How to Shorten the Power Cord
6
Rack Power Distribution Unit
Test the plug for
Use a multimeter and the following graphics to verify continuity
between the test points .
Continuity is achieved with a measurement of less than or equal to 1 Ohm.
Use the probes of the multimeter to verify continuity between the
following points on the plug prongs and the slots on the outlets:
• Ground (
J
) on the plug and Ground (
J
) on the outlet
• Neutral (
Q
) on the plug and Neutral (
Q
) on the outlet
• X (
[
) on the plug and X (
[
) on the outlet
• Y (
\
) on the plug and Y (
\
) on the outlet
Verify that there is no continuity among any of the four prongs on the
plug.
View of the plug face:
View of the outlets:
Note
verify that all circuit breakers are in the ON position.
J
Ground terminal
\
Y terminal
Q
Neutral terminal (Silver)
[
X terminal
J
Ground connection
Q
Neutral connection
[
X connection
\
Y connection
J
[
Q
\
ON
ON
ON
ON
J
Q
\
[
RA5204-L520-30A-L143
RA5204-L530-30A-L143