Chapter 4 Command Reference
Input Port Status and Setup Commands
4-12
User’s Guide
INPut:SELect?
This query indicates which input is selected as the source input.
Returns single character, A or B.
INPut:SELect:AUTO 0 | 1
This command enables or disables the automatic input switching
feature.
This setting is stored in non-volatile memory.
Use 0 (OFF) to disable auto-switching.
Use 1 (ON) to enable auto-switching.
INPut:SELect:AUTO?
This query returns the state of the automatic input switching feature.
Returns single character, 0 or 1.
A value of 0 indicates disabled.
A value of 1 indicates enabled.
INPut:SELect:DEFault A | B
This command selects the default input channel (or port) to be used at
powerup.
This setting has no impact on auto-switching and does not affect the
current input channel selection.
This setting is stored in non-volatile memory.
Use A or B to select the appropriate power-up default input port.
INPut:SELect:DEFault?
This query returns default input channel (or port) to be used at
powerup.
Returns single character, A or B.
Содержание 58502A
Страница 10: ...In This Guide x User s Guide ...
Страница 11: ...1 Getting Started ...
Страница 27: ...2 Performance Tests Verifying Specifications ...
Страница 29: ...Chapter 2 Performance Tests Introduction User s Guide 2 3 ...
Страница 47: ...3 Features and Functions ...
Страница 59: ...4 Command Reference ...
Страница 73: ...5 Functional Description ...
Страница 78: ...Chapter 5 Functional Description Functional Block Description of the 58502A 5 6 User s Guide ...
Страница 79: ...6 Service ...
Страница 81: ...7 Specifications ...
Страница 84: ...Chapter 7 Specifications Introduction 7 4 User s Guide ...