D100-101-00
2
I56-2806-003R
Testing
Before testing, notify the proper authorities that the smoke
detector system is undergoing maintenance and will tempo-
rarily be out of service. Disable the zone or system under-
going maintenance to prevent unwanted alarms. Detectors
must be tested after installation and as part of periodic
maintenance. Test 2151 and 2151T as follows:
NOTE:
Before testing the detector, check to ensure the
LEDs blink. If they do not, the detector has lost power
(check the wiring), it is defective (return it for repair), or
the detector sensitivity is outside the listed limits.
A. Test Magnet (p/n M02-04-01 or M02-09-00)
1. Place the magnet against the cover in the location
designated by the raised mark to activate the test fea-
ture (see Figure 1).
2. The LEDs should latch ON within 5 seconds indicat-
ing alarm and annunciating the panel.
LED Status
Indicators
Magnet Test
Marker
Test Magnet
Position
Test Magnet
Position
Magnet Test
Marker
SENS-RDR
Location
Figure 1. Bottom and side views showing position of test magnet:
B. Test Module (SENS-RDR)
Use the SENS-RDR Sensitivity Reader to measure the
sensitivity of the detectors. Please refer to the SENS-
RDR instruction manual for operating details.
C. Aerosol Generator (Gemini 501)
Set the generator to represent 4% to 5%/ft. obscuration
as described in the Gemini 501 Manual. Using the bowl-
shaped applicator, apply aerosol until unit alarms.
D. Direct Heat Method (Hair Dryer of 1000-1500 watts)
2151T only
A hair dryer of 1000-1500 watts should be used to test
the thermistors. Direct the heat toward either of the two
thermistors, holding the heat source approximately 12
inches from the detector in order to avoid damaging the
plastic housing. The detector will reset only after it has
had sufficient time to cool. Make sure both thermistors
are tested individually.
Notify the proper authorities that the system is back on line.
Detectors that fail these tests should be cleaned as described
under MAINTENANCE and retested. If the detectors still
fail these tests, they should be returned for repair.
C0145-01
CAUTION
Dust covers are an effective way to limit the entry of dust
into smoke detector sensing chambers. However, they may
not completely prevent airborne dust particles from enter-
ing the detector. Therefore, System Sensor recommends the
removal of detectors before beginning construction or other
dust producing activity.
Be sure to remove the dust covers from any sensors that
were left in place during construction as part of returning
the system to service.
CAUTION
Smoke detectors are not to be used with detector guards
unless the combination has been evaluated and found
suitable for that purpose.