Page | 19
06:
ECO voltage range setting
INTERFACE
SETTING
Parameter 1 & 2: Set the acceptable high voltage
point and low voltage point for ECO & AECO
mode.
Press the Down key or Up key.
HLS: High loss voltage in ECO mode.
For
200/208/220/230/240 VAC
models, the setting
range are from
+7V to +24V
of the nominal voltage
(Default: +12V).
For
100/110/115/120/127 VAC
models, the setting
range is from
+3V to +12V
of the nominal voltage
(Default: +6V).
LLS: Low loss voltage in ECO mode.
For
200/208/220/230/240 VAC
models, the setting
range is from
-7V to -24V
of the nominal voltage.
(Default: -12V).
For
100/110/115/120/127 VAC
models, the setting
range is from
-3V to -12V
of the nominal voltage
(Default: -6V).
07:
Bypass mode enable/disable.
INTERFACE
SETTING
Parameter2: Enable or disable Bypass function.
ENA:
Bypass mode
enable.
DIS: Bypass mode disable (Default).
08:
Bypass voltage range setting.
INTERFACE
SETTING
Parameter 1 & 2: Set the acceptable high voltage
point and acceptable low voltage point for
Bypass mode.
Press the Down key or Up key to set.
HLS: Bypass high voltage point.
For
200/208/220/230/240 VAC
models:
230-264: setting the high voltage point from