2880 North Plaza Drive • Rapid City, SD 57702
(800) 843-8848 • (605) 348-5580 • FAX (605) 348-5685
www.symcominc.com • email: [email protected]
Specifications
Line Voltage Ranges
................................95 to 120 (100V Model)
....................................................................190 to 240 (200V Model)
....................................................................380 to 480 (400V Model)
Frequency
................................................50 or 60 Hz
Low Voltage (% of set point)
•Trip ............................................................90%
•Reset ........................................................93%
Trip Delay Time
•Low Voltage or Optional High Voltage ......4 seconds
Restart Delay Time
•After a Fault ..............................................2 seconds
•After a Complete Power Loss ..................2 seconds
Output Contact Rating (Pilot Duty)
•SPDT ........................................................480 VA @ 240 VAC
or 10A @240 VAC Gen. Purpose
Transient Protection (Internal)
................IEC 1000-4-5; 1995 to ±4kV
Power Consumption
................................5 Watts (Max.)
Weight
......................................................9 oz.
Socket Available
......................................The same 600V socket can be
Model Number OT08
surface mounted or installed on
(UL Rating 600V)
Din Rail
Specifications
•
Operating Points
•
Special Options
9/02
SymCom warrants its microcontroller-based products against defects in material or workmanship for a period of
five (5) years from the date of manufacture. All other products manufactured by SymCom shall be warranted
against defects in material and workmanship for a period of two (2) years from the date of manufacture.
For complete information on warranty, liability, terms, returns, and cancellations, please refer to the SymCom
Terms and Conditions of Sale document.
Model 201-SP
Model 201-SP-T
Model 201-SP-T01
Single Phase
Voltage Monitor