The UPS will not turn on

 

The unit is not connected 
to an AC outlet. 

The unit must be connected to a 
220-240V 50/60Hz outlet. 

The battery is worn out. 

Contact Technical Support. 

Mechanical problem. 

Outlets do not provide 
power to equipment 

Circuit breaker is tripped 
due to overload 

Turn the UPS off and unplug at 
least one piece connected 
equipment. Unplug the power cord 
of the UPS then press the circuit 
breaker knob. 

Batteries are discharged 

Allow the unit to recharge for at 
least 4 hours. 

Unit has been damaged 
by a surge or spike. 

Contact Technical Support. 

  Alarm

 

Alarm code A06 

Battery low: Battery capacity  

 is low, UPS will turn off soon 

Shut off non-essential equipment. 
Save your data and turn off computer. 

Alarm code A14 

Over load occurs. 

Shut off non-essential equipment. 

   Fault

 

Fault code F09 

Output Short : 
Output circuit short. 

1. Shut down the UPS 
2. Your attached equipment may 
have problems, please remove 
them and check again. 

Fault code F11 

Battery high: 
Battery voltage is too high. 

1. Shut down the UPS 
2.Check the counts of Battery 

Fault code F12 

Battery Low : 
Battery voltage is too low. 

1. Shut down the UPS 
2. Check the counts of Battery 
3.Check battery connector when 
use battery packages. 

Fault code F19 

Over Temperature : 
High ambient temperature 
 

1. Shut down the UPS. Restart the 
UPS to Check the fan for operation 
and if the ventilation hole has been 
covered 
2. Contact Technical Support. 

Fault code F14 

Overload in line Mode: 
Your equipment requires 
more power than the UPS 
can provide.  
It will shutdown.  

Shut off non-essential equipment. 
If this solves the overload 
problem, the UPS will transfer to 
normal operation. 

Fault code F18 

Fan fail : 
Fan has been damaged. 

1.Shut down the UPS 
2.Replace the fan 

   Other

 

Software is inactive 

The serial is not 
connected. 

Connect the serial cable to the 
UPS unit and an open serial port 
on the back of the computer. You 
must use the cable that came with 
the unit. 

The unit is not providing 
battery power. 

Shutdown your computer and turn 
the UPS off. Wait 10 seconds and 
turn the UPS back on. This should 
reset the unit. 

 

If any abnormal situations occur that are not listed above, please contact service personnel. 

 

TECHNICAL SPECIFICATIONS 

 

Model 

CLAIRE II 1000

 

CLAIRE II 1500 

CLAIRE II 2000 

Capacity (VA) 

1000

 

1500

2000

Capacity(Watts) 

700

 

1050

1400

  Input

 

Input Voltage Range 

165 -285Vac

Frequency Range 

40-70 Hz

  Output

 

Output Voltage 

/-10% 

Output Frequency 

50Hz(default ) /60Hz

 

Overload Protection 

On Utility: breaker

On Battery: Internal Current Limiting

 

  Physical

 

Total 
UPS outlets 

(4) AS 

(4) AS +(1) 

Terminal Block

 

Maximum Dimensions 
(WxHxD) (mm) 

140 x 190.6 x 327

 

196 x 342x 412

 

Weight (kg) (without BAT) 

6.94

 

7.98

 

15.1

 

  Battery

 

Voltage 

24Vdc

 

48Vdc

Charger Current 

1A  

  Communication

 

Software 

Windows 10, Windows 8, Windows 7, Windows Server 2012 R2,   

Windows Server 2008 R2, Linux, Mac

 Warning Diagnostics

 

Indicators 

AC Mode, Power On, Battery mode, Fault

 

Audible Alarms 

Low Battery, Overload, Fault

 

  Environmental

 

Operating Temperature 

                                       +32°F to 104°F ( 0°C to 40°C )

 

Operating 
Relative Humidity 

0 to 90% NON-CONDENSING

 

  Management

 

Auto-Charger 

Yes

 

Auto-Restart 

Yes

 

DEFINITIONS FOR ILLUMINATED LCD INDICATORS 

 

LCD Indication 

 
 
 
 
 
 
 
 
 
 
 
 

 

Bat-mode 

 

Line mode 

 

Fault 

 

Sound disable 
(Press the display key 
3s to disable and 
enable the buzzer 
sound) 

 

Bat mode:  
Battery Capacity 
 
Line mode: 
1. Battery charging, 
cycle lighting 
2.  Battery  full  charged
lighting 

Load capacity 

 

Line mode & Bat mode

 

 

  

 

Initial 

AC INPUT

(

 Voltage

)

OUTPUT 

(

Voltage

 

 

ALARM DEFINITIONS  

 

Alarm 

Condition 

Off 

Normal 

Beep 1 time In Every 30 

Seconds 

Utility Failure - The UPS is providing battery power to outlets. 

Beep 1 time In Every 2 

Seconds 

Utility Failure - The UPS is providing battery power.  

The rapid beeps indicate the battery will run out of power shortly. 

Beep 1 time In Every 0.5 

Second 

Overload - Occurs when connected equipment exceeds the rating of 

the unit.  

Turn the UPS off and unplug at least one piece of equipment from the 

UPS. 

 

SOFTWARE DOWNLOAD 

 

Power Master management software provides a user-friendly interface for your power systems. The 

graphic user-interface is intuitive and displays essential power information at a glance. Please follow 

procedure below to install the software. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Installation procedure: 

 

Download Power Master from the website: http://www.powermonitor.software/ 

 

Double-click the file and follow the installation steps. 

 

When your computer restarts, the Power Master software will appear as a blue icon located in the 

system tray. 

 
 
 

 

K01-C000434-01

 

 