B401 Plug-In Detector Base

INSTALLATION AND MAINTENANCE INSTRUCTIONS

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

Before Installing 

Please thoroughly read the 

System Smoke Detectors 

Application Guide

, which provides detailed information 

on detector spacing, placement, zoning, wiring, and spe-
cial applications. Copies of this manual are available from 
System Sensor.

NOTICE: 

This manual should be left with the owner/user 

of this equipment.

IMPORTANT:

 The detector used with this base must be 

tested and maintained regularly following NFPA 72 require-
ments. The detector used with this base should be cleaned 
at least once a year.

Specifications

Base Diameter: 

10.2 cm (4.0 inches)

Base Height: 

2.0 cm (0.8 inches)

Weight: 

152 g (0.34 lb.)

Mounting: 

50 mm box

 

60 mm box

Operating Temperature Range: 

–10° to +60°C (14° to 140°F) — European Installation

 

0° to 49°C (32° to 120°F) — US/Australian Installation

Operating Humidity Range: 

10% to 93% Relative Humidity

Electrical Ratings — includes base and detector
 

Base And Smoke Detector 

Base And Heat Detector

System Voltage: 

12/24 VDC 

24 VDC

Maximum Ripple Voltage: 

4 Volts peak to peak 

4 Volts peak to peak

Start-up Capacitance: 

0.02 µF Maximum 

0.02 µF Maximum

Standby Ratings:* 

8.5 VDC Minimum 

15 VDC Minimum

 

35 VDC Maximum 

35 VDC Maximum

 

120 µA Maximum 

100 µA Maximum

Alarm Ratings: 

4.2 VDC Minimum at 10 mA** 

4.2 VDC Minimum at 10 mA**

 

6.6 VDC Maximum at 100 mA** 

6.6 VDC Maximum at 100 mA**

Reset Voltage: 

2.5 VDC Minimum 

2.5 VDC Minimum

Reset Time: 

0.3 Seconds Maximum 

0.3 Seconds Maximum

Start-up Time: 

34 Seconds Maximum 

34 Seconds Maximum

*  1151E: 30 µA Maximum. 
** Alarm current MUST be limited to 100 mA maximum (130 mA for models 1151 and 2151) by the control panel. 
  If used, the RA400Z Remote Annunciator operates within the specified detector alarm currents.

General Description

This B401 plug-in detector base is used with System Sensor 
smoke and heat detector heads. The capability of plugging 
these detectors into a variety of special bases makes them 
more versatile than equivalent direct-wired models. Refer 
to the System Sensor catalog for other available plug-in 
detector bases.

The B401 base is intended for use in 2-wire systems, with 
screw terminals provided for power and remote annuncia-
tor connections.

For use with the following detectors:
US Models: 

1151, 1451, 2151, 2451, 2451TH, 5451

European Models: 

1151E, 1451E, 2151E, 2451E, 5451E

Australian Models: 

1151AUS, 1451AUS, 2151AUS, 2451AUS, 4451AUS

 

5451AUS, 51A51, 51B51, 51C51, 51D51

I56-0338-010R

  

I56-0338-010R 

 

 03-11

Содержание 1451

Страница 1: ...eak to peak Start up Capacitance 0 02 µF Maximum 0 02 µF Maximum Standby Ratings 8 5 VDC Minimum 15 VDC Minimum 35 VDC Maximum 35 VDC Maximum 120 µA Maximum 100 µA Maximum Alarm Ratings 4 2 VDC Minimum at 10 mA 4 2 VDC Minimum at 10 mA 6 6 VDC Maximum at 100 mA 6 6 VDC Maximum at 100 mA Reset Voltage 2 5 VDC Minimum 2 5 VDC Minimum Reset Time 0 3 Seconds Maximum 0 3 Seconds Maximum Start up Time 3...

Страница 2: ... system control panels have specifications for allowable loop resistance Consult the control panel manufacturer s specifications for the total loop resistance allowed for the control panel being used before wiring the detector loops Wiring Instructions CAUTION Do not loop wire under terminals Break wire run to ensure supervision of connections Wire connections are made by stripping about 3 8 of in...

Страница 3: ...ion C0529 00 2 3 4 1 REMOTE ANNUNCIATOR 2 3 4 1 REMOTE ANNUNCIATOR 2 WIRE CONTROL PANEL E O L CLASS A OPTIONAL WIRING tant tab before installing the detector see Figure 3A The tamper resistant tab is on the detector mounting base To remove a tamper resistant detector from the base use a pocket screwdriver or similar tool to depress the tamper resistant tab and turn the detector counterclockwise Th...

Страница 4: ...end defective units postage prepaid to Please refer to insert for the Limitations of Fire Alarm Systems Three Year Limited Warranty Honeywell 12220 Rojas Drive Suite 700 El Paso TX 79936 USA Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to repair or replace units which are found to be defective because of damage unreasonable use ...

Отзывы: