DS1 and E1 Input Module Default Settings
424
SSU-2000 User’s Guide
12713020-002-2 Revision D – April 2004
DS1 and E1 Input Module Default Settings
The DS1 Input Module and E1 Input modules maintain factory default and current
user configuration information in nonvolatile memory. This information is retrieved at
power up and is modified by commands from the Communications module.
When the current user configuration cannot be used, the Input module settings
automatically revert to factory defaults.
lists factory default settings and
ranges for all DS1 Input module or E1 Input module software parameters.
Table E-4. DS1 and E1 Input Module Default Configuration
Configuration Setting
Factory Default
Range
Input Frequency (for
unframed signals)
1.544 for DS1 Input module
2.048 MHz for E1 Input module
1 MHz, 1.544 MHz, 2.048
MHz, 5 MHz, 10 MHz
Framing Type
ESF for DS1 Input module
CCS for E1 Input module
D4 or ESF for DS1 Input
Module
CAS or CCS for E1 Input
Module
Zero Suppression
On
On/Off
CRC
Off
On/Off
SSM
Off
On/Off
Provisioned PQL
4 for DS1 Input module
Note:
PQL 4=STU
4 for E1 Input Module
2,3,4,5,6, or 8
Priority
0
0 to 10 (0 = Monitor)
E1 SSM Bit Position
8 (Not applicable for DS1 Input
Module)
4 to 8
Cesium Fault Nominal
Off
Low/High/Off
Gain
Off
On or Off (20 dB)
Input Signal Error Limit
(LOS, AIS, OOF, BPV,
CRC)
Defaults are:
LOS:
10 seconds (Err Cnt)
5 seconds (Clr Cnt)
AIS:
12 seconds (Err Cnt)
5 seconds (Clr Cnt)
OOF:
14 seconds (Err Cnt)
5 seconds (Clr Cnt)
BPV, CRC:
16 seconds (Err Cnt)
5 seconds (Clr Cnt)
1 to 100 for LOS and AIS
1 to 10,000 for BPV, CRC and
OOF
Содержание SDU-2000
Страница 12: ...12 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 18: ...18 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 142: ...Clock Module Reference Data Communications Module 142 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 172: ...Input Module Reference Data Input Adapter Panels 172 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 222: ...Output Module Reference Data Output Adapter Panels 222 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 390: ...SNMP Protocol 390 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 420: ...I O Connector Grounding 420 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 434: ...User Changes to Factory Defaults 434 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...