ground the TXD-wires (PIN 4 and PIN 6) with PIN 7 and 8.
4.3.2
Recommended Cable Types HARTING Push Pull Connector
If the station is delivered with a HARTING Push Pull connector following type of cable should
be considered for assembling:
HARTING RJ Industrial
®
Ethernet Shielded Twisted Pair Standard Cable, AWG 22 solid,
according Category 5 cabling standard (ISO/IEC 11801:2002)
HARTING RJ Industrial
®
Ethernet Shielded Twisted Pair Trailing Cable, AWG 22/7
stranded, according Category 5 cabling standard (ISO/IEC 11801:2002)
Transmission characteristics according Category 5 ISO/IEC 801:2002 and EN 50173-1:
Technical Data: HARTING Push Pull Connector
Wire gauge data
AWG 22
– 24 stranded
AWG 22
– 23 solid
Wire isolation
Max. 1.6 mm Ø
Cable diameter
6.5 mm
– 7.2 mm
The assembly instruction of the HARTING Push Pull Connector is delivered with the product.
4.4 Connector box
The connection box is configured with 14 clamps. Therefore the connector box can be used
either for power supply or for relays.
Figure 13
– Connector box
Connection Box
Size (LxWxH)
125mm x 80mm x 57mm (without cable bushing)
Position mounting holes
4 x diameter 4.3mm; 52 x 113mm
Clamps
Wago 870-911 for cable diameter 0.08 till 2,5mm² ( till 4mm² if
flexible cables)