System Sensor 2251BR Скачать руководство пользователя страница 2

 

 Two LEDs on the sensor are controlled by the panel to indicate sensor 
status. Coded signals, transmitted from the panel, can cause the LEDs 
to blink, latch on, or latch off. Refer to the control panel technical docu-
mentation for sensor LED status operation and expected delay to alarm.

B.  Smoke Entry

 

 The GEMINI model 501 aerosol generator can be used for smoke entry 
testing. Set the generator to represent 4%/ft to 5%/ft obscuration as de-
scribed in the GEMINI 501 manual. Using the bowl shaped applicator, 
apply aerosol until the panel alarms. 

 

 Additionally, canned aerosol simulated smoke (canned smoke agent) 
may be used for smoke entry testing of the smoke detector. Tested and 
approved aerosol smoke products are:

MANUFACTURER

MODEL

Home Safeguard Industries

25S, 30S

SDi

CHEK02 and CHEK06

SDi

SOLOA4

SDi

SMOKESABRE-01

When used properly, the canned smoke agent will cause the smoke detector 
to go into alarm. Refer to the manufacturer’s published instructions for proper 
use of the canned smoke agent.

CAUTION

Canned aerosol simulated smoke (canned smoke agent) formulas will vary by 
manufacturer. Misuse or overuse of these products may have long term ad-
verse effects on the smoke detector. Consult the canned smoke agent manufac-
turer’s published instructions for any further warnings or caution statements.

C. 

 Remote  Test

 

 2251BR can be remotely tested using the RTS451, RTS451KEY, RTS151, or 
RTS151KEY test accessories. Refer to the DNR/DNRW manual for wiring 
diagrams. Maximum test response time may be up to two communica-
tions from the panel.

A sensor that fails any of these tests should be cleaned as described under 
CLEANING, and retested. If the sensor fails after cleaning, it must be replaced.

When testing is complete, restore the system to normal operation and notify 
the proper authorities that the system is back in operation.

FIGURE 3. TEST MAGNET POSITION:

LED

TEST MAGNET 

POSITION

MAGNET TEST

MARKER

LED

C0145-02

CLEANING

Before removing the detector, notify the proper authorities that the smoke 
detector system is undergoing maintenance and will be temporarily out of 
service. Disable the zone or system undergoing maintenance to prevent un-
wanted alarms.

1.  Remove the sensor to be cleaned from the system.
2.   Remove the sensor cover by pressing firmly on each of the four removal 

tabs that hold the cover in place.

3.   Vacuum the screen carefully without removing it. If further cleaning is 

required continue with Step 4, otherwise skip to Step 7.

4.   Remove the chamber cover/screen assembly by pulling it straight out.
5.   Use a vacuum cleaner or compressed air to remove dust and debris from 

the sensing chamber.

6.   Reinstall the chamber cover/screen assembly by sliding the edge over the 

sensing chamber. Turn until it is firmly in place.

7.   Replace the cover using the LEDs to align the cover and then gently 

pushing it until it locks into place.

8.  Reinstall the detector.
9.  Test the detector as described in TESTING.
10.  Reconnect disabled circuits.
11.  Notify the proper authorities that the system is back on line.

FIGURE 4. SENSOR ASSEMBLY:

SENSOR

COVER

SENSING

CHAMBER

COVER AND

SCREEN

COVER

REMOVAL

TABS

SENSING

CHAMBER

C0215-03

SPECIAL NOTE REGARDING SMOKE DETECTOR GUARDS

Smoke detectors are not to be used with detector guards unless the combina-
tion has been evaluated and found suitable for that purpose.

System Sensor warrants its enclosed smoke detector to be free from defects in materials and workman-
ship under normal use and service for a period of three years from date of manufacture. System Sensor 
makes no other express warranty for this smoke detector. No agent, representative, dealer, or employee 
of the Company has the authority to increase or alter the obligations or limitations of this Warranty. 
The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of 
the smoke detector which is found to be defective in materials or workmanship under normal use and 
service during the three year period commencing with the date of manufacture. After phoning System 
Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective 
units postage prepaid to: Honeywell, 12220 Rojas Drive, Suite 700, El Paso TX 79936 USA. Please include 

FCC STATEMENT

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference 
received, including interference that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable  protection against 
harmful interference in a residential installation.  This equipment generates,  uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful 
interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause Harmful interference to radio or television reception, 
which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
 

 

– Reorient or relocate the receiving antenna.

 

 

– Increase the separation between the equipment and receiver.

 

 

– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

 

 

– Consult the dealer or an experienced radio/TV technician for help.

THREE-YEAR LIMITED WARRANTY

a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to 
repair or replace units which are found to be defective because of damage, unreasonable use, modifica-
tions, or alterations occurring after the date of manufacture. In no case shall the Company be liable for 
any consequential or incidental damages for breach of this or any other Warranty, expressed or implied 
whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do 
not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or 
exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have 
other rights which vary from state to state.

Please refer to insert for the Limitations of Fire Alarm Systems

  

I56-3534-005R 

 

 

©2016 System Sensor. 04-19

Отзывы: