System  Sensor  warrants  its  enclosed  smoke  detector  to  be  free  from 
defects in materials and workmanship under normal use and service for a 
period of three years from date of manufacture. System Sensor makes no 
other express warranty for this smoke detector. No agent, representative, 
dealer, or employee of the Company has the authority to increase or alter 
the  obligations  or  limitations  of  this  Warranty.  The  Company’s  obliga-
tion of this Warranty shall be limited to the repair or replacement of any 
part of the smoke detector which is found to be defective in materials or 
workmanship under normal use and service during the three year period 
commencing with the date of manufacture. After phoning System Sensor’s 
toll  free  number  800-SENSOR2  (736-7672)  for  a  Return  Authorization 
number,  send  defective  units  postage  prepaid  to:  System  Sensor,  Repair 

Figure 5. Removal of cover and screen for cleaning:

LOCK PRONG

REMOVABLE SCREEN

(P/N RS14)

REMOVABLE 

COVER

FOR

CLEANING 

SENSING CHAMBER

Maintenance

NOTE:

  Before  starting,  notify  the  proper  authorities  that 

the  smoke  detector  system  is  undergoing  main-
tenance,  and  therefore  will  temporarily  be  out  of 
service.  Disable  the  zone  or  system  undergoing 
maintenance to prevent unwanted alarms. 

The 1412 and 1424 are cleaned as follows:

1. Remove  the  detector  screen  and  cover  assembly  by 

depressing the three lock prongs on the top of the cover, 
rotate  the  cover  counterclockwise,  and  pull  the  screen 
and cover assembly away from the detector (see Figure 
5). Usage of System Sensor CRT400 cover removal tool 
is recommended.

2. Remove the screen from the cover.
3. Use a vacuum cleaner to remove dust from the screen, 

the cover, and the sensing chamber.

4. After cleaning, snap the screen into the cover, then place 

the cover and screen assembly on the detector, turning 
clockwise until it is locked in place.

5. Test detector as described under TESTING.
6. Notify the proper authorities that the system is back on 

line.

S0138-00

Please refer to insert for the Limitations of Fire Alarm Systems

Three-Year Limited Warranty

Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. 
Please  include  a  note  describing  the  malfunction  and  suspected  cause 
of failure. The Company shall not be obligated to repair or replace units 
which  are  found  to  be  defective  because  of  damage,  unreasonable  use, 
modifications,  or  alterations  occurring  after  the  date  of  manufacture.  In 
no case shall the Company be liable for any consequential or incidental 
damages for breach of this or any other Warranty, expressed or implied 
whatsoever, even if the loss or damage is caused by the Company’s neg-
ligence or fault. Some states do not allow the exclusion or limitation of 
incidental or consequential damages, so the above limitation or exclusion 
may not apply to you. This Warranty gives you specific legal rights, and 
you may also have other rights which vary from state to state.

Содержание 1424

Страница 1: ...condensing Locking Alarm Reset by momentary power interruption Relay Contact Ratings Resistive or Inductive 60 power factor load Form A 2 0A 30VAC DC Form C 0 6A 110VDC 2 0A 30VDC 1 0A 125VAC 2 0A 30VAC For Canadian installations relay contact rating is 2 0A 30VAC DC Electrical Ratings 1412 1424 System Voltage 12 24 DC 4V Maximum Ripple Supply Voltages 11 3 20 VDC Minimum 17 3 29 VDC Maximum Reset...

Страница 2: ...nd by mode and will transfer in alarm condition CAUTION For system supervision for terminals 1 2 7 and 8 do not use looped wire under terminals Break wire run to provide system supervision of connections For signal wiring the wiring between interconnected detectors it is recommended that the wire be no smaller than 18 gauge Wire sizes up to 12 gauge wire may be used For best system performance the...

Страница 3: ...ce CAUTION Smoke detectors are not to be used with detector guards unless the combination has been evaluated and found suitable for that purpose Testing NOTE Before testing notify the proper authorities that the smoke detector system is undergoing main tenance and therefore will temporarily be out of service Disable the zone or system undergoing maintenance to prevent unwanted alarms Before testin...

Страница 4: ...mbly by depressing the three lock prongs on the top of the cover rotate the cover counterclockwise and pull the screen and cover assembly away from the detector see Figure 5 Usage of System Sensor CRT400 cover removal tool is recommended 2 Remove the screen from the cover 3 Use a vacuum cleaner to remove dust from the screen the cover and the sensing chamber 4 After cleaning snap the screen into t...

Отзывы: