![Synapse DIM10-250-11 Скачать руководство пользователя страница 1](http://html1.mh-extra.com/html/synapse/dim10-250-11/dim10-250-11_installation-manual_1420466001.webp)
DOC-1000089-B-1
SPECIFICATIONS
•
Relay Max Switched Circuit: Zero Cross, 5A
•
Dim Control Max Load:
20 mA Source/50 mA Sink
•
Radio Frequency: 2.4 GHz (IEEE 802.15.4)
•
RF Transmission Output Power:
+20dBM
•
Operating Temperature:
-40 to +70 C
•
Operating Humidity: 10 to 90%, non-condensing
•
Configuration/Programming: Stored in non-volatile
memory
•
Dimensions: 8.2L x 2.3W X 1.3H in
(209 X 59 X 33 m)
•
Enclosure Type: Galvanneal steel, powder-coated
white
CAUTION
•
DIM10-250-11 controllers must be installed in
accordance with national, state, and local
electrical codes and requirements
•
All work must be performed by qualified
personnel
•
Disconnect all power before installation or
service
•
Metal conduit connector must be grounded
•
The switched output
(LOAD)
is energized by
default at power up
•
Applying excessive force to the terminal blocks
may result in its failure.
NEEDED MATERIALS
•
50 OHM Terminator plug RP-SMA:
Part
Number 132360RP from Amphenol
•
Wiring Connectors:
All existing wiring
connectors must be replaced with new UL
listed wiring connectors that are correctly
sized for the application and the number and
the size of the electrical conductors.
ATTACHING THE TERMINATOR TO THE
BULKHEAD
Make sure the power is off. Attach the 50 OHM
Terminator to the RP-SMA bulkhead hand tight. Keep
the 50 OHM Terminator on the bulkhead at all times,
until the antenna replaces the 50 OHM Terminator.
When installing the device, the technician must be
grounded with a proper ground strap.
ATTACHING THE ANTENNA
When it is time to attach the antenna, touch a
grounded surface, remove the 50 OHM Terminator and
screw on the antenna tightly. Tighten a 1/4 turn with a
pair of needle nose pliers. Do not overtighten or the RF
pin in the bulkhead will crack, creating poor RF link
quality.
MOUNTING
It is critical to the performance of this device that the
antenna be oriented vertically. It must point straight up
or down for proper operation. When installing the
DIM10-250-11 in an enclosure, antenna position must
be considered in order to provide optimum wireless
signal strength. For best transmission, all antennas
should be oriented in the same direction.
NOTE: See the DIM10-250-11 mounting template for
assistance.
NOTE: Mount in an LED Fixture or Troffer.
Option A.
For standard installation: place the light
controller in the desired location and secure it
using (4) #8 screws. Prior to permanently
mounting it, make sure the antenna points
directly upward or downward and is free of
any metal objects within 12 in. of the antenna
(Figure 1).
Option B.
For installation in a light pole: hang the light
controller with an appropriate cable hook, by
using the cable hook hole at either end of the
device (Figure 2).
WARNING AND CAUTIONS:
•
TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER
AT CIRCUIT
BREAKER OR FUSE AND TEST THAT POWER IS OFF BEFORE WIRING!
•
Risk of Electric Shock -
More than one disconnect switch may be required to
de-energize the equipment before servicing.
•
To be installed and/or used in accordance with appropriate electrical codes and
regulations.
•
If you are unsure about any part of these instructions, consult an electrician;
all work should be performed by qualified personnel
•
Use this device with copper or copper clad wire only.
DIM10-250-11 Lighting Controller
0-10V CONTROL, 2 ANALOG INPUTS
Load Ratings: 5A @ 100-277VAC (+/- 10%), 50/60 Hz
Operating Temperature: -40 to +70 C / Operating Humidity: 10 to 90%, non-condensing
WARNING AND CAUTIONS:
•
Disconnect power at circuit breaker or fuse when servicing, installing or
removing fixture or changing lamps.
•
Switched output is energized by default at power up
•
Mounting:
It is critical to the performance of this device that the antenna be
oriented vertically. It must point straight up or down for proper operation.
•
Wiring Connectors:
All existing wiring connectors must be replaced with new
UL listed wiring connectors. All wiring connectors must be correctly sized for
the application and the number and the size of the electrical conductors.
INSTALLATION GUIDE