for five seconds. Wait two minutes for the duct smoke detector to alarm. If the
duct smoke detector alarms, air is flowing through the detector. Remove the
duct smoke detector cover and blow out the residual aerosol smoke from the
chamber and reset the duct smoke detector. Use duct tape to seal the aerosol
smoke entry hole.
*Aerosol smoke can be purchased from Home Safeguard Industries, model
25S Smoke Detector Tester, Malibu, CA. Phone: 310/457-5813. When used
properly, the canned smoke agent will cause the smoke detector to go into
alarm. Refer to the manufacturer’s published instructions for proper use of
the canned smoke agent.
CAUTION
Canned aerosol simulated smoke (canned smoke agent) formulas will vary
by manufacturer. Misuse or overuse to these products may have long term
adverse effects on the smoke detector. Consult the canned smoke agent
manufacturer’s published instructions for any further warnings or caution
statements.
SENSITIvITY vERIFICATION
The sensitivity of the sensor is confirmed to be operating within its allowable
range each time the sensor and power board LEDs blink every 5 seconds.
Note in a maintenance condition the sensor LEDs will blink red every 5 sec-
onds and power board will blink amber. The maintenance condition indicates
that the sensor is operating outside its original factory preset sensitivity and
shall be cleaned or replaced. This is a valid UL test.
Notify the proper authorities that the system is back on line.
Detectors that fail these tests should be cleaned as described below and re-
tested. If the detectors still fail these tests, they should be returned for repair.
CLEANINg
Before removing the detector, notify the proper authorities that the smoke
detector system is undergoing maintenance and will be temporarily out of
service. Disable the zone or system undergoing maintenance to prevent un-
wanted alarms.
1. Remove the sensor to be cleaned from the system.
2. Remove the sensor cover by pressing firmly on each of the four removal
tabs that hold the cover in place.
3. Vacuum the screen carefully without removing it. If further cleaning is
required continue with Step 4, otherwise skip to Step 7.
4. Remove the chamber cover/screen assembly by pulling it straight out.
FIgURE 1. CO-LOCATED INNOvAIR FLEx DUCT SMOKE DETECTOR:
SENSOR UNIT
TEST MAGNET
POSITION
LED STATUS INDICATORS
POWER BOARD UNIT
H0614-00
5. Use a vacuum cleaner or compressed air to remove dust and debris
from the sensing chamber.
6. Reinstall the chamber cover/screen assembly by sliding the edge over
the sensing chamber. Turn until it is firmly in place.
7. Replace the cover using the LEDs to align the cover and then gently
pushing it until it locks into place.
8. Reinstall the detector.
REINSTALLATION
1. Reinstall the detector in its housing.
2. Restore system power.
3. Perform Detector Check.
4. Notify the proper authorities testing has been completed and the smoke
detector system is back in operation.
FIgURE 2:
SENSOR
COVER
SENSING
CHAMBER
COVER AND
SCREEN
SENSOR
CHAMBER
COVER
REMOVAL
TABS
C1009-00
SS-300-017
2
I56-3328-000
©2008 System Sensor
System Sensor warrants its enclosed smoke detector to be free from defects in materials
and workmanship under normal use and service for a period of three years from date
of manufacture. System Sensor makes no other express warranty for this smoke detec-
tor. No agent, representative, dealer, or employee of the Company has the authority to
increase or alter the obligations or limitations of this Warranty. The Company’s obligation
of this Warranty shall be limited to the repair or replacement of any part of the smoke
detector which is found to be defective in materials or workmanship under normal use
and service during the three year period commencing with the date of manufacture.
After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return
Authorization number, send defective units postage prepaid to: System Sensor, Repair
THREE-YEAR LIMITED WARRANTY
Department, RA #__________, 6581 Kitimat Road, Unit 6, Mississauga, Ontario L5N-3T5.
Please include a note describing the malfunction and suspected cause of failure. The
Company shall not be obligated to repair or replace units which are found to be defective
because of damage, unreasonable use, modifications, or alterations occurring after the
date of manufacture. In no case shall the Company be liable for any consequential or inci-
dental damages for breach of this or any other Warranty, expressed or implied whatsoever,
even if the loss or damage is caused by the Company’s negligence or fault. Some states do
not allow the exclusion or limitation of incidental or consequential damages, so the above
limitation or exclusion may not apply to you. This Warranty gives you specific legal rights,
and you may also have other rights which vary from state to state.
Please refer to insert for the Limitations of Fire Alarm Systems