To write the configured inputs and outputs into the inverter select "Write Project Data (F5)".
8.0 Example of Remote Control Element
9.0 Status Display and Error Messages
•
The current rotational speed is displayed on a 3 digit 7 segment LED.
•
The status LEDs "READY", "RPM 0", "RPM OK" and ">100%" give information on the current spindle status.
•
The red LED ">100%" indicates generally an error or as an indicator for an overload condition.
•
In case of need of more detailed information about an error, the errors can be evaluated with the help of
the software SFU-Terminal.
•
At the bar graph display the current load state of the inverter is displayed.
•
Errors are displayed as error code in the display. If there are more than one errors present, the error
codes are displayed sequentially.
E30
Overload switch off
E31
Over temperature of inverter
E32
Overtemperature of spindle
E33
Overtemperature of inverter or spindle
E34
DC-link over voltage
E35
DC-link under voltage off
E36
DC-link Under Voltage stop
E37
Over current trip -> power stage off
E38
Emergency-stop input locked
E39
No spindle or spindle cable defective
E40
Timeout serial interface
E41
Spindle characteristic invalid or corrupted
E42
Error back energy (AC) / spindle stall (DC) -> power stage off