1400A Direct Wire
Ionization Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS
Before Installing
Please thoroughly read the System Sensor manual I56-
407-XX,
Guide for Proper Use of System Smoke Detec-
tors
. This manual provides detailed information on detector
spacing, placement, zoning, wiring, and special appli-
cations. Copies of this manual are available at no charge
from System Sensor. Please also refer to CAN/ULC-S524,
Standard for the Installation of Fire Alarm Systems
and
CEC Part , Sec. 32..
General Description
System Sensor 400A dual-chamber ionization smoke de-
tectors utilize state-of-the-art, unipolar sensing chambers.
These detectors are designed to provide open area pro-
tection, and to be used with compatible ULC-listed, 2-wire
control panels only. The detector’s operation and sensitiv-
ity can be tested in place.
Specifications
Diameter:
5.5 inches (40 mm)
Height:
3.2 inches (80 mm)
Weight:
0.7 lb. (30 g)
Operating Temperature:
0
o
to +49
o
C (32
o
F to 20
o
F)
Latching Alarm:
Reset by momentary power interruption.
Operating Humidity:
0% to 93% Relative Humidity, Noncondensing
Electrical Ratings:
System Voltage:
2/24 VDC
Maximum Ripple Voltage:
4 Volts peak to peak
Start-up Capacitance:
20 pf Maximum
Standby Ratings:
8.5 VDC Minimum
35 VDC Maximum
00 uA Maximum
Alarm Ratings:
4.2 VDC Minimum at 0 mA
6.6 VDC Minimum at 00 mA
Alarm current must be limited to 00 mA maximum by the control panel. If used,
the RA400ZA Remote Annunciator operates within the specified detector alarm cur
-
rents.
Reset Voltage:
2.5 VDC Minimum
Reset Time:
0.3 S Maximum
Start-up Time:
35 S Maximum
Each detector includes an LED that provides a local visual
indication of the detector’s status. The LED blinks every
ten seconds as an indication that power is applied to the
detector and lights continuously in alarm. These detectors
also have the latching alarm feature. The alarm can be re-
set only by a momentary power interruption.
The detector also has provision for the connection of
an optional Model RA400ZA Remote Annunciator. The
RA400ZA provides a visual indication of an alarm and
mounts to a single gang box.
Spacing
CAN\ULC-S524 defines the spacing requirements for
smoke detectors. Typically, this is 30 feet when the detec-
tors are installed on a smooth ceiling. However, ALL instal-
lations must comply with CAN/ULC-S524 and/or special
requirements of the authority having jurisdiction.
Mounting
Each 400A detector is supplied with a mounting bracket
kit that permits the detector to be mounted: