Note:

 When installing the DIM10-250-11 into an 

enclosure, consideration of antenna position and 
interference is required to provide the optimum 

wireless signal strength. (Figure 1) 

1.

 

Connect the electrical service 

black

 wire (hot) 

to the 

LINE 

input on the DIM10-250-11. 

2.

 

Connect the 

black

 wire of the LED fixture to 

the 

LOAD

 output on the DIM10-250-11. 

3.

 

Connect the electrical service 

white

 wire 

(neutral) to the 

NEUTRAL

 input on the 

DIM10-250-11 and the 

NEUTRAL

 input on the 

fixture. 

4.

 

Connect the 

white

 wire (neutral) from the 

LED fixture to the electrical service white 

wire/neutral.  

Note:   Steps 5-7 are for Class 1/2 Dimming 
 

Control 

5.

 

Connect the 

DIM-

 wire on the LED fixture to 

the 

DIM-

 input on the DIM10-250-11.  

6.

 

Connect the 

DIM+

 wire on the LED fixture to 

the 

DIM+

 input on the DIM10-250-11.  

7.

 

Switch power on to the fixture. The light 

should turn on.  

Note:

 

When switched on, lamps should turn on to 

full brightness; approximately 10 VDC signal on 

the DIM+ wire using the DIM- wire as reference. 
8.

 

Refer to the SimplySNAP User’s Manual for 

information on provisioning the DIM10-250-

11. 

Note:   Steps 9-12 are for attaching sensors.  See 

Figure 3 for details 

9.

 

Connect the DIM10-250-11 Input A to the first 

sensor output and Input B to the second 
sensor output (if applicable). 

10.

 

Connect the DIM10-250-11 COMMON signal to 
the Common (ground) connection on the 

sensor(s).  

11.

 

Connect the DIM10-250-11 +24VDC output to 

the power input on the sensor(s).  

12.

 

Connect the DIM10-250-11 COMMON input to 

the Common (ground) signal on the sensor(s). 

 

 
 

DIMMING 

Below are some recommendations for successful 
dimming using the DIM10-250-11. The dimming 

control wires are referenced as Dim+ and Dim- .  The 

dimming signals have a Maximum voltage of 10V DC. 

 

Use multi-strand 18 Gauge Wire for noise 

immunity and current capability 

 

Do not ground the dimming wire. This is a 

return signal and is critical for dimming. 

 

When possible, route dimming wires away 

from AC lines 

 

Use connections with properly sized 

connectors. 

 

Eliminate excess wire between fixtures. Line 

length will cause voltage drop. 

 

Number of fixtures that can be daisy-chained 

depends on the following factors: dimming 
current, current requirements for driver, 

length of wire, quality of connection, and 

gauge of wire  

 

Verify dimming capability via a “test bed” with 
the number of actual fixtures, wire length, 

connectors, and wire gauge 

 
 
INSTALLING WIRES 

Use a small screw driver inside the terminal block 

release mechanism to insert and release wires in the 

terminal block 
 

 