Physical Layer Interface Settings
27
GND
GND
TXA TXB RXA RXB
RS-422/485
MASTER
TXA TXB RXA RXB
RS-485
TXA TXB RXA RXB
RS-485
GND
GND
SLAVE
SLAVE
Figure 3-3. Four-wire RS-422/485 System
In most configurations, the device that is designated as the master will be an RS-422 device
to constantly drive the transmit lines.
Both pairs of lines of the multi-drop wire must be terminated at each end of the bus with a
resistance equal to the wire's characteristic impedance, generally 120 ohms. If the RX data
pins are not terminated at all and have nothing attached, they may be susceptible to cross
talk. Data on other lines on this port or other nearby ports may get coupled back onto the
unterminated receive lines. If you need to leave the RX lines unattached, you may need to
attach a simple 100 or 120 ohm termination resistor between the lines to avoid this.
Using the RCS Port Server in RS-422 or RS-485 Mode
Any serial port on the RCS/5000 or RCS/6000 can be configured for either RS-422 or RS-485
communication. Thus, the RCS can function as any of the devices in any of the
configurations described above. The RCS can be connected to either an RS-422 or an RS-485
device in a point-to-point connection. Or an RCS can be connected to a two-wire or four-
wire bus, as either a master or a slave, and can communicate in either RS-422 or RS-485
mode. Typically, a single RCS port server is connected to the bus and functions as the
master, but this is determined by the application.
Содержание RCS/5000
Страница 1: ...RCS 5000 and RCS 6000 Hardware Manual Document number 80 001048 1 Revision B...
Страница 2: ......
Страница 3: ...RCS 5000 and RCS 6000 Hardware Manual...
Страница 6: ......
Страница 8: ......
Страница 12: ......
Страница 29: ......
Страница 36: ......
Страница 41: ...Appendix Specifications 35 HEX code Error Category 9D HUB test error...