Issue 2: Sep 99
TMSL 097-44018-26
Page 153
Table F. Alarm/Event Summary
<aid>
<condtype>
<conddescr>
Severity
Service
Affecting
Notes:
1. The severities in this table are defined as follows:
MN
= minor alarm
SC
= standing condition
MJ
= major alarm
TC
= transient condition
NA
= not alarmed
2. The service-affecting states are: service affecting (SA) and nonservice affecting (NSA).
3. Up to 6 minutes may be required to detect and report an unequipped condition (UNEQUIPPED: IMPROPER
CARD REMOVAL OR COMM FAILURE) from a GTI or an LTI card. This condition may be caused by card
removal, cable removal, or loss of power to the LPR shelf.
4. An asterisk (*) next to a severity indicates the following:
• The severity can be changed using the SET-ATTR-PORT command
• The severity shown is the factory setting
5. A word enclosed in brackets [ ] may or may not appear as part of the <conddescr>.
6. The IS-NR-STBY condtype for TO cards applies to TO-EA, EA10, EA20, EA10M, EA20M cards only.
CLK-x
(x = 1–2)
ACTIVE
CLOCK IS SUPPLYING SIGNAL
SC
NSA
DRIFT
INPUT IS DRIFTING
MN
NSA
FREERUN
CLOCK FREERUNNING
SC
NSA
HOLDOVER
CLOCK IN HOLDOVER
MN
NSA
INACTIVE
CLOCK IS NOT SUPPLYING SIGNAL
SC
NSA
IS-NR-ACT
IN-SERVICE NORMAL-ACTIVE
SC
NSA
LOCKED
CLOCK CONVERGED ON REFERENCE INPUT
SC
NSA
NOT-LOCKED
CLOCK NOT CONVERGED ON REFERENCE
INPUT
SC
NSA
OOS-MT
OUT-OF-SERVICE MAINTENANCE
SC
NSA
OOS-MT-FLT
OUT-OF-SERVICE MAINTENANCE-FAILED
MJ/
MN
SA
TOLERANCE
SYSTEM INPUT TO CLOCK OUT OF TOLERANCE
MN
NSA
UNEQUIPPED
IMPROPER CARD REMOVAL
MN
NSA
DCIM-x
(x = 1–2)
ACTIVE
CARD IS SUPPLYING A SIGNAL TO THE
CLOCK(S)
SC
NSA
ALL-REF
LOSS OF ALL EXTERNAL INPUT REFERENCES
MJ
SA
CLOCK-x
(x = 1–2)
LOSS OF CLOCK SIGNAL
MN
NSA
FAIL
CARD FAIL:CLOCK SYNTHESIZER FAILURE
MJ
SA
FAIL
CARD FAIL: FRAMER FAILURE
MJ
SA
INACTIVE
CARD IS NOT SUPPLYING A SIGNAL TO THE
CLOCK(S)
SC
NSA