SymCom 777-TS Скачать руководство пользователя страница 5

 

5 - 

 

1/05 

 

RD1 

RD1 (restart delay one) is the rapid-cycle timer in seconds. This timer is initiated when 
power is first applied to the unit. If voltages are within the programmed limits and no SP 
(single-phase) or RP (reverse-phase) condition exists when power is applied to the 
device, the output relay will energize (the NO will close and the NC will open) as soon as 
RD1 expires). Typically, this is set to 20-30 seconds. This will provide adequate protection 
for successive power outages or short cycling caused by other motor controls. This timer 
is also initiated when another control shuts the motor off (current goes to zero). If the user 
does not want the unit’s relay to de-energize when another control shuts the motor off, 
then RD1 should be set to zero. This will also ensure that when an alarm circuit is used, 
an alarm will sound only when there is a true problem or when power is lost. 

 

RD2 

-  

RD2 (restart delay two) is the restart timer, in minutes, used when the unit has shut off 
due to a current unbalance, current single phasing, or an overload condition. This timer is 
known as a motor cool-down timer. A setting of 5-10 minutes will give most motors 
adequate time to cool down after an overload condition. The motor manufacturer should 
be contacted for an exact value. 

 

RD3 

-  

RD3 (restart delay three) is the restart timer, in minutes, used after an undercurrent trip. It 
is also known as a dry-well recovery timer in pumping applications. This would be the time 
it takes a well to recharge after pumping dry. This setting varies widely from application to 
application and there is no typical setting.   

 

#RU/ADDR 

- The #RU/ADDR is a dual function setting. The #RU settings cover from the 7 o’clock 

position to the 11 o’clock position. ADDR settings start after the 11 o’clock position.  

 

#RU (# of restarts after an undercurrent) is the number of restarts after an undercurrent 
trip condition before the unit locks and requires a manual restart. This counter will be 
cleared one minute after start-up if the unit does not trip again on UC. #RU can be set to 
0, 1, 2, 3, 4, or A. A setting of zero means no automatic restarts after an undercurrent. A 
setting of “A” means the unit will always automatically restart after an undercurrent.

 

 

ADDR (address) is the RS-485 address of the particular device. This is only used when 
communicating with an RM-2000 (set ADDR=A01), a PLC, or PC. The ADDR can be 
programmed from A01-A99. 

 

#RF 

-  

#RF (# of restarts after a fault) is the number of restarts allowed after a current unbalance, 
current single phasing, or an overload condition. A setting, which includes an “oc” prefix, 
will include overcurrent in the number of successive restarts. If “oc” is not a prefix to the 
programmed setting, the unit will require a manual restart after an overcurrent. A setting of 
zero means the unit will not try to restart after a CUB, OC, or SP. A setting of “ocA” means 
the unit will always try to restart after a CUB, OC, or SP. 

 

UCTD 

-   UCTD (undercurrent trip delay) is the amount of time, in seconds, the unit will allow the 

motor to run in an undercurrent situation before de-energizing its relay. Typically, UCTD is 
set to 2-4 seconds.  

 
GF 

-  

GF (ground fault) is the maximum allowable current, which can flow to ground before the 
unit de-energizes its relay. This is a residual, class II ground fault system and should not 
be used for personnel safety. A typical setting for this is 10%-20% of the motor full load 
current. The real GF current level is programmed into the unit. The GF test procedure on 
the last page of the installation instructions must be conducted before the device is 
brought online. 

 

Содержание 777-TS

Страница 1: ...perages from 26 90 amps insert the motor conductors through the holes marked A B and C Make certain the conductor through each hole corresponds to the right motor conductor i e the A phase conductor s...

Страница 2: ...XTERNAL CTs REQUIRED SEE FIGURE 2 FOR WIRING EXTERNAL CTs 91 110 5 100 100 5 111 160 5 150 150 5 161 220 5 200 200 5 221 320 5 300 300 5 321 420 5 400 400 5 421 520 5 500 500 5 521 620 5 600 600 5 621...

Страница 3: ...3 1 05 Figure 2 Typical Wiring Diagram Using External CTs Figure 3 Looping Example Showing Three Conductors MULT 3 from table 1 No other necessary connections are shown...

Страница 4: ...efore the maximum deviation from the average is 5 3 The VUB is then 5 3 208 3 x 100 2 5 The TS setting allows the user to turn the temperature sensor trip function on or off MULT MULT multiplier setti...

Страница 5: ...ck position to the 11 o clock position ADDR settings start after the 11 o clock position RU of restarts after an undercurrent is the number of restarts after an undercurrent trip condition before the...

Страница 6: ...ntil all parameters are programmed OPERATION The relay operation of the Model 777 TS is designed to be fail safe This means when everything is within the limits programmed into the unit the relay will...

Страница 7: ...15 Specialized applications 20 Standard Trip Most NEMA rated general purpose motors will be protected by this setting 30 Slow Trip Motors with long acceleration times 10 seconds or high inertia loads...

Страница 8: ...n e g worn bearings oc should not be included in the RF setting so that a manual reset after an overload fault is required A RF 1 will give the system 1 chance to recover from an unbalance or single p...

Страница 9: ...ual line line voltage The display is also used for programming the operating parameters of the device The display also identifies what caused the unit to de energize its relay or what is keeping the u...

Страница 10: ...vides isolation signal conditioning for compatibility with Modbus RTU and RS 485 networks and provides terminals for terminating the shielded communications cable Up to 99 units can be installed on on...

Страница 11: ...meter value The incoming voltage is not within the limits programmed in the VUB HV and LV settings Adjust the DISPLAY PROGRAM switch to read the incoming line voltage values Correct the incoming power...

Страница 12: ...irect Trip Times Those not shown have user selectable trip times Ground Fault Trip Time 101 200 of Setpoint 201 300 of Setpoint 301 400 of Setpoint 401 or Greater Trip time 8 seconds 1 second 4 second...

Страница 13: ...C Undercurrent Threshold 0 10 98A MULT or 40 100 of CT Primary CUB Current Unbalance Threshold 2 25 or 999 TC Overcurrent Trip Class 5 J5 10 J10 15 J15 20 J20 30 J30 RD1 Rapid Cycle Timer 0 2 500 Seco...

Страница 14: ...button 4 Turn MODE SELECT switch to RUN The program is now locked but all settings can be viewed The unit can be unlocked by following the same steps except adjust the DISPLAY PROGRAM knob to unL in...

Страница 15: ...ng s electrical installation in order to be available to the authority having jurisdiction 9 Confirm programmed parameters and proceed with installation instructions GROUND FAULT TEST RESULTS Date Per...

Страница 16: ...16 1 05 Visit our website at www symcominc com for our complete catalog and new product listings 2880 North Plaza Drive Rapid City SD 57702 800 843 8848...

Отзывы: