Modbus Registers – Configuration
Register
Type
Read/Wite
Description
40105
16bit (Big Endian)
Read/Write
Channel 1 Operating Mode
40106
16bit (Big Endian)
Read/Write
Channel 2 Operating Mode
40107
16bit (Big Endian)
Read/Write
Channel 3 Operating Mode
40108
16bit (Big Endian)
Read/Write
Channel 4 Operating Mode
40109
16bit (Big Endian)
Read/Write
Channel 5 Operating Mode
40110
16bit (Big Endian)
Read/Write
Channel 6 Operating Mode
40111
16bit (Big Endian)
Read/Write
Channel 7 Operating Mode
40112
16bit (Big Endian)
Read/Write
Channel 8 Operating Mode
40113
16bit (Big Endian)
Read Only
Channel 1 PWM Input Fault
40114
16bit (Big Endian)
Read Only
Channel 2 PWM Input Fault
40115
16bit (Big Endian)
Read Only
Channel 3 PWM Input Fault
40116
16bit (Big Endian)
Read Only
Channel 4 PWM Input Fault
40117
16bit (Big Endian)
Read Only
Channel 5 PWM Input Fault
40118
16bit (Big Endian)
Read Only
Channel 6 PWM Input Fault
40119
16bit (Big Endian)
Read Only
Channel 7 PWM Input Fault
40120
16bit (Big Endian)
Read Only
Channel 8 PWM Input Fault
40121
16bit (Big Endian)
Read/Write
Long/Short PWM Average
40122
16bit (Big Endian)
Read/Write
Pulse Count De-Bounce Setting
40123
16bit (Big Endian)
Read/Write
Modbus RTU Baud Rate
40124
16bit (Big Endian)
Read/Write
Configuration Register
40105-40112
Channel Mode
This is a per channel setting with the following options set as the register value as below, If a system
is set such that a PWM/Counter mixed mode is detected the system will not allow counter mode to
be initialised.
Register Value
Channel Setting
0
Static Level
1
Static Level
2
Pulse Counter
3
PWM Measurement
40113-40120 Channel PWM
Input Health
If a PWM channel times out during pulse measurement 3 times in a row the system will mark the
channel as dead and skip it on subsequent channel reads. A system reset (either invoked via
Modbus configuration register) or a power cycle will clear these registers.
This prevents total Modbus lock out in the situation that multiple sensors lose power or are non-
responsive.