12713020-002-2 Revision D – April 2004
SSU-2000 User’s Guide 213
Output Module Reference Data
Line Retiming Unit (LRU)
Installing a CTA in the SDU-2000
The SDU-2000 shelf has I/O interface connections on the rear panel for connecting
the SDU-2000 to the corresponding I/O adapter panels. The LRM I/O connections
are made from the 50-pin Micro-D female connectors on the rear panel of the
SDU-2000, through the CTA, and to the adapter panel using the appropriate cable.
Connectors J1 through J14 are labeled OUT-1 through OUT-14 and each connector
is associated with a specific I/O plug-in module slot. Symmetricom recommends
using connectors J5 through J12, which correspond to module slots A5 through A12
respectively (see
).
Figure 8-22. Installing the Cut-Through Assembly in the SDU-2000
Use the following steps to install the Cut-Through Assembly on an SDU-2000. Refer
to
for a description of the SSU-2000 and CTA I/O connector pin functions
and to
for pin orientation.
Содержание SDU-2000
Страница 12: ...12 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 18: ...18 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 142: ...Clock Module Reference Data Communications Module 142 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 172: ...Input Module Reference Data Input Adapter Panels 172 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 222: ...Output Module Reference Data Output Adapter Panels 222 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 390: ...SNMP Protocol 390 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 420: ...I O Connector Grounding 420 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Страница 434: ...User Changes to Factory Defaults 434 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...