System Sensor 1400A Direct Wire Скачать руководство пользователя страница 1

D400-07-00                REV#-002 

 

I56-006-002

1400A Direct Wire 
Ionization Smoke Detector

INSTALLATION AND MAINTENANCE INSTRUCTIONS

Before Installing 

Please  thoroughly  read  the  System  Sensor  manual  I56-

407-XX, 

Guide  for  Proper  Use  of  System  Smoke  Detec-

tors

. This manual provides detailed information on detector 

spacing,  placement,  zoning,  wiring,  and  special  appli-

cations. Copies of this manual are available at no charge 

from System Sensor. Please also refer to CAN/ULC-S524, 

Standard  for  the  Installation  of  Fire  Alarm  Systems

  and 

CEC Part , Sec. 32..

General Description

System Sensor 400A dual-chamber ionization smoke de-

tectors utilize state-of-the-art, unipolar sensing chambers. 

These detectors are designed to provide open area pro-

tection, and to be used with compatible ULC-listed, 2-wire 

control panels only. The detector’s operation and sensitiv-

ity can be tested in place.

Specifications

Diameter: 

5.5 inches (40 mm)

Height: 

3.2 inches (80 mm)

Weight: 

0.7 lb. (30 g)

Operating Temperature: 

0

o

 to +49

o

C (32

o

F to 20

o

F)

Latching Alarm: 

Reset by momentary power interruption.

Operating Humidity: 

0% to 93% Relative Humidity, Noncondensing

Electrical Ratings:

System Voltage: 

2/24 VDC

Maximum Ripple Voltage: 

4 Volts peak to peak

Start-up Capacitance: 

20 pf Maximum

Standby Ratings: 

8.5 VDC Minimum

 

35 VDC Maximum

 

00 uA Maximum

Alarm Ratings: 

4.2 VDC Minimum at 0 mA

 

6.6 VDC Minimum at 00 mA

 

Alarm  current  must  be  limited  to  00  mA  maximum  by  the  control  panel.  If  used, 

the RA400ZA Remote Annunciator operates within the specified detector alarm cur

-

rents.

Reset Voltage: 

2.5 VDC Minimum

Reset Time: 

0.3 S Maximum

Start-up Time: 

35 S Maximum

Each detector includes an LED that provides a local visual 

indication  of  the  detector’s  status. The  LED  blinks  every 

ten seconds as an indication that power is applied to the 

detector and lights continuously in alarm. These detectors 

also have the latching alarm feature. The alarm can be re-

set only by a momentary power interruption.

The  detector  also  has  provision  for  the  connection  of 

an  optional  Model  RA400ZA  Remote  Annunciator.  The 

RA400ZA  provides  a  visual  indication  of  an  alarm  and 

mounts to a single gang box.

Spacing

CAN\ULC-S524  defines  the  spacing  requirements  for 

smoke detectors. Typically, this is 30 feet when the detec-

tors are installed on a smooth ceiling. However, ALL instal-

lations  must  comply  with  CAN/ULC-S524  and/or  special 

requirements of the authority having jurisdiction.

Mounting

Each 400A detector is supplied with a mounting bracket 

kit that permits the detector to be mounted:

658  Kitimat Rd., Unit #6, Mississauga, Ontario, L5N 3T5

-800-SENSOR2, FAX: 905-82-077

www.systemsensor.ca

 

 

 

           

Содержание 1400A Direct Wire

Страница 1: ... up Capacitance 20 pf Maximum Standby Ratings 8 5 VDC Minimum 35 VDC Maximum 100 uA Maximum Alarm Ratings 4 2 VDC Minimum at 10 mA 6 6 VDC Minimum at 100 mA Alarm current must be limited to 100 mA maximum by the control panel If used the RA400ZA Remote Annunciator operates within the specified detector alarm cur rents Reset Voltage 2 5 VDC Minimum Reset Time 0 3 S Maximum Start up Time 35 S Maximu...

Страница 2: ...erminal to ensure that the connections are supervised Do NOT loop the wire under the terminals Tamper resistant Feature This detector includes a tamper resistant feature that ef fectively prevents removal of the detector without the use of a tool To make the detector tamper resistant break off the smaller tab at the scribed line on the tamper resistant tab on the detector mounting bracket see Figu...

Страница 3: ...ese tests should be cleaned as de scribed under MAINTENANCE and retested If the detec tors still fail these tests they should be returned for repair Maintenance NOTE Before starting notify the proper authorities that the smoke detector system is undergoing main tenance and therefore will be temporarily out of service Disable the zone or system undergoing maintenance to prevent unwanted alarms The ...

Страница 4: ...d to the repair or replacement of any part of the smoke detector which is found to be defective in materials or work manship under normal use and service during the three year period commencing with the date of manufacture After phoning System Sensor s toll free number 1 800 SENSOR2 736 7672 for a Return Authorization number send defective units post age prepaid to System Sensor Repair Department ...

Отзывы: