Figure 5. Removal of cover and screen for cleaning:

LOCK PRONG

REMOVABLE

SCREEN

REMOVABLE

COVER FOR

CLEANING

LOCKING

PRONGS

removal tool is recommended. 

2. Remove the screen from the cover.

3. Use a vacuum cleaner to remove dust from the screen, 

the cover, and the sensing chamber. 

4.  After  cleaning,  snap  the  screen  into  the  cover,  then 

place  the  cover  and  screen  assembly  on  the  detector 

turning clockwise until it is locked in place.

5. Test the detector as described in TESTING.

6. Notify the proper authorities that the system is back on 

line.

A78-554-04

Three-Year Limited Warranty

System Sensor warrants its enclosed smoke detector to be free from defects in ma-
terials and workmanship under normal use and service for a period of three years 
from date of manufacture. System Sensor makes no other express warranty for this 
smoke detector. No agent, representative, dealer, or employee of the Company has 
the authority to increase or alter the obligations or limitations of this Warranty. The 
Company’s obligation of this Warranty shall be limited to the repair or replacement 
of any part of the smoke detector which is found to be defective in materials or work-
manship under normal use and service during the three year period  commencing 
with the date of manufacture. After phoning System Sensor’s toll free number -800-
SENSOR2 (736-7672) for a Return Authorization number, send defective units post-
age prepaid to: System Sensor, Repair  Department, RA #__________, 658 Kitimat 
Rd., Unit #6, Mississauga, Ontario, L5N 3T5. Please include a note describing the 

malfunction and suspected cause of failure. The Company shall not be obligated to 
repair or replace units which are found to be defective because of damage, unrea-

sonable use, modifications, or alterations occurring after the date of manufacture. In 
no case shall the Company be liable for any consequential or incidental damages 

for breach of this or any other Warranty, expressed or implied whatsoever, even if 
the loss or damage is caused by the Company’s negligence or fault. Some states do 

not allow the exclusion or limitation of incidental or consequential damages, so the 
above limitation or exclusion may not apply to you. This Warranty gives you specific 

legal rights, and you may also have other rights under common law.

Please refer to insert for the Limitations of Fire Alarm Systems

Содержание 1400A Direct Wire

Страница 1: ... up Capacitance 20 pf Maximum Standby Ratings 8 5 VDC Minimum 35 VDC Maximum 100 uA Maximum Alarm Ratings 4 2 VDC Minimum at 10 mA 6 6 VDC Minimum at 100 mA Alarm current must be limited to 100 mA maximum by the control panel If used the RA400ZA Remote Annunciator operates within the specified detector alarm cur rents Reset Voltage 2 5 VDC Minimum Reset Time 0 3 S Maximum Start up Time 35 S Maximu...

Страница 2: ...erminal to ensure that the connections are supervised Do NOT loop the wire under the terminals Tamper resistant Feature This detector includes a tamper resistant feature that ef fectively prevents removal of the detector without the use of a tool To make the detector tamper resistant break off the smaller tab at the scribed line on the tamper resistant tab on the detector mounting bracket see Figu...

Страница 3: ...ese tests should be cleaned as de scribed under MAINTENANCE and retested If the detec tors still fail these tests they should be returned for repair Maintenance NOTE Before starting notify the proper authorities that the smoke detector system is undergoing main tenance and therefore will be temporarily out of service Disable the zone or system undergoing maintenance to prevent unwanted alarms The ...

Страница 4: ...d to the repair or replacement of any part of the smoke detector which is found to be defective in materials or work manship under normal use and service during the three year period commencing with the date of manufacture After phoning System Sensor s toll free number 1 800 SENSOR2 736 7672 for a Return Authorization number send defective units post age prepaid to System Sensor Repair Department ...