proper authorities that the system is in operation.

CAUTION

Dust  covers  are  an  effective  way  to  limit  the  entry  of  dust  into  
the smoke detector sensing chamber during construction. However, they 
may not completely prevent airborne dust particles from entering the de-
tector.  Therefore,  System  Sensor  recommends  the  removal  of  detectors 
before beginning construction or other dust producing activity. When re-
turning the system to service, be sure to remove the dust covers from any 
detectors that were left in place during construction.

CAUTION

Smoke detectors are not to be used with detector guards unless the combi-
nation has been evaluated and found suitable for that purpose.

CAUTION

When using the RRS-MOD with model 2WTA-B, do not mix the 2WTA-B 
with  other  model  smoke  detectors  and  dry  contact  closure  devices,  in-
cluding  mechanical  heat  detectors,  manual  pull  stations  and  waterflow 
switches.  Such  mixing  can  cause  a  direct  short  on  the  auxiliary  power 
terminals, damaging the control panel’s internal circuitry and/or damage 
devices connected to the initiating device circuit.

Testing

Detectors must be tested after installation and following maintenance.

NOTE:

 Before testing, notify the proper authorities that maintenance is be-

ing performed and the system will be temporarily out of service. Disable the 
zone or system undergoing maintenance to prevent any unwanted alarms.
Ensure proper wiring and power is applied. 

After power up, allow 80 sec-

onds for the detector to stabilize before testing.

Test i

3

 Series detectors as follows:

A. Test Switch

1.  An  opening  for  the  recessed  test  switch  is  located  on  the  detector 

housing (See Figure 4).

2.  Insert a small screwdriver or allen wrench (0.18˝ max.) into the test 

switch opening; push and hold.

3.  If the detector is within the listed sensitivity limits, the detector’s red 

LED should light within one second.

Figure 4: Recessed Test Switch Opening and
SENS-RDR Position

LED

RECESSED TEST SWITCH

POSITION SENS-RDR
AT AN ANGLE ON THE
OVAL AREA OR AT THE
CHAMBER OPENING
BY THE WORD “PAINT”

PUSH RECESSED
SWITCH WITH
A  0.18  MAX.
DIAMETER TOOL

S0110-00

B. Smoke Entry Test

Hold a smoldering punk stick or cotton wick at the side of the detector and 
gently blow the smoke through the detector until it alarms.

C. Direct Heat Method

Using  a  1000-1500  watt  hair  dryer,  direct  the  heat  toward  either  of  the 
thermistors.  Hold  the  heat  source  about  12  inches  from  the  detector  to 
avoid damage to the plastic. 

NOTE:

  For  the  above  tests,  the  detector  will  reset  only  after  the  power 

source has been momentarily interrupted. It is not necessary to reset the 
model 4WITAR-B, when smoke is used to initiate the alarm.
When testing the 4WITAR-B model, pressing the test switch will result in a 
non-latching local alarm that does not alarm at the control panel. Once the 
test button is released, the unit will return to its standby condition. Only 
the fixed-temperature heat sensor will cause the 4WITAR-B to initiate an 
alarm at the panel.
If  a  detector  fails  any  of  the  above  test  methods,  its  wiring  should  be 
checked and it should be cleaned as outlined in the Maintenance section. 
If the detector still fails, it should be replaced.
Notify the proper authorities when the system is back in service.

Loop Verification (models 2WTR-B and 2WTA-B only)

Loop verification is provided by the EZ Walk loop test feature. This feature 
is  for  use  with  i

3

  Series  compatible  control  panels  or  the  i

3

  Series  2W-

MOD2 module only. The EZ Walk loop test verifies the initiating loop wir-
ing and provides visual status indication at each detector. Refer to System 
Sensor literature for further information on the 2W-MOD2.

WARNING

The  2W-MOD2  has  replaced  the  previous  model  number  2W-MOD.  To 
ensure proper EZ Walk Test capabilities, do not use the 2W-MOD with i

model numbers 2WTR-B and 2WTA-B.

Table 3: EZ Walk Test Detector Modes

Green LED

Red LED

Proper Operation

Double blink 5 sec

Out of Sensitivity

Double Blink 5 sec

Freeze Condition

Double Blink 10 sec

NOTE: The EZ Walk loop test must not be used instead of alarm testing.

Maintenance

NOTE:

 Before performing maintenance on the detector, notify the proper 

authorities that maintenance is being performed and the system will be 
temporarily out of service. Disable the zone or system undergoing mainte-
nance to prevent any unwanted alarms. Power must be removed from the 
detector before performing maintenance of any kind.
1.  Remove the detector cover by turning counterclockwise. (See Figure 5.)
2.  Vacuum the cover or use canned air to remove any dust or debris.
3.  Remove the top half of the screen/sensing chamber by lifting straight 

up (Figure 5).

4.  Vacuum  or  use  canned  air  to  remove  any  dust  or  particles  that  are 

present on both chamber halves.

5.  Replace  the  top  half  of  the  screen/sensing  chamber  by  aligning  the 

arrow on the screen/sensing chamber with the arrow on the housing. 
Press down firmly until the screen/sensing chamber is fully seated. 

6.  Replace the detector cover by placing it over the screen/sensing cham-

ber and turning it clockwise until it snaps into place.

7.  Reinstall the detector and test. (See the Testing section.)
8.  Notify the proper authorities when the system is back in service.

Figure 5: Removing Screen/Sensing Chamber

REMOVABLE
DETECTOR
COVER

SCREEN/SENSING
CHAMBER
(TOP HALF)

DETECTOR
HOUSING

S0111-00

Содержание 2WTR-B

Страница 1: ...e RRS MOD All i3 Series detectors are designed to provide open area protection Two wire models must be used with compatible UL Listed panels only When used with an i3 Ready control panel or the i3 Series 2W MOD2 module refer to installation manual the 2WTR B and 2WTA B are ca pable of generating a maintenance needed signal The 2W MOD2 can indicate a need for cleaning replacement or a freeze troubl...

Страница 2: ...than 2 gauge apart under the same clamping plate Two Wire Compatibility System Sensor two wire smoke detectors are marked with a compatibility identifier located on the label on the back of the product For two wire models 2WTR B and 2WTA B connect detectors only to compatible alarm control panels as identified by System Sensor s two wire compatibility chart available at www systemsensor com NOTE M...

Страница 3: ...ither of the thermistors Hold the heat source about 12 inches from the detector to avoid damage to the plastic NOTE For the above tests the detector will reset only after the power source has been momentarily interrupted It is not necessary to reset the model 4WITAR B when smoke is used to initiate the alarm When testing the 4WITAR B model pressing the test switch will result in a non latching loc...

Страница 4: ... of the FCC Rules These limits are designed to pro vide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a parti...

Отзывы: