Operation Instruction of AQUAFLOW Series Solar Pumping Inverter
Operation Control
29
2. Conduct parameter setting for the motor
(a) Setting S00.01=0. Command code channel is keyboard manual mode instruction.
(b) Set water pump nameplate parameters: S02.01 motor rated power value; S02.02 motor rated
power value; S02.04 motor rated voltage value; S02.05 motor rated current value.
(c) After finishing parameter setting of water pump, set S00.01=1. The operation code channel is
altered as original automatic mode instruction.
See the following figure. The settings of nameplate parameters of water pump are listed as
follows (for example: 7.5KW inverter drives 5.5KW water pump):
Operation
Description
Display
Initial status:
non-historical data
display
↓
↓
↓
↓
↓
↓
Enter the main
parameter
modification interface
for long press 2s
Represent S00 parameter group
Press OK key to enter
the branch menu
Represent S00.00
Press UP key to view
the S00.01
Represent S00.01
Press OK key to enter
the S00.01(the factory
set is 1)
Represent 1
Edited it to
0(controlled by
keyboard)
Represent 0
Press to save the
parameter value and
display the next code
number
Represent S00.03