INSTALLATION AND MAINTENANCE INSTRUCTIONS

FOR MODEL 2300TB

Before installing detectors, please thoroughly read System Sensor Manual I56-407-XX, 

Guide for Proper Use of System Smoke 

Detectors,

 which provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies 

of this manual are available at no charge from System Sensor.

GENERAL DESCRIPTION:

Model 2300TB is a 2-wire combination smoke/heat detector. In addition to photoelectronic smoke detection, two supervised 
electronic thermistors provide restorable 135°F fixed temperature heat detection. The installation is simplified by the use of an 
adaptor bracket and a plug-in screw terminal block which can be pre-wired to the system allowing the detector to be easily 
installed or removed for cleaning. It is designed to provide open area protection, and to be used with UL listed compatible 2-
wire control panels. The detector’s sensitivity can be tested in place using the MOD400R field sensitivity test module.
The 2300TB is listed to UL 268 and is a latching type system detector. When latched in alarm, the detector must be reset by 
a momentary power interruption.
An LED on the detector provides a local indication of the detector’s status. If power is applied to the detector, and the detector 
is functioning properly in standby, the status LED will blink every 10 seconds. The detector performs a self-test on its smoke 
sensing chamber and internal electronics every 40 seconds. If this test fails, the detector stops blinking the status LED in 
standby, and the LED will remain off. In alarm, the LED will be latched on continuously until the detector is reset.
The detector provides an output for connection to an optional Remote Annunciator (model RA400Z). The Remote Annunciator 
mounts to a single gang box and provides an LED indication of an alarm condition.

SPECIFICATIONS:

Diameter:                                                 5.5 inches      (14 cm)
Height:                                                     2.5 inches      (64 mm)
Weight:                                                    0.7 lb              (310 gm)
Operating Temperature Range:              0° to +38° C  (32° to 100° F)
Operating Humidity Range:                    10% to 90% Relative Humidity Non-condensing
Latching Alarm:                                       Reset by momentary power interruption.
Test Feature:                                           Recessed test switch.
Maximum Air Velocity:                            3000 Ft./Min. (15 Meters/Sec.).
Sensitivity:                                               Nominal 3%/Ft.
Heat Sensor:                                           135°F Fixed Temperature Electronic Thermistor

ELECTRICAL RATINGS:

System Voltage  nominal:              12 or 24 VDC
                            minimum:            8.5 VDC
                            maximum:           35 VDC
Maximum Ripple Voltage:              30% of nom. Voltage (peak to peak)
Start-up Capacitance:                    0.02 

µ

F maximum

Standby Current:                            120 

µ

A maximum

Alarm Ratings:                                4.2 VDC minimum at 10 mA.
                                                        6.6 VDC maximum at 100 mA.
              Alarm current must be limited to 100 mA maximum by the
              control panel. If used, the RA400Z Remote Annunciator
              operates within the specified detector alarm currents.
Reset Voltage:                                2.5 VDC minimum
Reset Time:                                    .3 Sec. maximum
Start-up Time:                                 34 Sec. maximum
                                                        (After 60 Sec. Reset)

D300-01-00                                                                                                                                                             I56-490-05
                               System Sensor, 3825 Ohio Avenue, St. Charles, Illinois 60174, 1-800-SENSOR2, FAX 708-377-6495

S0181-00

Figure 1. 2300TB Smoke/Heat Detector

Содержание 2300TB

Страница 1: ...rms a self test on its smoke sensing chamber and internal electronics every 40 seconds If this test fails the detector stops blinking the status LED in standby and the LED will remain off In alarm the LED will be latched on continuously until the detector is reset The detector provides an output for connection to an optional Remote Annunciator model RA400Z The Remote Annunciator mounts to a single...

Страница 2: ...ll wiring should be installed in sepa rate grounded conduit do not mix fire system wiring in the same conduit as any other electrical wiring Twisted pair may be used to provide additional protection against extraneous electrical interference Wire connections are made by stripping about 1 4 inch of insulation from the end of the feed wire inserting the wire into the appropriate terminal and tighten...

Страница 3: ...fore testing the detector look for the presence of the flashing LED If it does not flash power has been lost to the detector check the wiring or the unit is defective return for repair A TEST SWITCH 1 A recessed test switch is located on the detector housing See Figure 4 2 Push and hold the recessed test switch with a 0 1 inch maximum diameter tool such as an allen wrench or small screw driver 3 T...

Страница 4: ...oke detector is usually located For this reason there may be large delays in detecting a smoldering fire with either an ionization type detector or a photoelectric type detector Either one of them may alarm only after flaming has initiated which will generate the heat needed to drive the smoke to the ceiling Smoke from fires in chimneys in walls on roofs or on the other side of a closed door s may...

Отзывы: